General Purpose Relays
SCHRACK
Interface Power Relay RT
I I I I I I I
1 pole 12 / 16 A, 2 pole 8 A, 1 CO contact or 2 CO contacts DC- or AC coil Sensitive coil 400 mW Reinforced insulation, protection class II (VDE 0700) 5 kV / 10 mm coil-contact 1 pole 12 A with 3.5 or 5 mm pinning Recycleable packaging
Applications Panel boards, mechanical engineering
F0269-C
Approvals
V REG.-Nr.of6106, Z on request E214025 Technical data approved types
Contact data 1-pole 2-pole
Contact configuration 1 CO 2 CO Contact set single contact Type of interruption micro disconnection Rated voltage / max. switching voltage AC 240 / 400 VAC Rated current 12 / 16 A 8A Maximum breaking capacity AC 3000 / 4000 VA 2000 VA Limiting making capacity,max 4 s, df 10% 25 / 30 A 15 A Contact material AgNi 90/10 Rated frequency of operation DC coil with / without load 6 / 1200 min-1 AC coil with / without load 6 / 600 min-1 Operate- / release time DC coil max 8 / 6 ms max 10 / 5 ms Bounce time DC coil, NO / NC contact max 4 / 6 ms max 4 / 9 ms Contact ratings Type Contact IEC 61810 RT314 DC-coil RT314 AC-coil RT314 AC-coil RT424 AC coil UL 508 RT314 RT314 RT314 RT314 RT424 DC coil RT424 DC coil RT424 DC coil RT424 DC coil EN60730-1 RT314 DC-coil RT424 DC coil NO NO CO CO Load 10 A, 400 VAC, cosϕ=1 16 A, 250 VAC, cosϕ=1 16 A, 250 VAC, cosϕ=1 8 A, 250 VAC, cosϕ=1 Ambient temp. [°C] 85°C 70°C 70°C 70°C Cycles 150x103 50x103 10x103 30x103 50x103 6x103 6x103 1x103 6x103 30x103 1x103 6x103 100x103 100x103
NO 16 A, 250 VAC, general purpose, DF: 10% 85°C NO A300 40°C NC B300 40°C NO 240 VAC, 1 hp 40°C NO / NC 8 A, 30 VDC, general purpose 85°C NO 10 A, 250 VAC, general purpose 85°C NO / NC motor, 1/2 hp, 240 VAC 85°C NO / NC pilot duty, B300, R300 85°C NO 12(2) A, 250 VAC NO / NC 6(2) A, 250 VAC 85°C 85°C
Coil data
Rated coil voltage range DC coil AC coil Operative range to IEC 61810 Coil insulation system according UL1446 5...110 VDC 24...230 VAC 2 class F
1
Datasheet Rev. HK1 Issued 2008/11 www.tycoelectronics.com www.schrackrelays.com Dimensions are in mm unless otherwise specified and are shown for reference purposes only. Product specification according to IEC 61810-1. Product data, technical parameters, test conditions and processing information only to be used together with the 'Definitions' section in the catalogue or at schrackrelays.com in the ‘Schrack’ section. Specifications subject to change.
General Purpose Relays
SCHRACK
Interface Power Relay RT (Continued)
Coil versions, DC-coil Coil Rated Operate Release Coil Rated coil code voltage voltage voltage resistance power VDC VDC VDC Ohm mW 006 6 4.2 0.6 90+10% 400 012 12 8.4 1.2 360+10% 400 024 24 16.8 2.4 1440+10% 400 048 48 33.6 4.8 5520+10% 417 060 60 42.0 6.0 8570+12% 420 110 110 77.0 11.0 28800+12% 420 All figures are given for coil without preenergization, at ambient temperature +23°C Other coil voltages on request Coil versions, AC-coil 50Hz Coil Rated Operate Release Coil Rated coil code voltage voltage voltage resistance power 50 Hz 50 Hz 50 Hz VAC VAC VAC Ohm VA 524 24 18.0 3.6 350+10% 0.76 615 115 86.3 17.3 8100+15% 0.76 730 230 172.5 34.5 32500+15% 0.74 All figures are given for coil without preenergization, at ambient temperature +23°C Other coil voltages on request
Insulation
Dielectric strength coil-contact circuit open contact circuit adjacent contact circuits Clearance / creepage coil-contact circuit Material group of insulation parts Tracking index of relay base Insulation to IEC 61810-1 Type of insulation coil-contact circuit open contact circuit Rated insulation voltage Pollution degree 12 A version 16 A version 2 x 8 A version Rated voltage system Overvoltage category 5000 Vrms 1000 Vrms 2500 Vrms W 10 / 10 mm IIIa PTI 250 V reinforced micro disconnection 250 V 3 3 3 2 3 2 240 V 230 / 400 V III
Terminal assignment
Bottom view on pins
1 CO contact 12 A
S0163-BC
Other data
1-pole
2-pole
1 CO contact 16 A
Mechanical endurance DC coil > 30 x 106 >30 x 106 AC coil > 10 x 106 >5 x 106 Material RoHS - Directive 2002/95/EC compliant as per product date code 0413 Environment Ambient temperature range DC coil -40...+85°C AC coil -40...+70°C Vibration resistance (function), NO / NC contact 20 / 5 g, 30 ... 500 Hz Shock resistance (destruction) 100 g Category of protection RTII Processing Mounting distance dense packing of sockets Relay weight 14 g Packaging unit 20 / 500 pcs
S0163-BE
2 CO contacts 8 A
S0163-BJ
Dimensions
Accessories
For Details see datasheet
NOTE:
Accessories Interface Power Relay RT
indicated contact ratings and electrical endurance data for direct wiring of relays (according IEC 61810-1, table 12); for relays mounted on sockets deratings may apply.
Relay Packages
Complete packages consisting of a relay mounted on a socket see Package RT
S0272-BA
2
Datasheet Rev. HK1 Issued 2008/11 www.tycoelectronics.com www.schrackrelays.com Dimensions are in mm unless otherwise specified and are shown for reference purposes only. Product specification according to IEC 61810-1. Product data, technical parameters, test conditions and processing information only to be used together with the 'Definitions' section in the catalogue or at schrackrelays.com in the ‘Schrack’ section. Specifications subject to change.
General Purpose Relays
SCHRACK
Interface Power Relay RT (Continued)
Product key
Type
Typical product key
RT
3
1
4
024
RT Interface Power relay RT Version 1 1-pole, 12 A, pinning 3.5 mm 3 1-pole, 16 A, pinning 5 mm 2 1-pole, 12 A, pinning 5 mm 4 2-pole, 8 A, pinning 5 mm Contact configuration 1 1 CO contact (1 form C) 2 2 CO contacts (2 form C) Contact material 4 AgNi 90/10 Coil Coil code: please refer to coil versions table, preferred types in bold print Wash tight version on request
Product key RT114024 RT114524 RT114615 RT114730 RT214024 RT214524 RT214615 RT214730 RT314024 RT314524 RT314615 RT314730 RT424024 RT424524 RT424615 RT424730
Version 1-pole, 12 A pinning 3.5 mm 1-pole, 12 A pinning 5 mm 1-pole, 16 A pinning 5 mm 2-pole, 8 A pinning 5 mm
Contacts 1 CO contact
Cont. material AgNi 90/10
Coil DC-coil AC-coil DC-coil AC-coil DC-coil AC-coil
2 CO contacts
DC-coil AC-coil
Coil 24 VDC 24 VAC 115 VAC 230 VAC 24 VDC 24 VAC 115 VAC 230 VAC 24 VDC 24 VAC 115 VAC 230 VAC 24 VDC 24 VAC 115 VAC 230 VAC
Part number 1-1393239-3 1-1393239-7 1-1393239-8 1-1393239-9 5-1393239-5 5-1393239-9 6-1393239-0 1419108-6 9-1393239-8 1393240-4 1393240-6 1393240-7 6-1393243-8 7-1393243-6 7-1393243-8 7-1393243-9
3
Datasheet Rev. HK1 Issued 2008/11 www.tycoelectronics.com www.schrackrelays.com Dimensions are in mm unless otherwise specified and are shown for reference purposes only. Product specification according to IEC 61810-1. Product data, technical parameters, test conditions and processing information only to be used together with the 'Definitions' section in the catalogue or at schrackrelays.com in the ‘Schrack’ section. Specifications subject to change.