Corcom Product Guide Power Entry Module with Voltage Selection and Fusing
Catalog: 1654001 Issue Date: 06.2011
J Series
UL Recognized CSA Certified
Front View, all models 6J4
6HJ4
J Series
• Power entry module with North American style 3AG fuse holder • 2 or 4 voltage selection • Compact snap-in design • Two element circuit provides basic EMI attenuation • Available with minimal leakage current suitable for medical applications (HJ models) • Also available without filter (VJ models)
Specifications
Maximum leakage current each Line to Ground: 6HJ4 or 6J4 Models non–filtered @250 VAC 50 Hz: 500 A 5 A Hipot rating (one minute): Line to Ground: Line to Line: Operating Voltage: suffix - 1 or - 4 models: suffix - 2 models: Operating Frequency: 1550 VAC 1450 VDC 100, 120, 220 or 240VAC 115 or 230 VAC 50/60 Hz 6A .25 x 1.25
(not included)
Ordering Information 6 H J 4 -4
Available Voltage Selections 1 - Four (non–filtered versions) 2 – Two 4 or blank – Four (filtered versions) Filtered Indicator 1 – Non–filtered 4 – Filtered J Series Filter Type H – Medical V – Non-filtered Blank – general purpose Current Rating 6A
Rated Current: Required Fuse:
Available Part Numbers
Non–filtered models 6VJ1 6VJ1-2
General Purpose Filters 6J4 Medical Filters 6HJ4-4 6HJ4-2 6J4-2
172
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change.
For email, phone or live chat, please go to te.com/help corcom.com
Corcom Product Guide Power Entry Module with Voltage Selection and Fusing
Catalog: 1654001 Issue Date: 06.2011
(continued)
J Series
Electrical Schematics 6VJ1 & 6VJ1-2
Note 3 Note 2 Hot S R Power On/Off Off H Ground On Pilot light M N Note 1 L F Transformer primary 120V 100V A B J D K Note 2 Neutral P A B C D E
120V
Accessories
GA400:NEMA 5-15P to IEC 60320-1 C-13 line cord
220V 240V
20V
100V
JA302: 2 Voltage Select Card Comes standard with 6VJ1-2, 6J4-2 and 6HJ4-2
6J4 & 6J4-2
Note 3 120V 100V A Hot Ground Power On-O O On Pilot light B C D E Neutral Note 1 J H F A
20V
220V 240V
JA304: 4 Voltage Select Card Comes standard with 6VJ1, 6J4 and 6HJ4-4 JA403: Mounting clips for .105 - .125” panels
B
100V
C D E
120V
3
Power Inlet Filters & Power Entry Modules
JA410-419: Equipment Rating Labels Self-adhesive, available in multiples of 40 Specify part number
2.330
F Transformer primary
6HJ4-4 & 6J4-2
Note 3 120V 100V A Hot Ground Power On-O O On Pilot light B C D E Neutral Note 1 J H F A
20V
220V 240V
.210
Line V. + 5 - 10% 48-440 - 50 VA Max.
Fuse
100/120V (115V)
220/240V (230V)
500mA
250mA
B
100V
A
B
C
C D E
120V
A Part No. JA410 JA411 JA412 JA413 JA414 JA415 JA416 JA417 JA418 JA419
VA max.
B
C
F Transformer primary
Fuse Fuse 100/120 (115) 220/240 (230)
Voltage Selection
25 50 100 200 250 300 400 500 600 Assortment
250 mA 500 mA 1A 2A 2.5A 3A 4A 5A 6A
125 mA 250 mA 500 mA 1A 1.25A 1.5A 2A 2.5A 3A
JA410-JA418: 40 labels of one part number JA419: 5 each of JA410 - JA418 (45 labels)
Open cover door and slide fuse-pull lever to left. Select operating voltage by orienting voltage selection card with the desired voltage on top left side. Push card firmly into module slot. Slide fuse-pull lever to right into normal position and re-insert fuse into holders. Use caution in selecting correct fuse value.
JA500: Voltage Selector Card Extractor Tool
173
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change.
For email, phone or live chat, please go to te.com/help corcom.com
Corcom Product Guide Power Entry Module with Voltage Selection and Fusing
Catalog: 1654001 Issue Date: 06.2011
(continued)
J Series
Case Styles Non-filtered Models Case Dimensions
Part No. 6VJ1, 6VJ1-2
C
A
B
C
D
6J4, 6J4-2, 6HJ4-4, 6HJ4-2
D B
A
Performance Data Typical Insertion Loss
Measured in closed 50 Ohm system
Filtered Models
6J4
db 100 90 80
6HJ4
db 100 90 80 70 60 50 40 30 20 10
C
70 60 50 40 30
A
D B
20 10 0 0.1 1 10 30 Frequency in MHz
0
0.1
1
10 30 Frequency in MHz
Common Mode / Asymmetrical (L-G) Differential Mode / Symmetrical (L-L)
Recommended Panel Cutouts
Door Open Position
Minimum Insertion Loss
1.063* 1.17 27.0 29.7
Measured in closed 50 Ohm system Common Mode / Asymmetrical (Line to Ground)
Bezel Clearance
2.60* 66.0 2.68 68.1 3.00 76.2
*± .003 [.076]
174
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change.
For email, phone or live chat, please go to te.com/help corcom.com
很抱歉,暂时无法提供与“6HJ4-4”相匹配的价格&库存,您可以联系我们找货