Sensor/Actuator cable, 4-position, PUR/PVC, Yellow RAL 1021, Plug angled M12, A-coded, on Socket angled
M12, A-coded, Cable length: 0.3 m, DESINA
Product Features
Easy and safe: 100% electrically tested plug-in components
Convenient: simplified planning with connecting cables according to DESINA standard
Key commercial data
Packing unit
11
Weight per Piece (excluding packing)
35.7 GRM
Custom tariff number
85444290
Country of origin
Germany
Technical data
Dimensions
Length of cable
0.3 m
Ambient conditions
Ambient temperature (operation)
-25 °C ... 90 °C (Plug / socket)
Degree of protection
IP65
IP67
IP68
General
Rated current at 40°C
4A
Rated voltage
250 V
12.11.2013 Page 1 / 5
https://www.phoenixcontact.com/us/products/1696138
Sensor/Actuator cable - SAC-4P-M12MR/0,3-PUR/M12FR D - 1696138
Technical data
General
Number of positions
4
Contact resistance
≤ 5 mΩ
Insulation resistance
≥ 100 MΩ
Coding
A - standard
Status display
No
Protective circuit/component
Unwired
Surge voltage category
II
Pollution degree
3
Insertion/withdrawal cycles
≥ 100
Material
Inflammability class according to UL 94
HB
Contact material
CuSn
Contact surface material
Ni/Au
Contact carrier material
TPU GF
Material of grip body
TPU, hardly inflammable, self-extinguishing
Material, knurls
Zinc die-cast, nickel-plated
Sealing material
NBR
Cable
Cable type
PUR/PVC yellow
Cable type (abbreviation)
140
Cable abbreviation
LiYY-11Y
UL AWM style
20549
Conductor cross section
0.34 mm²
AWG signal line
22
Conductor structure signal line
42x 0.10 mm
Core diameter including insulation
1.5 mm ±0.05 mm
Thickness, insulation
approx. 0.3 mm (Core insulation)
≥ 0.38 mm (Outer cable sheath)
approx. 0.35 mm (Inner sheath)
Wire colors
brown, white, blue, black
Overall twist
4 wires, twisted
External sheath, color
Yellow RAL 1021
External cable diameter D
5.2 mm ± 0.2 mm
Smallest bending radius, fixed installation
52 mm
Smallest bending radius, movable installation
52 mm
Number of bending cycles
2000000
12.11.2013 Page 2 / 5
https://www.phoenixcontact.com/us/products/1696138
Sensor/Actuator cable - SAC-4P-M12MR/0,3-PUR/M12FR D - 1696138
Technical data
Cable
Bending radius
52 mm
Traversing path
5m
Traversing rate
3 m/s
Cable weight
39 kg/km
Outer sheath, material
PUR
Material, inner sheath
PVC
Material conductor insulation
PVC
Conductor material
Bare Cu litz wires
Insulation resistance
≥ 1 GΩ*km (at 20 °C)
Conductor resistance
max. 58 Ω/km (at 20 °C)
Nominal voltage, cable
≤ 300 V
Test voltage, cable
≥ 3000 V
Flame resistance
in accordance with DIN UL-Style 20549
Ambient temperature (operation)
-25 °C ... 80 °C (cable, fixed installation)
-5 °C ... 80 °C (cable, flexible installation)
Classifications
eCl@ss
eCl@ss 4.0
27060306
eCl@ss 4.1
27060306
eCl@ss 5.0
27061801
eCl@ss 5.1
27061801
eCl@ss 6.0
27061801
eCl@ss 7.0
27061801
eCl@ss 8.0
27061801
ETIM
ETIM 2.0
EC000830
ETIM 3.0
EC001855
ETIM 4.0
EC001855
ETIM 5.0
EC001855
UNSPSC
UNSPSC 6.01
31251501
UNSPSC 7.0901
31251501
UNSPSC 11
31251501
UNSPSC 12.01
31251501
12.11.2013 Page 3 / 5
https://www.phoenixcontact.com/us/products/1696138
Sensor/Actuator cable - SAC-4P-M12MR/0,3-PUR/M12FR D - 1696138
Classifications
UNSPSC
UNSPSC 13.2
31251501
Approvals
Approvals
Approvals
UL Listed / GOST / cUL Listed / cULus Listed
Ex Approvals
Approvals submitted
Approval details
UL Listed
Nominal current IN
4A
Nominal voltage UN
300 V
GOST
cUL Listed
Nominal current IN
4A
Nominal voltage UN
300 V
cULus Listed
12.11.2013 Page 4 / 5
https://www.phoenixcontact.com/us/products/1696138
Sensor/Actuator cable - SAC-4P-M12MR/0,3-PUR/M12FR D - 1696138
Drawings
Schematic diagram
Schematic diagram
4
3
3
4
1
2
2
1
Pin assignment M12 plug, 4-pos., A-coded, view plug side
Pin assignment M12 socket, 12-pos., A-coded, view female side
Cable cross section
Dimensioned drawing
Ø14,8
Ø12
30,9
M12
PUR/PVC yellow [140]
36,3
M12 x 1 male plug, angled, shielded
Dimensioned drawing
Circuit diagram
Ø14,8
1
1
4
4
3
3
2
2
Ø12
28
M12
36,3
Contact assignment of the M12 plug and the M12 socket
M12 x 1 socket, angled, shielded
© Phoenix Contact 2013 - all rights reserved
http://www.phoenixcontact.com
12.11.2013 Page 5 / 5