0
登录后你可以
  • 下载海量资料
  • 学习在线课程
  • 观看技术视频
  • 写文章/发帖/加入社区
会员中心
创作中心
发布
  • 发文章

  • 发资料

  • 发帖

  • 提问

  • 发视频

创作活动
NICFP-2220

NICFP-2220

  • 厂商:

    NI

  • 封装:

  • 描述:

    NICFP-2220 - Analog Input/Output Combination Modules for Compact FieldPoint and FieldPoint - Nationa...

  • 数据手册
  • 价格&库存
NICFP-2220 数据手册
Analog Input/Output Combination Modules for Compact FieldPoint and FieldPoint NI [c]FP-AIO-600 ◾◾ 4 voltage or current inputs ◾◾ ±30 V ◾◾ 0 to 20, 4 to 20 mA ◾◾ 4 current outputs ◾◾ 0 to 10 V ◾◾ 0 to 20, 4 to 20 mA ◾◾ 12-bit resolution ◾◾ Input and output ranges software configurable per channel ◾◾ 2,300 Vrms bank isolation for transient overvoltage protection ◾◾ Hot swappable with autoconfiguration ◾◾ -40 to 70 °C operating range Module [c}FP-AIO-600 Input Channels 4 Input Ranges (Software Configurable per Channel) Current: 0 to 20 mA, 4 to 20 mA Voltage: ±5 V, ±15 V, ±30 V, 0 to 5 V, 0 to 15 V, 0 to 30 V Output Channels 4 Output Ranges (Software Configurable per Channel) Current: 0 to 20 mA, 4 to 20 mA Resolution 12 bits All Channel Update Rate 1.7 kHz Overview The NI [c]FP-AIO-600 is a versatile combination analog input and analog output module for Compact FieldPoint and FieldPoint that you can use to measure voltages and 0 to 20 or 4 to 20 mA current loops from industrial sensors and transmitters and to control valves, gauges, and other industrial actuators. The [c]FP-AIO-600 is ideal for low-channel-count systems or for PID control with high-speed I/O. The module has overranging and onboard diagnostics to ensure trouble-free installation and maintenance. The [c]FP-AIO-600 measures and linearizes signals onboard to return scaled values to your control or monitoring software, accept engineering units from your control or monitoring software, and automatically scale and linearize output signals. The [c]FP-AIO-600 module comes with a NIST-traceable calibration certificate, ensuring accurate and reliable analog measurement and control. [c]FP-AIO-600 The [c]FP-AIO-600 includes four 0 to 30 V or 0 to 20/4 to 20 mA analog inputs and four 0 to 20/4 to 20 mA analog outputs. The analog inputs and outputs use a 12-bit DAC. Each output channel includes a monitoring circuit and LED indicator for open current loop detection. The [c]FP-AIO-600 requires an external power supply, providing 5 to 30 VDC. Isolation The [c]FP-AIO-600 features optical bank isolation with 2,300 Vrms of breakdown isolation. These Compact FieldPoint and FieldPoint modules do not have channel-to-channel isolation. Field I/O Connections Compact FieldPoint and FieldPoint modules include a built-in power distribution bus that provides multiple power connections on the module. A field-wired power supply connected to the voltage (V) and common (C) terminals is internally connected to a power distribution bus that provides additional breakout terminals for voltage supply (VSuP) and common (COM). These terminals offer a convenient way to distribute power to field devices that require external power. The [c]FP-AIO-600 has: ◾◾ 4 voltage input terminals (VIN) ◾◾ 4 current input terminals (IIN) Smart I/O Module You can connect the [c]FP-AIO-600 directly to industrial actuators or units under test and achieve high-accuracy measurement and control. The module calibrates, scales engineering units to sensor signals, and performs self-diagnostics to look for problems with the module or with the wiring, such as open current loops. With the [c]FP-AIO-600 module, your software application reads and writes engineering values from the module, eliminating the error-prone step of converting voltage or current to binary values. The module has an update rate of 1.7 kHz. Overall data throughput depends on the software loop speeds and the network speeds. ◾◾ 4 current output terminals (IOuT) ◾◾ 12 common terminals (COM) ◾◾ 8 power connections for field devices or current loops (VSuP) Analog Input/Output Combination Modules for Compact FieldPoint and FieldPoint Ordering Information Compact FieldPoint NI cFP-AIO-600 ............................................................................. 777318-600 Recommended Compact FieldPoint System Products NI cFP-2220 ................................................................................ 777317-2220 NI cFP-BP-4..................................................................................... 778617-04 NI cFP-CB-1 .................................................................................... 778618-01 PS-15 power supply ....................................................................... 781093-01 NI Developer Suite Professional Control Edition ........................... 777906-03 FieldPoint FP-AIO-600 ................................................................................... 777518-600 Recommended FieldPoint System Products NI FP-1601 ...................................................................................... 777792-01 NI FP-TB-1 ...................................................................................... 777519-01 PS-4 power supply ......................................................................... 778586-90 NI Developer Suite Standard Control Edition ................................ 777905-03 BUY NOW For complete product specifications, pricing, and accessory information, call 800 813 3693 (u.S.) or go to ni.com/fieldpoint. B uY ONLINE at ni.com or C ALL 800 813 36 93 (u.S.) 2 Analog Input/Output Combination Modules for Compact FieldPoint and FieldPoint Specifications Typical for -40 to 70 °C unless otherwise noted. cFP-AIO-600 Offset Errors Voltage Input Range 0-20 mA 4-20 mA ±20 mA Offset Errors at 15 to 35 °C 9 μA typ, 20 μA max 9 μA typ, 20 μA max 16 μA typ, 38 μA max Offset Errors at -40 to 70 °C 9 μA typ, 20 μA max 9 μA typ, 20 μA max 17 μA typ, 38 μA max Input and Output Characteristics Number of input channels..................... Number of output channels .................. ADC resolution ...................................... Type of ADC........................................... DAC resolution ...................................... Type of DAC........................................... update rate (all channels) ..................... 4 4 12 bits Successive approximation 12 bits R-2R 1.7 kHz (588 μs) Current Outputs ([c]FP-AIO-600) Output ranges........................................ Output type............................................ External power supply........................... Internal voltage drop ............................. Resistive load ........................................ Protection .............................................. Default power-up state ......................... Gain Errors at -40 to 70 °C 0.11% typ, 0.16% max 0.11% typ, 0.16% max 0.11% typ, 0.16% max 0.11% typ, 0.16% max 0.13% typ, 0.19% max 0.13% typ, 0.19% max 0.13% typ, 0.19% max 0.13% typ, 0.19% max Current Output Range (with Overrange) 0 to 21 mA 3.5 to 21 mA 0-20 or 4-20 mA, programmable (0-21 or 3.5-21 mA with overranging) Current source (external power supply required) 10-30 VDC, 125 mA for four output channels 3V up to 1 kW with 24 VDC power supply Short-circuit and open-circuit 0 mA Isolation Voltage Accuracy at -40 to 70 °C (% of Output Value; % of Full Scale) ±0.14%; ±0.2% ±0.14%; ±0.23% Voltage Inputs Effective resolution ............................... Input impedance.................................... Input signal bandwidth ......................... 11.3 bits 1.5 MW 350 Hz cFP-AIO-600 Gain Errors Voltage Input Range 0-5 V 0-10 V 0-15 V 0-30 V ±5 V ±10 V ±15 V ±30 V Gain Errors at 15 to 35 °C 0.03% typ, 0.04% max 0.03% typ, 0.04% max 0.03% typ, 0.04% max 0.03% typ, 0.04% max 0.03% typ, 0.04% max 0.03% typ, 0.04% max 0.03% typ, 0.04% max 0.03% typ, 0.04% max Accuracy at 15 to 35 °C (% of Output Value; % of Full Scale) ±0.03%; ±0.13% ±0.03%; ±0.16% Isolation Voltage Maximum isolation voltage .................. Channel-to-channel isolation ................ Transient overvoltage............................ 250 Vrms, Installation Category II No isolation between channels 2,300 Vrms cFP-AIO-600 Offset Errors Voltage Input Range 0-5 V 0-10 V 0-15 V 0-30 V ±5 V ±10 V ±15 V ±30 V Offset Errors at 15 to 35 °C 4 mV typ, 9 mV max 6 mV typ, 14 mV max 8 mV typ, 18 mV max 13 mV typ, 32 mV max 6 mV typ, 14 mV max 10 mV typ, 23 mV max 14 mV typ, 32 mV max 25 mV typ, 59 mV max Offset Errors at -40 to 70 °C 6 mV typ, 15 mV max 8 mV typ, 20 mV max 10 mV typ, 24 mV max 15 mV typ, 37 mV max 8 mV typ, 20 mV max 12 mV typ, 29 mV max 16 mV typ, 38 mV max 28 mV typ, 64 mV max Dynamic Characteristics Maximum update rate........................... Slew rate ............................................... 1,700 updates/s 0.4 mA/μs Physical Characteristics LED indicators POWER (green) ................................. READY (green) .................................. Fault status (red) ............................... Dimensions (FP only, including terminal base) ..... 10.7 by 10.9 by 9.1 cm (4.2 by 4.3 by 3.6 in.) Weight FP-AIO-600 ........................................ cFP-AIO-600 ...................................... 141 g (4.9 oz) 111 g (3.9 oz) Power on and self-test passed Module configured and ready Open circuit Current Inputs Effective resolution ............................... Input impedance.................................... Overcurrent protection .......................... Overvoltage protection.......................... Input signal bandwidth ......................... Gain errors 15 to 35 ºC ........................................ -40 to 70 ºC ....................................... 0.08% typ, 0.18% max 0.25% typ, 0.66% max 11.3 bits 105 W ±100 mA ±10 V 400 Hz Power Requirement Power from network module................. 350 mW B uY ONLINE at ni.com or C ALL 800 813 36 93 (u.S.) 3 Analog Input/Output Combination Modules for Compact FieldPoint and FieldPoint Environment Operating temperature.......................... Storage temperature ............................. Relative humidity .................................. -40 to 70 °C -55 to 85 °C 10 to 90%, noncondensing Shock and Vibration These specifications apply only to Compact FieldPoint. NI recommends Compact FieldPoint if your application is subject to shock and vibration. Operating vibration, random (IEC 60068-2-64) ............................... Operating vibration, sinusoidal (IEC 60068-2-6) ................................. Operating shock (IEC 60068-2-27) ............................... 50 g, 3 ms half sine, 18 shocks at 6 orientations; 30 g, 11 ms half sine, 18 shocks at 6 orientations 10 to 500 Hz, 5 g 10 to 500 Hz, 5 grms Safety This product meets the requirements of the following standards of safety for electrical equipment for measurement, control, and laboratory use: ◾◾ IEC 61010-1, EN 61010-1 ◾◾ uL 61010-1, CSA 61010-1 Note: For uL and other safety certifications, refer to the product label or the Online Product Certification section. Electromagnetic Compatibility This product meets the requirements of the following EMC standards for electrical equipment for measurement, control, and laboratory use: ◾◾ EN 61326 (IEC 61326): Class A emissions; Industrial immunity ◾◾ EN 55011 (CISPR 11): Group 1, Class A emissions ◾◾ AS/NZS CISPR 11: Group 1, Class A emissions ◾◾ FCC 47 CFR Part 15B: Class A emissions ◾◾ ICES-001: Class A emissions Note: For the standards applied to assess the EMC of this product, refer to the Online Product Certification section. Note: For EMC compliance, operate this product according to the documentation. CE Compliance This product meets the essential requirements of applicable European Directives as follows: ◾◾ 2006/95/EC; Low-Voltage Directive (safety) ◾◾ 2004/108/EC; Electromagnetic Compatibility Directive (EMC) B uY ONLINE at ni.com or C ALL 800 813 36 93 (u.S.) 4 NI Services and Support NI has the services and support to meet MA IN IN TA PL your needs around the globe and through the application life cycle – from planning and development through deployment and ongoing maintenance. We offer services and service levels to meet customer requirements in research, design, validation, and manufacturing. Visit ni.com/services. Local Sales and Technical Support In offices worldwide, our staff is local to the country, giving you access to engineers who speak your language. NI delivers industry-leading technical support through online knowledge bases, our applications engineers, and access to 14,000 measurement and automation professionals within NI Developer Exchange forums. Find immediate answers to your questions at ni.com/support. We also offer service programs that provide automatic upgrades to your application development environment and higher levels of technical support. Visit ni.com/ssp. AN SERVICE NEEDS LO Y V DE Training and Certification NI training is the fastest, most certain route to productivity with our products. NI training can shorten your learning curve, save development time, and reduce maintenance costs over the application life cycle. We schedule instructor-led courses in cities worldwide, or we can hold a course at your facility. We also offer a professional certification program that identifies individuals who have high levels of skill and knowledge on using NI products. Visit ni.com/training. EL OP Professional Services Our NI Professional Services team is composed of NI applications and systems engineers and a worldwide National Instruments Alliance Partner program of more than 600 independent consultants and integrators. Services range from start-up assistance to turnkey system integration. Visit ni.com/alliance. OEM Support We offer design-in consulting and product integration assistance if you want to use our products for OEM applications. For information about special pricing and services for OEM customers, visit ni.com/oem. P DE Hardware Services System Assurance Programs NI system assurance programs are designed to make it even easier for you to own an NI system. These programs include configuration and deployment services for your NI PXI, CompactRIO, or Compact FieldPoint system. The NI Basic System Assurance Program provides a simple integration test and ensures that your system is delivered completely assembled in one box. When you configure your system with the NI Standard System Assurance Program, you can select from available NI system driver sets and application development environments to create customized, reorderable software configurations. Your system arrives fully assembled and tested in one box with your software preinstalled. When you order your system with the standard program, you also receive systemspecific documentation including a bill of materials, an integration test report, a recommended maintenance plan, and frequently asked question documents. Finally, the standard program reduces the total cost of owning an NI system by providing three years of warranty coverage and calibration service. use the online product advisors at ni.com/advisor to find a system assurance program to meet your needs. Calibration Services NI recognizes the need to maintain properly calibrated devices for highaccuracy measurements. We provide manual calibration procedures, services to recalibrate your products, and automated calibration software specifically designed for use by metrology laboratories. Visit ni.com/calibration. Repair and Extended Warranty NI provides complete repair services for our products. Express repair and advance replacement services are also available. We offer extended warranties to help you meet project life-cycle requirements. Visit ni.com/services. ni.com n 8 00 813 3693 n National Instruments info@ni.com ©2009 National Instruments. All rights reserved. CompactRIO, FieldPoint, National Instruments, National Instruments Alliance Partner , NI, ni.com, and NI Developer Suite are trademarks of National Instruments. Other product and company names listed are trademarks or trade names of their respective companies. A National Instruments Alliance Partner is a business entity independent from National Instruments and has no agency, partnership, or joint-venture relationship with National Instruments. 0644
NICFP-2220 价格&库存

很抱歉,暂时无法提供与“NICFP-2220”相匹配的价格&库存,您可以联系我们找货

免费人工找货