AD1072F Series
Very Low Cost, 72W DIN Rail Mount Single Output AC/DC Power Supplies
Key Features:
• 72W Output Power • DIN Rail Mountable • Universal AC Input • UL 508 Compliant • EN60950 Compliant • 12, 24 & 48 VDC Outputs • Cond./Rad. EMI Class B • >150 kH MTBF • LOW COST!
New Industrial Supplies!!
Conditions Universal Min. 100 127 47 Typ. Max. 240 370 63 Units VAC VDC Hz A A mA Units % % % % mSec % mS % %/ºC
Electrical Specifications
Input
Parameter Input Voltage Range Input Frequency Inrush Current, Cold Start Leakage Current
Specifications typical @ +25°C, nominal input voltage & rated output current, unless otherwise noted. Specifications subject to change without notice.
110 VAC 220 VAC 264 VAC Conditions Min.
22 44 1.8
Output
Parameter Output Voltage Accuracy Output Voltage Adjustment Range Line Regulation Load Regulation (Note 1) Hold Time Ripple & Noise (20 MHz) (Note 2) Output Power Protection Transient Recovery Time (Note 3) Transient Response Deviation Temperature Coefficient Output Short Circuit Typ. Max. ±0.5 ±10.0 Vin = Min to Max ±1.0 Iout = 20% to 100% ±1.0 110 VAC, Full Load 10 220 VAC, Full Load 20 See Model Selection Guide Power Limit 130 160 2 50% Load Change 5 ±0.04 ±0.05 Continuous With Autorecovery Min. 3,000 2,000 500 100 Typ. Max.
RoHS Compliant
Models available to 360W! Call today for details
MicroPower Direct
292 Page Street Suite D Stoughton, MA 02072 USA T: (781) 344-8226 F: (781) 344-8481 E: sales@micropowerdirect.com W: www.micropowerdirect.com
General
Parameter Isolation Voltage Isolation Resistance (Note 4) Switching Frequency Conditions Input - Output Input - FG (Frame Ground) Output - FG (Frame Ground) 500 VDC Fixed Conditions Units VAC MΩ kHz
80
Environmental
Parameter Operating Temperature Range Storage Temperature Range Cooling Humidity Vibration Min. Typ. Max. Units -20 +25 +50 ºC -20 +85 ºC Free Air Convection RH, Non-condensing 95 % 10 Hz ~ 2 kHz; 2G 10 min./1 Cycle; X, Y, Z axis each 1 hour Ambient 4.76 x 4.33 x 2.2 Inches (121.0 x 110.0 x 56.0 mm) Aluminum (Base) and Steel (Cover) Screw Terminal Conditions MIL HDBK 217F, 25ºC, Gnd Benign Min. Typ. Max. Units 150 kHours UL 1950, EN 60950, IEC 60950 Compliance to EN55011, EN55022 (CISPR22) Class B EN6100-4-2,3,4,5,6,8,11 Level 3
Physical
Case Size Case Material Connection
Reliability Specifications
Parameter MTBF Safety Standards EMI Compliance EMS Immunity Compliance
Model Selection Guide
Model Number AD1072-12F AD1072-24F AD1072-48F Rated Power (W) 72 72 72 Input Voltage (VAC) Current (A) Output Voltage Current (A) Current (A) (VDC) Max) Range 12 24 48 6.0 3.0 1.5 0 ~ 6.0 0 ~ 3.0 0 ~ 1.5 Overvoltage Protection (VDC) 15 ~ 17 27 ~ 30 52 ~ 56 Ripple & Noise
(mV p-p)
Efficiency (%, Typ) 78 81 82
Universal Range 115 VAC 230 VAC 100 - 240 1.0 0.5 100 - 240 1.0 0.5 100 - 240 1.0 0.5
100 150 250
Notes: 1. Load regulation is specified for a load change of 20% to 100%. 2. Ripple & noise is measured using equipment with 20 Mhz of bandwidth with the unit under test operating at rated load and a 110 VAC input. Connection to the unit is made with a 0.1 μF / 630V metalized capacitor & a 47 μF electrolytic capacitor connected in parallel. 3. Transient recovery is measured to within a 1% error band for a load step change of 50% to 100%. 4. Isolation resistance is given for Input/Output and Input/FG. For Output/FG., it is 50 MΩ 5. Overload protection is power limiting. The unit recovers automatically when the fault is removed. 6. Over voltage protection is a shut down type. The unit recovers automatically when the fault is removed. 7. To mount the unit to the DIN rail, tilt the unit rearwards from the top, fitting the mount over the top of the rail. Press back on the bottom front of the unit until it locks in place on the rail. To remove the unit from the rail, pull the removal clip at the bottom rear of the unit downward with a screw driver. With the clip down, lift up on the unit from the bottom front until it clears the rail. Before installation or removal all wiring should be disconnected and the main power to the system shut off. 8. When wiring the supply, all lines should be as thick and short as possible. AWG 14 wire is recommended for the AD1072F series. 9. The units should be mounted so they are vertically orientated. Air flow (if it is provided) would optimally flow from the bottom to the top of the unit. 10. It is recommended that a fuse be used on the input of a power supply for protection. For the AD1072F series a 250VAC 2.0A is recommended.
Derating Curve
Mechanical Dimensions
Units with the optional “FT” outputs may be easily connected for “Fault Tolerant operation. Contact the factory for details
Connections TB 1
Pin 1 2 3 4 5 6 7 Function DC Output (+V) DC Output (-V) FT (Optional) FT (Optional) Frame Ground (FG) AC Input - Neutral AC Input - Live
Notes: • All dimensions are typical in inches (mm) • Tolerance x.xx = ±0.01 (±0.25)
MicroPower Direct
www.micropowerdirect.com
•
292 Page Street Ste D Stoughton, MA 02072
TEL: (781) 344-8226
•
FAX: (781) 344-8481
•
E-Mail: sales@micropowerdirect.com