Function: 47
Phase sequence relays are designed to monitor the correct phase rotation of a three phase system. Several models are avilable from 50 Hz, 60 Hz, and 400 Hz with voltages up to 575 volts. High shock relay output and reverse contacts are also available. Operation: The relay remains de-energized when voltage in the proper phase sequence (A, B, C) is applied, the relay is energized when voltage with incorrect sequence (A, C, B) is applied.
3 5/32
2 3/4
1
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.
Part Number
Input Voltage .................................... See Part Number Selection Output Contacts SPDT
Contact Ratings ................................ 5 amp resitive at 120 Vac or 28 Vdc
Tyco Electronics / www.tycoelectronics.com / Factory Direct Technical Support: 800-253-4560, ext. 2023 (U.S., Canada, Mexico) or 805-220-2020, ext. 2023 (International)
2
3 /4 6 5 /1
2
2
1 /8 6 11/1
PART NUMBER SELECTION
6 - 32 x 3/8 studs 4 places
PRODUCT SPECIFICATIONS
PART NUMBER SELECTION
Sample Part No. 901X Type: 900-3X = 120 VAC, 60 Hz, 3 phase,L-L 910X = 190-520 VAC, 60 Hz, 3 Phase, L-L 900-2X = 208-230, 50/60 Hz, 3 Phase 900X = 230 VAC, 60 Hz, 3 phase, L-L 901X = 460 VAC, 60 Hz, 3 phase,L-L Mounting: X = Flange Blank - Stud Consult factory for additional models and options