CORCOM Product Guide High Performance 3-Phase RFI Power Line Filters for WYE Applications
A Series
UL Recognized CSA Certified VDE Approved
AYP/AYT
A Series
The 3-phase filters are designed for 3-phase, four wire, WYE applications providing filtering in each of the three lines plus the neutral and ground line. The 3-phase models feature: I Both common mode and differential mode suppression from 50 kHz to 30 MHz I Effective for both balanced and unbalanced three phase loads I Ground choke included I Shielded construction The dual stage AYT provides higher performance, while the single stage AYP is good for lower noise environments.
Specifications
Maximum leakage current, each line-to-ground: @ 120 VAC 60 Hz: @ 250 VAC 50 Hz: Hipot rating (one minute): line-to-ground neutral-to-ground line-to-neutral Operating frequency: Rated voltage: phase-to-phase: phase-to-neutral/ground: Minimum insertion loss in dB: Line-to-ground in 50 ohm circuit Current Frequency - MHz Rating .05 .1 .15 .5 1 5 AYP6C 20A 30A 45A 60A AYT6C 20A 30A 45A 60A 22 15 8 5 45 29 15 12 32 24 19 16 63 53 36 37 39 30 25 22 70 61 43 46 55 55 49 50 75 75 75 75 56 55 49 50 75 75 75 75 65 61 56 54 75 75 75 75 1.4 mA 3.4 mA 1500 VAC 1500 VAC 1450 VDC 50/60 Hz 440 VAC 250 VAC
10 65 63 58 54 75 75 75 70
30 54 50 45 47 65 60 50 45
End Bell Mounting Accessories
Mounting brackets available in two sizes, 20/30 amp (AA400) and 45/60 amp (AA405). End Bell mounting kit available in two sizes, 20/30 amp (AA406) and 45/60 amp (AA407).
Filter
Line-to-line in 50 ohm circuit Frequency - MHz Current Rating .05 .1 .15 .5 1 5 AYP6C 20A 30A 45A 60A AYT6C 20A 30A 45A 60A 20 18 8 20 27 17 14 26 38 28 20 24 56 46 41 50 50 43 27 27 65 55 50 58 65 65 60 60 70 75 75 75 65 65 65 65 70 75 75 75 65 65 65 65 70 75 75 75
10 60 59 56 56 70 75 75 75
30 52 48 43 50 70 70 65 60
AA406/407
End Bell Kit Cover Plate
8
Catalog 1654001 Revised 05-07 Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change. USA Cust. Svc.: 1-800-468-2023 CORCOM Prods: 1-847-680-7400 Germany: 49-89-6089-0 www.corcom.com www.tycoelectronics.com
CORCOM Product Guide High Performance 3-Phase RFI Power Line Filters for WYE Applications (Continued)
A Series
RFI Power Line Filters
Case Style
AYP6C & AYT6C
C E A
Case Dimensions
Part No. 20AYP6C 30AYP6C 45AYP6C A* (max) 8.82 224.0 8.82 224.0 9.43 239.5 9.43 239.5 13.82 351.0 13.82 351.0 13.83 351.3 13.83 351.3 B (max) 5.57 141.5 5.57 141.5 6.92 175.8 6.92 175.8 5.57 141.5 5.57 141.5 6.92 175.8 6.92 175.8 C (max) 2.56 65.0 2.56 65.0 4.82 122.4 4.82 122.4 2.56 65.0 2.56 65.0 4.82 122.4 4.82 122.4 D
± .030 ± .76
E
± .015 ± .38
D
B
60AYP6C 20AYT6C 30AYT6C
Terminals: 1/4 x 20 (10)
Mounting studs: No. 8-32 (8)
45AYT6C 60AYT6C
Torque 56 2 in. lbs.
4.616 117.2 4.616 117.2 5.950 151.1 5.950 151.1 4.616 117.2 4.616 117.2 5.950 151.1 5.95 151.1
1.50 38.1 1.50 38.1 3.75 95.3 3.75 95.3 1.50 38.1 1.50 38.1 3.75 95.3 3.75 95.3
* For end bell covering terminals and connections, add: 20A & 30A 5.57 141.48 6.45 163.83
Electrical Schematics
AYP6C Models
LINE
A B C N
45A & 60A
LOAD
A B C N LOAD GND
Part Numbers
20AYP6C 30AYP6C 45AYP6C 60AYP6C 20AYT6C 30AYT6C 45AYT6C 60AYT6C
LINE GND
Mounting Hardware
AYT6C Models
LINE
A B C N
LOAD
A B C N LOAD GND
Mounting Bracket Kit with Captive Nuts: AA400 (20/30 Amp) AA405 (45/60 Amp) End Bell Kit with Captive Nuts: AA406 (20/30 Amp) AA407 (45/60 Amp) Additional Captive Nuts to Mount Filters: AA401 (10 Nuts)
LINE GND
Resistor location for reference only.
9
Catalog 1654001 Revised 05-07 Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change. USA Cust. Svc.: 1-800-468-2023 CORCOM Prods: 1-847-680-7400 Germany: 49-89-6089-0 www.corcom.com www.tycoelectronics.com