Embedded Power for Business-Critical Continuity
NFS40 Medical Series
Single & Triple Output
Total Power: 40 - 50W Input Voltage: 85 - 264 VAC 120 - 370 VDC # of Outputs: Single, triple
Rev.06.9.09_118 NFS40 Medical 1 of 4
Special Features
• 5.0 x 3.0 x 1.2 inch package (1U applications) • Industry standard package • Overvoltage and short circuit protection • 40 W with free air convection • EN55022, EN55011 conducted noise level A • UL, VDE and CSA safety approvals • Available RoHS compliant • 2 year warranty
Electrical Specifications
Output
Voltage adjustability: Line regulation: LL to HL, FL Load regulation: FL to NL Transient response: Temperature coefficient: Overvoltage protection: Output power limit: Short circuit protection: +5 V output on triples Vout on singles Main output Auxiliary outputs Main output Auxiliary outputs +5 V (1.5 - 3 A step) All outputs +5 V output Primary power limited Single outputs Multiple outputs ± 5.0% ± 5.0% ± 0.2% ± 1.0% ± 2.0% ± 5.0% ± 120 mV max. dev. 500 µs recovery ±0.02%/°C 6.25 ± 0.75 Vout 90 W input power limit Continuous Short term 85 - 264 Vac 120 - 370 Vdc 47 - 440 Hz 110 Vac, 60 Hz, cold start 230 Vac, 50 Hz, cold start 110 Vac, 60 Hz 230 Vac, 50 Hz 10 A 22 A 18 µA max. 28 µA max.
Input
Input voltage range:
Safety
• UL2601 • CSA22.2 No. 125 • IEC601/VDE0750
Input frequency range: Input surge current: Safety ground leakage current:
Embedded Power for Business-Critical Continuity
Rev.06.9.09_118 NFS40 Medical of 4
Electrical Specifications Continued
All specifications are typical at nominal input, full load at 25 °C unless otherwise stated
EMC Charateristics
Conducted emissions: Radiated emissions: ESD air: ESD contact: Surge: Fast transients: Radiated immunity: Conducted immunity: EN55022, FCC part 15 EN55022, FCC part 15 EN61000-4-2, level 3 EN61000-4-2, level 4 EN61000-4-5, level 3 EN61000-4-4, level 3 EN61000-4-3, level 3 EN61000-4-6, level 3 110 Vac 230 Vac 110 Vac, 230 Vac Input/output Input/chassis Level A Level A Perf. criteria 1 Perf. criteria 1 Perf. criteria 1 Perf. criteria 1 Perf. criteria 2 Perf. criteria 2 18 ms 132 ms 70% typical 4000 Vac 1500 Vac 20 - 110 kHz
General Specifications
Hold-up time: Efficiency: Isolation voltage: Switching frequency: Approvals and standards: (See Note 12) Weight: MTBF demonstrated:
VDE0750, IEC601, EN60601-1, UL2601, CSA C22.2 No. 125 270 g (9.6 oz) MIL-HDBK-217E 170,000 hours
Environmental Specifications
Thermal performance: Operating, see curve Non-operating 0 - 50 °C ambient temperature, convection cooled 0 - 50 °C ambient temperature +50 °C to +70 °C ambient Peak (30 seconds) Relative humidity: Altitude: Vibration (See Note 11): Non-condensing Operating Non-operating 5 - 500 Hz 0° C to +70 °C -40 °C to +85 °C 40 W 50 W @ 20 CFM Derate linearly to 50% load 60 W 5 to 95% RH 10,000 feet max. 40,000 feet max. 0.75 G peak
Embedded Power for Business-Critical Continuity
Ordering Information
Ordering Information
Output Voltage +5.1 V (VA) +12 V (VB) –12 V (6) +5.1 V (VA) +15 V (VB) -15 V (6) 12 V 24 V
(7)
Rev.06.9.09_118 NFS40 Medical of 4
Output Currents Conv Max 3A 2A 0.35 A 3A 2A 0.35 A 3.3 A 2.6 A 1.6 A 4A 0.35 A 0.35 A
(1)
20 CFM Max. 5A 2A 0A 5A 2A 0.5 A 4A 3.3 A 2A 7A 1A 1A
(2)
Peak 7A 3A --7A
(3)
Ripple (4) PK-PK 50 mV 120 mV 120 mV 50 mV 150 mV 150 mV 120 mV 150 mV 240 mV 50 mV 120 mV 120 mV
Total Regulation (5) ± 2.0% ± 5.0% ± 5.0% ± 2.0% ± 10%/-3.0% ± 5.0% ± 2.0% ± 2.0% ± 2.0% ± 2.0% ± 5.0% ± 5.0%
Model Numbers (13, 14) NFS40-7908J
NFS40-7910J
2.5 A --5A 4A 2.5 A 5A 0.5 A 0.5 A
NFS40-7912J NFS40-7915J NFS40-7924J NFS40-7928J
15 V (7)
(7)
+5.1 V +12 V –12 V Notes
1 2 3 4 5
6 7 8 9 10 11 12 13 14
Natural convection cooling, 40 W maximum. Forced air, 20 CFM at 1 atmosphere, 50 W maximum. Peak output current lasting less than 30 seconds with duty cycle less than 10%. During peak loading, outputs may go outside of total regulation limits. Peak total power must not exceed 60 W. 50 MHz bandwidth, peak-to-peak, measured differentially. Total regulation is defined as the static output regulation at 25 °C, including initial tolerance, load currents within stated limits, and output voltages adjusted to their factory settings. Also, 0.25 ² IA / IB ² 5.0 to maintain stated regulation. A minimum load of 0.5 A is required on the +5 V output to obtain full current from the negative output. Single output models have floating outputs which may be referenced as either positive or negative. Derating curve is application specific for ambient temperatures > 50 °C, for optimum reliability no part of the heatsink should exceed 120 °C and no semiconductor case temperature should exceed 130 °C. Caution: Allow a minimum of 1 second after disconnecting the power when making thermal measurements. Although the minimum output current of the NFS40-79XXJ is 0 A, a 4 W minimum load is required to achieve design MTBF. Three orthogonal axes, sweep at 1 octave/min, 5 minute dwell at four major resonances. This product is only for inclusion by professional installers within other equipment and must not be operated as a stand alone product. The ‘J’ suffix indicates that these parts are Pb-free (RoHS 6/6) compliant. NOTICE: Some models do not support all options. Please contact your local Emerson Network Power representative or use the on-line model number search tool at http://www.PowerConversion.com to find a suitable alternative.
AC mating connector
Molex 09-50-3031 or equivalent with Molex 08-50-0105 or equivalent crimp terminal.
DC mating connector
Molex 09-91-0600 or equivalent with Molex 08-50-0164 or equivalent crimp terminal.
Pin Connections
J1 Pin 1 Pin 2 J2 Pin 1 Pin 2 Pin 3 Pin 4 Pin 5 Pin 6 P1 Pin 1
DERATING CURVE Output Power (Watts)
50W 20 CFM FORCED AIR COOLING 40W
-7908J, -7928J AC Line AC Neutral +12 V +5.1 V +5.1 V Return Return -12 V
-7910J AC Line AC Neutral +15 V +5.1 V +5.1 V Return Return -15 V
SINGLES AC Line AC Neutral +Vout +Vout +Vout Return Return Return
Safety Earth Ground
NATURAL CONVECTION COOLING
25W 20W
0C
10C
20C
30C
40C
50C
60C
70C
Embedded Power for Business-Critical Continuity
Mechanical Drawing
0.156 (3.96) Dia. (4 Places) 5.00 (127.00)
Americas
5810 Van Allen Way Carlsbad, CA 92008 USA Telephone: +1 760 930 4600 Facsimile: +1 760 930 0698
Rev.06.9.09_118 NFS40 Medical 4 of 4
NON-METALLIC STAND-OFF (SEE NOTE A)
C5 Q1
MAXIMUM COMPONENT HEIGHT 1.2 inches
Europe (UK)
Waterfront Business Park Merry Hill, Dudley West Midlands, DY5 1LX United Kingdom Telephone: +44 (0) 1384 842 211 Facsimile: +44 (0) 1384 843 355
J1 3.00 (76.2)
~ N ~ L F1 F 3.15A, H 250VAC P1 (SEE NOTE C)
1 T1 J2
2.550 (64.8)
Asia (HK)
14/F, Lu Plaza 2 Wing Yip Street Kwun Tong, Kowloon Hong Kong Telephone: +852 2176 3333 Facsimile: +852 2176 3888
0.22 (5.59) 4.55 (115.8)
For global contact, visit:
www.PowerConversion.com techsupport.embeddedpower @emerson.com
While every precaution has been taken to ensure accuracy and completeness in this literature, Emerson Network Power assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
0.22 (5.59)
ALL DIMENSIONS IN INCHES (mm)
Mechanical Notes
A In order to meet safety requirements, a non-metallic stand-off is mandatory for one hole as specified in the mechanical drawing above. B The ground pad of the mounting hole near P1 allows system grounding through a metal stand-off. C To improve conducted noise, the ground pad of the mounting hole near the output connector should be connected with the ground pad of the mounting hole near P1. Use metal stand-offs attached to a common metal chassis. This connection also significantly attenuates common mode noise. D A standard L-bracket and enclosure kit is available for mounting which contains all screws, connectors and necessary mounting hardware. Order part number NFS40CJ.
Emerson Network Power. The global leader in enabling business-critical continuity. AC Power Connectivity DC Power Embedded Computing Embedded Power Monitoring Outside Plant Power Switching & Controls Precision Cooling Racks & Integrated Cabinets Services Surge Protection EmersonNetworkPower.com
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2009 Emerson Electric Co.