Inline analog output terminal, without accessories, 1 output, 0-20 mA,
4-20 mA, 0-10 V, 2-wire connection method
Product notes
WEEE/RoHS-compliant since:
07/09/2007
Commercial data
GTIN (EAN)
4
017918
168131
sales group
K412
Pack
1 pcs.
Customs tariff
85389091
Catalog page information
Page 80 (AX-2007)
http://
www.download.phoenixcontact.com
Please note that the data given
here has been taken from the
online catalog. For comprehensive
information and data, please refer
to the user documentation. The
General Terms and Conditions of
Use apply to Internet downloads.
Product description
The analog Inline output terminals are used in applications in which analog actuators are to be addressed.
With these terminals, common current and voltage output ranges can be configured individually. The analog signals are
made available with a resolution of 16 bits.
It goes without saying that you also have advantages in handling with the analog Inline output terminals, such as multiwire connection or the automatic contact with the grounding conductor when the terminal is snapped onto the DIN rail.
The Inline terminals can be labeled using hinged labeling fields. The fields have insert cards that can be labeled
individually to suit the application. Additionally, there is the proven ZBFM-6... Zack strip for labeling the terminal points.
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 1 / 6
Feb 7, 2011
IB IL AO 1/SF Order No.: 2726298
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2726298
Technical data
General data
Width
24.4 mm
Height
119.8 mm
Depth
71.5 mm
Weight
46 g
Mounting type
DIN rail
Ambient temperature (operation)
-25 °C ... 55 °C
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection
IP20
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Test section
7.5 V supply (bus logic), 24 V supply UANA / I/O 500 V AC 50 Hz 1
min
7.5 V supply (bus logic), 24 V supply UANA/functional earth ground
500 V AC 50 Hz 1 min
24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min
Interface
Name
Inline local bus
Type of connection
Inline data jumper
Transmission speed
500 kbps
500 kBit/s
Transmission physics
Copper
Inline potential routing
Communications power UL
7.5 V DC (via voltage jumper)
Current consumption from UL
max. 40 mA
Typ. 30 mA
I/O supply voltage UANA
24 V DC
Current consumption from UANA
max. 65 mA
Typ. 50 mA
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 2 / 6
Feb 7, 2011
IB IL AO 1/SF Order No.: 2726298
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2726298
Analog outputs
Number of outputs
1
Connection method
2-wire (shielded)
Output name
Analog outputs
D/A conversion time
< 100 µs
D/A resolution
16 Bit
Type of protection
Transient protection of outputs
Measured value representation
16 bits (15 bits + sign bit)
DAC resolution
16 Bit
Process data update
< 1 ms
Current output signal
0 mA ... 20 mA
4 mA ... 20 mA
Load/output load current output
> 500 Ω
Voltage output signal
0 V ... 10 V
Load/output load voltage output
> 2 kΩ 0.05 %
Precision
Typ. 0.8 % (of output range final value)
Typ. 0.5 % (of output range final value)
Certificates / Approvals
Certification
CUL, GOST, UL
Certification Ex:
CUL-EX, PxC-EX, UL-EX LIS
Accessories
Item
Designation
Description
1051993
B-STIFT
Marker pen, for manual labeling of unprinted Zack strips, smearproof and waterproof, line thickness 0.5 mm
0809492
ESL 62X10
Insert strip for laser printer, lettering field: 62 x 10 mm
2727501
IB IL FIELD 2
Labeling field, width: 12.2 mm
Marking
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 3 / 6
Feb 7, 2011
IB IL AO 1/SF Order No.: 2726298
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2726298
0811228
X-PEN 0,35
Marker pen without ink cartridge, for manual labeling of markers,
labeling extremely wipe-proof, line thickness 0.35 mm
0808778
ZBF 6:SO/CMS
Zack strip, flat, 10-section, divisible, special printing, marking
according to customer requirements
0808710
ZBF 6:UNBEDRUCKT
Zack strip, flat, unprinted: 10-section, for individual labeling with
M-PEN or ZBF-T, sufficient for 100 terminal blocks, color: white
0803618
ZBFM 6/WH:UNBEDRUCKT
Zack marker sheet, flat, unprinted: 100-section, 10 strips à 10
markers, sufficient for 100 terminal blocks, for all terminal blocks,
pitch 6.2 mm, labeling with M-PEN or CMS system, color: white
0803650
ZBFM 6:SO/CMS
Special printing, Zack marker sheet, flat, 100-section, divisible,
marking according to customer requirements
2732664
IB IL AO/CNT-PLSET
Connector set
2726353
IB IL SCN-6 SHIELD
Inline shield connector
2726337
IB IL SCN-8
Connector, for digital 1, 2 or 8-channel Inline terminals
2727608
IB IL SCN-8-CP
Inline connector, colored
Plug/Adapter
Diagrams/Drawings
Connection diagram
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 4 / 6
Feb 7, 2011
IB IL AO 1/SF Order No.: 2726298
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2726298
Block diagram
Dimensioned drawing
FAQs
•
How many and which I/O connectors have to be used to connect the analog conductor for the Inline terminal
IB IL AO 1/SF?
Two connectors must be used, since this terminal is a double terminal (24.4 mm wide). The available channel can
be used as either voltage or current output. In order to connect an analog conductor, an Inline shield connector (IB
IL SCN-6-SHIELD, Order no. 2726353) must be used and snapped into the left (voltage output) or right slot (current
output) to suit the application. One free slot is always left over and this must be occupied by another connector.
We recommend using a standard Inline connector without shield (IB IL SCN-8, Order no. 2726337). The connector
versions necessary are in the connector set IB IL AO/CNT-PLSET (Order no. 2732664).
•
Output behavior of the analog output terminals after a bus error
The output behavior of the Inline analog terminals after a bus error is different from the standard behavior of familiar
INTERBUS analog modules. An interruption in the bus within a particular time window can lead to an undefined
output behavior. In this case, it is not possible to clearly determine whether the outputs return to zero, or whether the
old value is retained.
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 5 / 6
Feb 7, 2011
IB IL AO 1/SF Order No.: 2726298
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2726298
Address
PHOENIX CONTACT Inc., USA
586 Fulling Mill Road
Middletown, PA 17057,USA
Phone (800) 888-7388
Fax (717) 944-1625
http://www.phoenixcon.com
© 2011 Phoenix Contact
Technical modifications reserved;
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 6 / 6
Feb 7, 2011