Altech UL1077
TR11 Series
E209569 up to 12 Amps
UL1077 Recognized Supplementary Protector/ Circuit Breaker for Equipment
Applications: Protection of single phase Motors, Transformers, UPS, Power strips, Solenoids etc., against damage due to overcurrent conditions.
Current Rating Rated Voltage Initial insulation resistance Dielectric strength Overload Switching Capacity Maximum Breaking Capacity Power Loss Operating Temperature Operational Life at 2xIn Limited short circuit current Terminals Applicable Standards Approvals Accessories
0.5 -16.0A 240V AC, 50/60Hz, 32V DC / 24V DC (VDE)
(As per EN 60934) > 100 M ohms. (As per EN 60934) 1.5 KV for One minute. 6 In ~ up to 9.0A (As per EN 60934) 4 In - up to 12.0A 60A Max. ~ from 10.0A to 12.0A 60A Max. - from 10.0A to 12.0A 8x In for 6.0A 1 - 2 Watts Maximum 60°C Ambient 1000 Cycles 1000 Amps PC 1
Operating Characteristic
(min) 60 30 20 10 5 1 (S) 50 20 10 5 2 1 Trip time 0.5 0.2 0.1 1.05 1.32 2 3 45 8 10
0.25” Quick connect EN 60934, CSA 22.2 No. 235, UL-1077 up to 16.0 A upto 12.0A Dust Cover, DC-TR11 C (see page 14)
Time Current Characteristics: The standard characteristic is valid for ambient temperatures of +23°C. If the device is to be used in an ambient temperature other than +23°C, allowances must be made when selecting the current rating according to the following guidelines:
Ambient temp. °C Correction Factor Example : -20 -5 0 +10 0.96 : : : : : +20 1 +30 1.05 +40 1.12 +50 1.2 +60 1.3 0.8 0.88 0.9
Normal Continuous Current Ambient Temperature Correction Factor Recommended Current Rating Select the nearest
1.8A 40°C 1.12 1.8 x 1.12 = 2.016 2.0A
Multiple of Rated Current
Rated current Ambient Temperature
6A 23°C
16
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
Application Examples: Protection of single phase Motors, Transformers, UPS, Power strips, Solenoids etc., against damage due to overcurrent conditions.
TR-11 Characteristics & Mounting Options
E209569 Type/ Cat. No. TR-11CX630.5A TR-11CX630.9A TR-11CX631A TR-11CX631.2A TR-11CX631.5A TR-11CX631.8A TR-11CX632A TR-11CX632.2A TR-11CX632.5A TR-11CX632.7A TR-11CX633A TR-11CX633.3A TR-11CX634A TR-11CX635A TR-11CX636A TR-11CY636.5A TR-11CY637A TR-11CY638A TR-11CY639A TR-11CY6310A TR-11CY6312A TR-11CY6315A TR-11CY6316A Type/ Cat. No. up to 12 Amps Rated Current Type/ Cat. No.
Standard Pack: 10 Weight: 0.27kg (0.6 lb.)
Central Mounting
Rated Current 0.5A 0.9A 1.0A 1.2A 1.5A 1.8A 2.0A 2.2A 2.5A 2.7A 3A 3.3A 4A 5A 6A 6.5A 7A 8A 9A 10A 12A 15A 16A Rated Current
Standard Pack: 10 Weight: 0.27kg (0.6 lb.)
Wing Clips*
Rated Current
Type/ Cat. No.
Standard Pack: 10 Weight: 0.27kg (0.6 lb.)
Snap Fitting*
Standard Pack: 10 Weight: 0.27kg (0.6 lb.)
Integral Mounting*
* SPECIAL ORDER ONLY. Contact Altech for more details.
PCB Mounting and additional Shunt Terminal available, please contact Altech.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
Altech UL1077
17
Altech UL1077
TR-11 Dimensions & Mounting Options
Central Mounting
DIA 4
A/F 13
MAXIMUM TORQUE 0.5 Nm
10
9
M10 X 1
13.3/14.5
10.8/12
6
PANEL CUTOUT
19 3
11
27.5
10.2
9
7
Wing Clips
0.8
15
9.4
8.7
10.2
Alternate 1
DIA 4 14.5 DIA 12 12 3
Alternate 2
PANEL CUTOUT
15 9+0.1 15.5
27.5
11
19 7
12.7 15.2 13.9 +0.1
0.8
15
Snap Fitting
DIA 4 11.2
13
12
8.5
PANEL CUTOUT
25.6 21.7 X +0.1 11.3 +0.1
14 11 2
0.8
15
Integral Mounting
DIA 4
10
9 11.2
11
27.5
19
0.8 15
Dust Cover
18 2
M10 X 1
DIA 16
Cover is suitable for central mounting type circuit breaker to provide dust & splash protection (IP 54). Type/Cat. No.: DC TR11 C
Dimensions in mm (to convert to inches multiply by 0.03937)
18
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
7
85
.2
7
Ø1
5 .5