Embedded Power for Business-Critical Continuity
µMP Series
Up to 1200 Watts
Total Power: Up to 1200 Watts Input Voltage: 85 - 264 Vac 120-300 Vdc # of Outputs: Up to 12
MicroMP 1U Multi Output
Rev. 07.18.11_10 µMP Series 1 of 6
Special Features
• Full Medical EN60601 approval • PMBus • High efficiency • Current limit modification (foldback or constant current) • High power density. uMP4: 10.8 W/cu-in uMP1: 15.1 W/cu-in • Intelligent fan (speed control/fault status) • Downloadable GUI from website • uP controlled PFC input with active inrush protection • Optional conformal coating • Industrial temp range (-40 ºC to 70 ºC) • No preload required • Industrial shock/vibration (> 50G’s) • Low cost • IEC or terminal block input • Low profile 1U size
Electrical Specifications
Input
Input range: Frequency: Inrush current: Efficiency: Power Factor: Turn-on time: EMI filter: Leakage current: Radiated EMI: Holdover storage: AC OK: Harmonic distortion: Isolation: Input fuse (internal): Warranty: 47 - 440 Hz 40 A peak max. (soft start) Up to 91% @ full case load
µMP4C shown
85 - 264 Vac, 120 - 350 Vdc (limited to 250 Vac/300 Vdc in medical apps)
0.99 typ. meets EN61000-3-2 (n/a @ 440 Hz) AC on 2 sec for uMP1 and 1.5 sec for uMP4, inhibit/enable 250 ms typical CISPR 22/EN55022 Level “B” 300 µA max. @ 240 Vac for uMP1 and 500 µA max for uMP4; 47 - 63 Hz CISPR 22/EN55022 Level “B” 16.7 ms minimum (independent of input Vac, 0 °C to 50 °C)) Signal goes low indicating loss of AC input. Hold up = Full cycle ride thru (50 Hz) Meets EN61000-3-2 Meets EN60950 and EN60601 uMP1: 16 A/250 V TLAG, uMP4: 10 A / 250 V. (both lines fused) 2 years
Global Inhibit/Enable: TTL, Logic “1” and Logic “0”; fan off when unit is inhibited
Environmental Specifications
Operating temperature:
Safety
• • • • • • • • UL CSA VDE BABT CB CE CCC BSMI UL60950/UL60601-1 CSA22.2 No. 234 Level 5 EN60950/EN60601-1 Compliance to EN60950/EN60601 BS7002 Certificate and report Mark to LVD Approved Approved
-40 ° to 70 °C ambient. Derate each output 2.5% per degree from 50 °C to 70 °C. ( -20 °C start up). Meets full spec after 1/2 load. 10 min warm-up Storage temperature: -40 °C to 85 °C Electromagnetic susceptibility: Designed to meet EN61000-4; 3, -6, -11 Level 3, Level 4 for -2, -4, -5 Humidity: Operating; non-condensing 10% to 95% RH Vibration: MIL-STD-810E > 350,000 hours at full load, one uMP4 case + two modules, Telcordia SR-332 MTBF demonstrated: calculated MTBF Altitude: Up to 10k feet; derate linear to 50% from 10k-30k feet
Embedded Power for Business-Critical Continuity
Output
Factory set point accuracy: ± 1% Margining: Overall regulation: Ripple: ± 3 - 7% nominal analog (single output module only) 0.4% or 30 mV which ever is greater.
Rev. 07.18.11_10 µMP Series 2 of 6
RMS: 0.1% or 10 mV, whichever is greater Pk-Pk: 1.0% or 50 mV, whichever is greater. Bandwidth limited to 20 MHz Dynamic response: < ± 5% or 250 mV, with 50% step load Recovery time: To within 1% in < 300 µsec Reverse voltage protection: 100% of rated output current Thermal protection: (OTP) Remote sense: Single wire parallel: DC OK: Minimum load: Housekeeping standby: Module inhibit: Output/Output isolation: Vout 3V3 Module
0.9 3.3 3.6 40 40 40 36 36 30 25 20 16 13 10 8 7 5 4 TBD 5.96 V 6.32 V 6.8 V 8.8 V 9.2 V 12 V 18 V 20 V 18 V 31 V 38 V TBD TBD TBD 130% 130% 130% 130% 130% 130% 130% 130% 130% 130% 130% 130% 130% 130% 130% 160% 160% 160% 160% 160% 160% 160% 160% 160% 160% 160% 160% 200% 160% 200% 150 250 250 250 250 300 300 600 750 600 1200 1500 1400 2400 3000 ± 250 ± 250 ± 250 ± 250 ± 250 ± 300 ± 300 ± 600 ± 750 ± 600 ± 1200 ± 1500 ± 1400 ± 2400 ± 3000
All outputs disabled when internal temp exceeds safe operating range. Up to 0.5 V total drop (not available on triple output module) Current share to within 5% of total rated current ± 5% of nominal. Not required 5 Vdc @ 1.0 A max. present whenever AC input is applied Logic - output on with low or open. Different logic options available > 1 Megohm, 500 V Full load (A) OVP trip max (V) OCP trip typ (Iout%) SCP trip max (Iout%) Overshoot (max mV) Peak Deviation (max mV)
5 V Module
3.2 5 6
12 V Module
6 12 15
24 V Module
12 24 30
48 V Module
28 48 60
Case Line-Up
Case µMP4 - 4 Slot µMP1 - 6 Slot Max Output 400 W - 600 W 1000 W - 1200 W Dimensions 256.9±0.8 x 88.9±0.5 x 40.0±0.7 (10.11” x 3.5” x 1.57”) 256.9±0.8 x 127±0.5 x 40.0±0.5 (10.11” x 5” x 1.57”) Connections IEC/Terminal Block IEC/Terminal Block Max Current Amps 9.91 13.87
Output Module Line-Up
Output Range (Vdc) 0.9 - 3.6 3.2 - 6.0 6.0 - 15.0 12.0 - 30.0 28.0 - 54.0 5.0 - 28.0 5.0 - 28.0 Max Current (Amps) 40 36 25 13 7 4 4 Max Power (Watts) 144 180 240 240 240 96 96 Module Codes Standard Outputs A, B, C, D - 2, 2.2, 3, 3.3 E, F, G, H - 5, 5, 2, 5.5, 6 I, J, K, L, M, N - 8, 10, 11, 12, 14, 15 O, P, Q, R, S - 18, 20, 24, 28, 30 T, U, V, W, X, Y - 28, 30, 33, 36, 42, 48, 54, 60 Dual Output Module. Each output is rated to 96W (192 Watts total). Wide range is adjustable.
Embedded Power for Business-Critical Continuity
Ordering Info
Case Size Module/Voltage/Option Codes Case Option Codes Software Code
Rev. 07.18.11_10 µMP Series 3 of 6 Hardware Code
µMPXY
Case Size Single - Phase Input where X = 4 = 1.57” x 3.5” x 10”; 400 W - 600 W, 4 Slots 1 = 1.57” x 5” x 10”; 1000 W - 1200 W, 6 Slots Input Type where Y = T = Terminal Block C = IEC Connector, C14 B = IEC Connector, C16
- S2E - DER -
DLL
-
00
Case Option Codes First digit 0 - E = Parallel Code Second digit 0 = No Options 1 = Reverse Air 3 = Global Enable 5 = Opt 1 + Opt 3
-
A
Factory assigned for modified standards
-
###
Factory assigned for modified standards
Module Codes S2 = 200 W Single O/P (1 slot) D = 96 W/96 W Dual O/P Common Ground (1 slot) I = 96 W/96 W Dual O/P Isolated Ground (1 slot) Voltage Codes: See Voltage Code Table
Parallel Codes
Code 1 2 3 4 5 Slots in Parallel 1&2 2&3 3&4 4&5 5&6 Code 6 7 8 9 A Slots in Parallel 1,2&3 1,2,3&4 1,2,3,4&5 1,2,3,4,5&6 1&2; 3&4 Code B C D E 0 Slots in Parallel 1,2&3; 4&5 1,2,3&4; 5&6 1&2; 3&4; 5&6 1,2&3; 4,5&6 no module in parallel
Voltage Codes
Standard Output Ratings
Module Output Voltage Code Module Identification Single Output ONE SLOT 240 Watts Max
S2
Derating Curves - µMP1
Standard Fan(12 V/24 V/48 V)
85 VAC 100 VAC 110 VAC 200 VAC 264 VAC
Dual Output ONE SLOT 192 Watts Max
D = Dual Common Ground I = Dual Isolated Ground
1200 1100 1000
Output Module Line-Up
Output Power
Code A B C D E F G H I J K L M N O P Q R S T U V W X Y * For “I” codes only
Volts 2.0 V 2.2 V 3.0 V 3.3 V 5.0 V 5.2 V 5.5 V 6.0 V 8.0 V 10.0 V 11.0 V 12.0 V 14.0 V 15.0 V 18.0 V 20.0 V 24.0 V 28.0 V 30.0 V 33.0 V 36.0 V 42.0 V 48.0 V 54.0 V 60.0 V
Output Current V1 40.0 40.0 40.0 40.0 36.0 34.0 32.0 30.0 25.0 24.0 22.0 20.0 17.0 16.0 13.0 12.0 10.0 8.6 8.0 7 6.7 5.7 5.0 4.4 4.0
Output Current V1 V2 N/A N/A N/A 4.0* 4.0* 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.4 3.4 N/A N/A N/A N/A N/A N/A N/A
900 800 700 600 500 400 0 10 20 30 40 Temperature 50 60 70
Reverse FAN(12 V/24 V/48V)
85 VAC 100 VAC 110 VAC 200 VAC 264 VAC
1200 1100 1000
Output Power
900 800 700 600 500 400 0 10 20 30 40 Temperature 50 60 70
Embedded Power for Business-Critical Continuity
µMP4 (AC input on opposite side)
S L O T S L O T S L O T S L O T J2
S2 Module
Rev. 07.18.11_10 µMP Series 4 of 6
DC Output Control & Signals (Single output)
Pin 1 2 3 4 5 6 7 8 9 10 Function No connection No connection Current share Module inhibit return Module ISO inhibit SCOM -RMT sense Margin Remote margin / V prog. +RMT sense
29.8±0.2 37.5±0.3 32.5±0.3 36.5±0.3 CAPS HEIGHT 12.5 MAX 3.0 MAX 0.8 - 1.5 1.6±0.16
4
3
2
1
J1
Input
µMP4 =4 available slots
400 W max.
85-264 Vac
600 W max.
200-264 Vac
240 W
µMP1 (AC input on opposite side)
S L O T 6 S L O T 5 S L O T 4 S L O T 3 S L O T 2 S L O T 1 J2
5.3±0.5 1.0±0.25 V ADJ
J1
V+ V-
36.5±0.3
Input
4.5±0.3
µMP1 = 6 available slots
1000 W max.
85-264 Vac
1200 W max.
200-264 Vac
Pin Connectors
Figure 1. AC Input
AC Input
Pin 1 2 3
J1
130.0±1.5
1 2
9 10
IEC Connector
Terminal Block
PE N L
Function AC neutral AC line (hot) Chassis (earth) ground Function Input AC OK - “emitter” Input AC OK - “collector” Global DC OK - “emitter” Global DC OK - “collector” Spare Global inhibit/optional enable logic “1” Global inhibit/optional enable logic “0” Global inhibit/optional enable return +5 VSB housekeeping
Dual Module
DC Output Control & Signals (Dual output)
Pin 1 2 3 4 5 6 7 8 9 10
V2 ADJ
PFC Input Connector (control & signals)
Pin 1 2 3 4 5 6 7 8 9
V1 ADJ
Function -RMT sense V2 +RMT sense V2 No connection Module inhibit rtn Module ISO inhibit SCOM -RMT sense V1 No connection No connection +RMT sense V1
10 +5 VSB housekeeping return
Figure 2. Connector J1 & J2 J2
122.0 ± 0.5 0 ~ 0.1 mm (2X)
I C Bus Output Connector
2
37.8 ± 0.3
1 2
9 10
Mates with Landwin 2050S1000 Housing 2053T011V Pin or JST PHDR-10VS Housing JST SPHD-002T-P0.5 (28-24) JST SPHD-001T-P0.5 (26-22) Connector Kit Part No.: 70-841-023
Pin 1 2 3 4 5 6 7 8 9 10
Function 5 Vcc bus Serial data signal (SDA) Secondary return (COM) Serial clock signal (SCL) Address bit 2 (A2) No connection Address bit 1 (A1) No connection Address bit 0 (A0) No connection
V1+ COM V2+ COM
130.0 ref 12.5 MAX 1.6 ± 0.15 2.5 MAX
Embedded Power for Business-Critical Continuity
µMP Series µMP4 (400/600 Watts Max)
Case Size: µMP4: 10.11” x 3.5” x 1.57” (256.9mm x 88.9mm x 40.0mm) Weight: µMP4 Case: 1.96 lbs • Single O/P: 0.22 lb. • Dual O/P: 0.16 lb. • Blank: 0.06 lb.
Rev. 07.18.11_10 µMP Series 5 of 6
Embedded Power for Business-Critical Continuity
µMP Series µMP1 (1000/1200 Watts Max)
Case Size: µMP1: 10.11” x 5” x 1.57” (256.9mm x 127mm x 40.0mm) Weight: µMP1 Case: 2.78 lbs • Single O/P: 0.22 lb. Americas • Dual O/P: 0.16 lb. • Blank: 0.06 lb. 5810 Van Allen Way
Rev. 07.18.11_10 µMP Series 6 of 6
Carlsbad, CA 92008 USA Telephone: +1 760 930 4600 Facsimile: +1 760 930 0698
Europe (UK)
Waterfront Business Park Merry Hill, Dudley West Midlands, DY5 1LX United Kingdom Telephone: +44 (0) 1384 842 211 Facsimile: +44 (0) 1384 843 355
Asia (HK)
14/F, Lu Plaza 2 Wing Yip Street Kwun Tong, Kowloon Hong Kong Telephone: +852 2176 3333 Facsimile: +852 2176 3888
For global contact, visit:
www.Emerson.com/EmbeddedPower techsupport.embeddedpower @emerson.com
While every precaution has been taken to ensure accuracy and completeness in this literature, Emerson Network Power assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
Emerson Network Power. The global leader in enabling business-critical continuity. AC Power Connectivity DC Power Embedded Computing Embedded Power Monitoring Outside Plant Power Switching & Controls Precision Cooling Racks & Integrated Cabinets Services Surge Protection EmersonNetworkPower.com
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2011 Emerson Electric Co.