UNO2-PS/1AC/48DC/240W - Power supply unit
1110155
https://www.phoenixcontact.com/us/products/1110155
Please be informed that the data shown in this PDF document is generated from our online catalog. Please find the complete data in the user
documentation. Our general terms of use for downloads are valid.
Primary-switched power supply unit, UNO POWER, Screw connection, DIN rail mounting, input: 1-phase, output: 48 V DC / 5 A,
adjustable from 42 V DC ... 56 V DC
Your advantages
• Save space in the control cabinet with an extremely narrow overall width of just 45 mm
• Save energy, thanks to a high degree of efficiency
• Outdoor installation possible, with a wide temperature range of -25°C … +70°C
• Simple output voltage monitoring, thanks to the floating DC OK relay contact
Commercial data
Item number
1110155
Packing unit
1 pc
Minimum order quantity
1 pc
Sales key
CM15
Product key
CMPV14
GTIN
4063151024840
Weight per piece (including packing)
888 g
Weight per piece (excluding packing)
855 g
Customs tariff number
85044095
Country of origin
TH
Jan 8, 2024, 9:50 AM
Page 1 (19)
UNO2-PS/1AC/48DC/240W - Power supply unit
1110155
https://www.phoenixcontact.com/us/products/1110155
Technical data
Input data
AC operation
Supply system configuration
Star network (TN, TT, IT (PE))
Nominal input voltage range
100 V AC ... 240 V AC
Input voltage range
100 V AC ... 240 V AC -15 % ... +10 %
Derating
< 90 V AC (1 %/V)
Typical national grid voltage
120 V AC
230 V AC
Voltage type of supply voltage
AC
Inrush current
typ. 10 A (at 25 °C)
2
Inrush current integral (I t)
< 0.05 A2s
Frequency range (fN)
50 Hz ... 60 Hz ±10 %
Mains buffering time
typ. 20 ms (120 V AC)
typ. 20 ms (230 V AC)
Current consumption
2.6 A (100 V AC)
2.2 A (120 V AC)
1.16 A (230 V AC)
1.2 A (240 V AC)
Protective circuit
Transient surge protection; Varistor, gas-filled surge arrester
Switch-on time
typ. 530 ms
Device mains fuse
5 A internal (device protection), fast-blow
Recommended breaker for input protection
10 A ... 16 A (Characteristic B, C, D, K or comparable)
Discharge current to PE
< 3.5 mA
Output data
Efficiency
typ. 91.5 % (120 V AC)
typ. 93 % (230 V AC)
Nominal output voltage
48 V DC
Setting range of the output voltage (USet)
42 V DC ... 56 V DC (≥48 V DC, constant capacity
restricted 60 V DC (on (flashing green))
Electrical properties
Number of phases
1.00
Insulation voltage input/output
4 kV AC (type test)
3 kV AC (routine test)
Insulation voltage input / PE
3.5 kV AC (type test)
2.4 kV AC (routine test)
Product properties
Product type
Power supply
Product family
UNO POWER
MTBF (IEC 61709, SN 29500)
> 1000000 h (25 °C)
> 550000 h (40 °C)
Jan 8, 2024, 9:50 AM
Page 4 (19)
UNO2-PS/1AC/48DC/240W - Power supply unit
1110155
https://www.phoenixcontact.com/us/products/1110155
> 280000 h (55 °C)
Environmental protection directive
RoHS Directive 2011/65/EU
WEEE
Reach
Insulation characteristics
Protection class
I
Degree of pollution
2
Dimensions
Item dimensions
Width
45 mm
Height
130 mm
Depth
129 mm
125 mm (Device depth (DIN rail mounting))
Installation dimensions
Installation distance right/left (active, passive)
0 mm / 0 mm (POut ≥50% )
Installation distance top/bottom (active, passive)
30 mm / 30 mm (POut ≥50% )
Mounting
Mounting type
DIN rail mounting
Assembly instructions
alignable: 0 mm horizontally, 30 mm vertically
Mounting position
horizontal DIN rail NS 35, EN 60715
With protective coating
No
Material specifications
Flammability rating according to UL 94
V0 (Housing, terminal blocks)
Housing material
Metal
Hood version
Stainless steel
Side element version
Aluminum
Foot latch material
Sheet steel, zinc-plated
Housing material
Aluminum (AlMg3) / sheet steel, zinc-plated
Environmental and real-life conditions
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C (> 55 °C Derating: 2.5 %/K)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Ambient temperature (start-up type tested)
-40 °C
Maximum altitude
≤ 3000 m (> 2000 m, Derating: 10 %/1000 m)
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Shock (operation)
18 ms, 30g, per spatial direction (IEC 60068-2-27)
Vibration (operation)
10 Hz ... 50 Hz, amplitude ±0.2 mm
Jan 8, 2024, 9:50 AM
Page 5 (19)
UNO2-PS/1AC/48DC/240W - Power supply unit
1110155
https://www.phoenixcontact.com/us/products/1110155
50 Hz to 150 Hz, 2.3 g, 90 min.
Standards and regulations
Overvoltage category
EN 61010-1
II (≤ 3000 m)
Overvoltage category
EN 62477-1
III (≤3000 m)
Safety of power supply units up to 1100 V (insulation distances)
Standard designation
Safety of power supply units up to 1100 V (insulation distances)
Standards/specifications
DIN EN 61558-2-16
Electrical safety
Standard designation
Electrical safety
Standards/specifications
IEC 61010-2-201 (SELV)
Electronic equipment for use in power installations
Standard designation
Equipping high voltage installations with electronic equipment
Standards/specifications
EN 50178/VDE 0160 (PELV)
Safety for measurement, control, and laboratory equipment
Standard designation
Safety for equipment for measurement, control, and laboratory
use
Standards/specifications
IEC 61010-1
Protective extra-low voltage
Standard designation
Protective extra-low voltage
Standards/specifications
IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Safe isolation
Standard designation
Safe isolation
Standards/specifications
IEC 61558-2-16
IEC 61010-2-201
Limitation of harmonic line currents
Standard designation
Limitation of harmonic line currents
Standards/specifications
EN 61000-3-2
Mains voltage dips
Standard designation
Requirement of the semiconductor industry with regard to mains
voltage dips
Standards/specifications
SEMI F47 - 0706 (185 V AC)
Approvals
UL
Identification
UL/C-UL Listed UL 61010-1
Jan 8, 2024, 9:50 AM
Page 6 (19)
UNO2-PS/1AC/48DC/240W - Power supply unit
1110155
https://www.phoenixcontact.com/us/products/1110155
UL
Identification
UL/C-UL Listed UL 61010-2-201
UL
Identification
UL/C-UL Listed ANSI/UL 121201 Class I, Division 2, Groups A,
B, C, D (Hazardous Location)
SIQ
Identification
CB scheme (IEC 61010-1, IEC 61010-2-201)
EMC data
Low Voltage Directive
Conformance with Low Voltage Directive 2014/35/EC
Interference emission
Interference emission in accordance with EN 61000-6-3
(residential and commercial) and EN 61000-6-4 (industrial)
EMC requirements for noise immunity
EN 61000-6-2
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Conducted noise emission
EN 55016
EN 61000-6-3 (Class B)
Noise emission
EN 55016
EN 61000-6-3 (Class B)
Harmonic currents
Standards/regulations
EN 61000-3-2
EN 61000-3-2 (Class A)
Frequency range
0 kHz ... 2 kHz
Flicker
Standards/regulations
EN 61000-3-3
Frequency range
0 kHz ... 2 kHz
Electrostatic discharge
Standards/regulations
EN 61000-4-2
Electrostatic discharge
Contact discharge
6 kV (Test Level 3)
Discharge in air
8 kV (Test Level 3)
Comments
Criterion A
Electromagnetic HF field
Standards/regulations
EN 61000-4-3
Electromagnetic HF field
Frequency range
80 MHz ... 1 GHz
Test field strength
10 V/m (Test Level 3)
Frequency range
1 GHz ... 6 GHz
Test field strength
10 V/m (Test Level 3)
Comments
Criterion A
Jan 8, 2024, 9:50 AM
Page 7 (19)
UNO2-PS/1AC/48DC/240W - Power supply unit
1110155
https://www.phoenixcontact.com/us/products/1110155
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Fast transients (burst)
Input
4 kV (Test Level 4 - asymmetrical)
Output
2 kV (Test Level 3 - asymmetrical)
Comments
Criterion A
Surge voltage load (surge)
Standards/regulations
EN 61000-4-5
Input
2 kV (Test Level 4 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Output
1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Comments
Criterion A
Conducted interference
Standards/regulations
EN 61000-4-6
Conducted interference
Input/Output
asymmetrical
Frequency range
0.15 MHz ... 80 MHz
Comments
Criterion A
Voltage
10 V (Test Level 3)
Voltage dips
Standards/regulations
EN 61000-4-11
Voltage
230 V AC
Frequency
50 Hz
Voltage dip
70 %
Number of periods
25 / 30 periods
Comments
Criterion A
Voltage dip
40 %
Number of periods
12 periods
Additional text
Test Level 2
Comments
Criterion A
Voltage dip
0%
Number of periods
1 period
Additional text
Test Level 2
Comments
Criterion B
Criteria
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected
by the device itself.
Jan 8, 2024, 9:50 AM
Page 8 (19)
UNO2-PS/1AC/48DC/240W - Power supply unit
1110155
https://www.phoenixcontact.com/us/products/1110155
Drawings
Power Factor
Diagram
1,1
1,0
0,9
0,8
0,7
0,6
0,5
0,4
0,3
0
= UIn: 120 V AC/UOut : 48 V DC
= UIn: 230 V AC/UOut : 48 V DC
1
2
3
4
5
IOut [A]
Power factor
Jan 8, 2024, 9:50 AM
Page 9 (19)
UNO2-PS/1AC/48DC/240W - Power supply unit
1110155
https://www.phoenixcontact.com/us/products/1110155
Dimensional drawing
UNO POWER
Ord.No.1110155
45
3.1 3.2 2.1 2.2 2.3 2.4
13
+
+
14
Output DC
48V 240W
42-56 V
130
DC OK
Input AC
100-240V
L N
1.1 1.2 1.3
Device dimensions (dimensions in mm)
Jan 8, 2024, 9:50 AM
Page 10 (19)
UNO2-PS/1AC/48DC/240W - Power supply unit
1110155
https://www.phoenixcontact.com/us/products/1110155
Block diagram
Input AC
1.1
L
1.2
N
1.3
Output DC
Filter
aktive
PFC
2.1
Filter
2.2
+
2.3
2.4
Signal
Functions
UVP
OVP
3.1
3.2
13
14
User Interface
OTP
OCP
SCP
UOUT
DC OK
Block diagram
Eta [%]
Diagram
96
95
94
93
92
91
90
89
88
87
86
1
2
= UIn: 120 V AC/UOut : 48 V DC
= UIn: 230 V AC/UOut : 48 V DC
3
4
5
IOut [A]
Efficiency
Jan 8, 2024, 9:50 AM
Page 11 (19)
UNO2-PS/1AC/48DC/240W - Power supply unit
1110155
https://www.phoenixcontact.com/us/products/1110155
Schematic diagram
Housing
Signaling
PE
3.1 13
1.1
3.2 14
B
Input
L 1.2
N 1.3
C
D
A
Output
2.1
2.2
2.3
2.4
+
Test sections, insulation voltage
Jan 8, 2024, 9:50 AM
Page 12 (19)
UNO2-PS/1AC/48DC/240W - Power supply unit
1110155
https://www.phoenixcontact.com/us/products/1110155
IIn [A]
Diagram
2,5
2
1,5
1
0,5
= UIn: 120 V AC/UOut : 48 V DC
= UIn: 230 V AC/UOut : 48 V DC
0
0
1
2
3
4
5
IOut [A]
Input current/output current
Dimensional drawing
130
48
80
130
125
Device dimensions (dimensions in mm)
Jan 8, 2024, 9:50 AM
Page 13 (19)
UNO2-PS/1AC/48DC/240W - Power supply unit
1110155
https://www.phoenixcontact.com/us/products/1110155
POut [%]
Diagram
120
110
100
90
80
70
60
50
PN 100% ≤ 50°C
0
1000
2000
3000
4000
5000
H [m]
Output power/installation altitude
Jan 8, 2024, 9:50 AM
Page 14 (19)
UNO2-PS/1AC/48DC/240W - Power supply unit
1110155
https://www.phoenixcontact.com/us/products/1110155
Approvals
To download certificates, visit the product detail page: https://www.phoenixcontact.com/us/products/1110155
cULus Listed
Approval ID: FILE E 123528
EAC
Approval ID: RU S-DE.BL08.W.00764
cULus Listed
Approval ID: FILE E 199827
Jan 8, 2024, 9:50 AM
Page 15 (19)
UNO2-PS/1AC/48DC/240W - Power supply unit
1110155
https://www.phoenixcontact.com/us/products/1110155
Classifications
ECLASS
ECLASS-11.0
27040701
ECLASS-12.0
27040701
ECLASS-13.0
27040701
ETIM
ETIM 9.0
EC002540
UNSPSC
UNSPSC 21.0
39121000
Jan 8, 2024, 9:50 AM
Page 16 (19)
UNO2-PS/1AC/48DC/240W - Power supply unit
1110155
https://www.phoenixcontact.com/us/products/1110155
Environmental product compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 25;
For information on hazardous substances, refer to the
manufacturer’s declaration available under “Downloads”
Jan 8, 2024, 9:50 AM
Page 17 (19)
UNO2-PS/1AC/48DC/240W - Power supply unit
1110155
https://www.phoenixcontact.com/us/products/1110155
Accessories
TRIO-DIODE/48DC/2X10/1X20 - Redundancy module
2866527
https://www.phoenixcontact.com/us/products/2866527
Redundancy module with function
monitoring, 48 V DC, 2x 10 A, 1x 20 A
PLT-SEC-T3-230-FM-UT - Type 3 surge protection device
2907919
https://www.phoenixcontact.com/us/products/2907919
Type 2/3 surge protection, consisting
of protective plug and base element
with screw connection. For singlephase power supply network with
integrated status indicator and remote
signaling. Nominal voltage:
230 V AC/DC
PLT-SEC-T3-230-FM-PT - Type 3 surge protection device
2907928
https://www.phoenixcontact.com/us/products/2907928
Type 2/3 surge protection, consisting
of protective plug and base element
with Push-in connection. For singlephase power supply network with
integrated status indicator and remote
signaling. Nominal voltage:
230 V AC/DC
Jan 8, 2024, 9:50 AM
Page 18 (19)
UNO2-PS/1AC/48DC/240W - Power supply unit
1110155
https://www.phoenixcontact.com/us/products/1110155
Phoenix Contact 2024 © - all rights reserved
https://www.phoenixcontact.com
Phoenix Contact USA
586 Fulling Mill Road
Middletown, PA 17057, United States
(+717) 944-1300
info@phoenixcon.com
Jan 8, 2024, 9:50 AM
Page 19 (19)