ILB IB AI4 AO2
1 2
E4
Inline Block IO Module for INTERBUS
With 4 Analog Inputs and 2 Analog Outputs
AO
RT
E3
AI4
RT
E2
SF
UL
RC
BATR
US
RD
PW
BU
D3
AI3
RT
E1
1/2
D4
D2
AI2
RT
D1
AI1
R
S2
S1
BU
AUTOMATIONWORX
Data Sheet
7280_en_02
1
© PHOENIX CONTACT - 02/2007
Description
The ILB IB AI4 AO2 module is designed for use within an
INTERBUS network. It is used to acquire analog input
signals and output analog signals.
Features of INTERBUS
–
–
–
–
Remote bus branch; Inline connector
500 kbps transmission speed
I/O areas can be parameterized individually for each
channel
Parameterization via process data or PCP
Features of Inputs
–
–
–
–
4 differential analog signal inputs or
4 universal RTD inputs
Connection of sensors in 2, 3 or 4-wire technology
Sensor supply with channel-specific integrated
short-circuit and overload protection
Three current measuring ranges:
0 mA to 20 mA, ±20 mA, 4 mA to 20 mA
–
–
–
–
–
Four voltage measuring ranges:
0 V to 5 V, ±5 V, 0 V to 10 V, ±10 V
Various RTD measuring ranges:
E.g., linear R: 0 Ω to 9500 Ω, Pt 100, Pt 1000, Ni 1000
Measured value representation in four possible formats
16-bit measured value resolution (15 bits + sign bit)
Adjustable filter times
Features of Outputs
–
–
–
–
–
2 universal analog signal outputs to connect either
voltage or current signals
Connection of actuators in 2-wire technology
Three current ranges:
0 mA to 20 mA, ±20 mA, 4 mA to 20 mA
Four voltage ranges:
0 V to 5 V, ±5 V, 0 V to 10 V, ±10 V
Short-circuit-proof outputs
Please refer to the "Assembly and Removal of Inline Block IO Modules" application note (see "Ordering Data"
on page 4).
Make sure you always use the latest documentation.
It can be downloaded at www.download.phoenixcontact.com.
A conversion table is available on the Internet at
www.download.phoenixcontact.com/general/7000_en_00.pdf.
ILB IB AI4 AO2
Table of Contents
1
2
3
4
5
6
7
Description.................................................................................................................................. 1
Ordering Data ............................................................................................................................. 4
Technical Data............................................................................................................................ 4
Internal Circuit Diagram.............................................................................................................12
Electrical Isolation......................................................................................................................13
Local Diagnostic and Status Indicators .....................................................................................13
Connection of INTERBUS, Supply, Analog Sensors, and Actuators.........................................14
7.1
7.2
7.3
7.4
7.5
8
9
Terminal Point Assignment of the INTERBUS Connectors.......................................................................... 15
Terminal Point Assignment of the Power Connector ................................................................................... 15
Terminal Point Assignment of the Connectors for the Analog Inputs........................................................... 15
Terminal Point Assignment of the Connectors for the Analog RTD Inputs .................................................. 16
Terminal Point Assignment of the Connectors for the Analog Outputs........................................................ 16
Connection Notes ......................................................................................................................17
Connection Examples................................................................................................................17
9.1
9.2
9.3
Connection Examples for Analog Inputs ...................................................................................................... 18
Connection Examples for RTD Inputs.......................................................................................................... 19
Connection Examples for Analog Outputs ................................................................................................... 19
10 Programming Data ....................................................................................................................20
11 Process Data .............................................................................................................................20
11.1
Assignment of the Process Data to the Terminal Points for the
"Read and Write Analog Values" Command................................................................................................ 21
12 OUT Process Data Words .........................................................................................................22
13 IN Process Data Words .............................................................................................................23
13.1
13.2
Input Word IN1 (Status Word)...................................................................................................................... 23
Input Words IN2 to IN5................................................................................................................................. 23
14 Formats for the Representation of Measured Values (IN2 to IN5) ............................................24
14.1
14.2
14.3
14.4
Format: "IB IL" (Default Setting)................................................................................................................... 24
Format: "RT" ................................................................................................................................................ 26
Format: "S7-Compatible" ............................................................................................................................. 27
Format: "Standardized Representation"....................................................................................................... 29
15 Configuration .............................................................................................................................31
16 Configuration via Process Data .................................................................................................31
16.1
16.2
16.3
Output Word OUT1 (Control Word) for Command Code 40xxhex (Configure Device) ................................. 31
Output Words OUT2 to OUT5 (Configuration) ............................................................................................. 32
Example for the Module Configuration via Process Data............................................................................. 33
17 Configuration via PCP ...............................................................................................................34
18 PCP Communication .................................................................................................................35
18.1
18.2
Object Dictionary.......................................................................................................................................... 35
Object Description........................................................................................................................................ 36
19 Diagnostics ................................................................................................................................38
7280_en_02
PHOENIX CONTACT
2
ILB IB AI4 AO2
20 Channel Conversion Times and Process Data Update Time ....................................................39
21 Behavior of the Analog Outputs in the Event of INTERBUS Reset and Power Up ...................40
22 Notes on Systematic and Random Errors During Resistance and Temperature Measurement...
40
22.1
22.2
22.3
22.4
7280_en_02
Measures to Optimize Tolerances ............................................................................................................... 40
Connection Method ...................................................................................................................................... 41
RTD 3-Wire Connection ............................................................................................................................... 41
Systematic Errors During Temperature Measurement With 2-Wire Technology ......................................... 42
PHOENIX CONTACT
3
ILB IB AI4 AO2
2
Ordering Data
Module
Description
Type
Order No.
Pcs./Pck.
ILB IB AI4 AO2
2878777
1
Accessories: Connectors as Replacement Item
Description
Type
Order No.
Pcs./Pck.
Shield connector for the bus connection (with color print)
IB IL SCN-6 SHIELD-CP
2863151
5
Connector for the supply (with color print)
On request
Inline Block IO module for INTERBUS
with 4 analog inputs and 2 analog outputs
Shield connector for the connection of analog sensors (without color print)
IB IL SCN-6 SHIELD
2726353
5
Shield connector for the connection of analog actuators (without color print)
IB IL SCN 6-SHIELD-TWIN
2740245
5
Connector (without color print)
IB IL SCN-8
2726337
10
Accessories: Other
Description
Type
Order No.
Pcs./Pck.
CLIPFIX 35-5
3022276
50
Documentation
Description
Type
Order No.
Pcs./Pck.
"Assembly and Removal of Inline Block IO Modules" application note
AH ILB INSTALLATION
9014931
1
"General Introduction to the INTERBUS System" user manual
IBS SYS INTRO G4 UM E
2745211
1
Recommended end clamp; placed both to the right and left of the module to
secure it on the DIN rail
"Peripherals Communication Protocol (PCP)" user manual
IBS SYS PCP G4 UM E
2745169
1
"Porting Using PCP Compact" user manual
IBS PCP COMPACT UM E
9015349
1
3
Technical Data
General Data
Housing dimensions with connectors (width x height x depth)
156 mm x 59 mm x 141 mm
Weight
505 g (with connectors)
Operating mode
INTERBUS
Transmission speed
500 kbps
Connection method for sensors
2, 3, and 4-wire technology (shielded)
Connection method for actuators
2-wire technology (shielded)
Housing Dimensions
120
59
141
156
7280B001
Figure 1
7280_en_02
Module housing dimensions (in mm)
PHOENIX CONTACT
4
ILB IB AI4 AO2
Ambient Conditions
Guidelines
Developed according to VDE 0160/EN 50178/IEC 62103, UL 508
Ambient temperature (operation)
-25°C to +60°C
Ambient temperature (storage/transport)
-25°C to +85°C
Humidity (operation/storage/transport)
10% to 95%, according to DIN EN 61131-2
Air pressure (operation)
80 kPa to 108 kPa (up to 2000 m above sea level)
Air pressure (storage/transport)
66 kPa to 108 kPa (up to 3500 m above sea level)
Degree of protection according to DIN 40050, IEC 60529
IP20
Protection class according to DIN 57106-1
Class 3 according to VDE 0106/IEC 60536
Air and creepage distances
According to DIN VDE 0110/IEC 60664, IEC 60664A,
DIN VDE 0160/EN 50178/IEC 62103
Housing material
Plastic, PVC-free, PBT, self-extinguishing (V0)
Pollution degree according to
EN 60664-1/IEC 60664-1, EN 61131-2/IEC 61131-2
2; condensation not permitted during operation
Surge voltage class
II
Electrical Isolation/Isolation of the Voltage Areas
Test Distance
Test Voltage
Incoming remote bus/logic area, outgoing remote bus
500 V AC, 50 Hz, 1 min.
Incoming remote bus/analog I/O
500 V AC, 50 Hz, 1 min.
Incoming remote bus/communications power UL (primary)
500 V AC, 50 Hz, 1 min.
Incoming remote bus/initiator supply UIS
500 V AC, 50 Hz, 1 min.
Incoming remote bus/functional earth ground
500 V AC, 50 Hz, 1 min.
Logic area, outgoing remote bus/analog I/O
500 V AC, 50 Hz, 1 min.
Logic area, outgoing remote bus/communications power UL (primary)
500 V AC, 50 Hz, 1 min.
Logic area, outgoing remote bus/initiator supply UIS
500 V AC, 50 Hz, 1 min.
Logic area, outgoing remote bus/functional earth ground
500 V AC, 50 Hz, 1 min.
Analog I/O/communications power UL (primary)
500 V AC, 50 Hz, 1 min.
Analog I/O/initiator supply UIS
500 V AC, 50 Hz, 1 min.
Analog I/O/functional earth ground
500 V AC, 50 Hz, 1 min.
Communications power UL (primary)/initiator supply UIS
500 V AC, 50 Hz, 1 min.
Communications power UL (primary)/functional earth ground
500 V AC, 50 Hz, 1 min.
Initiator supply UIS/functional earth ground
500 V AC, 50 Hz, 1 min.
Outgoing remote bus/analog I/O
500 V AC, 50 Hz, 1 min.
Outgoing remote bus/functional earth ground
500 V AC, 50 Hz, 1 min.
Mechanical Requirements
Vibration test sinusoidal vibrations according to
EN 60068-2-6/IEC 60068-2-6
5g load, 2.5 hours in each space direction
Shock test according to EN 60068-2-27/IEC 60068-2-27
30g load for 11 ms, half sinusoidal wave,
3 shocks in each space direction and orientation
Broadband noise according to EN 60068-2-64/IEC 60068-2-64
0.78g load, 2.5 hours in each space direction
7280_en_02
PHOENIX CONTACT
5
ILB IB AI4 AO2
Conformance With EMC Directive 89/336/EEC
Noise Immunity Test According to EN 61000-6-2
Electrostatic discharge (ESD)
EN 61000-4-2
IEC 61000-4-2
Criterion B
Electromagnetic fields
EN 61000-4-3
IEC 61000-4-3
Criterion A
Fast transients (burst)
EN 61000-4-4/
IEC 61000-4-4
Criterion B
6 kV contact discharge
8 kV air discharge
Field strength: 10 V/m
Remote bus: 2 kV
Power supply: 2 kV
I/O cables: 2 kV
Criterion A
All interfaces: 1 kV
Surge voltage
EN 61000-4-5
IEC 61000-4-5
Criterion B
DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical)
Signal lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical)
Conducted interference
EN 61000-4-6
IEC 61000-4-6
Criterion A
Test voltage 10 V
Noise Emission Test According to EN 61000-6-4
Noise emission of housing
EN 55011
Class A
Interface: INTERBUS
Incoming remote bus
Copper cable (RS-422), connected with Inline shield connector; supply
electrically isolated; shielding connected with a capacitor to functional earth
ground
Outgoing remote bus
Copper cable (RS-422), connected with Inline shield connector; supply
electrically isolated; shielding connected directly to functional earth ground
Recommended cable lengths
See INTERBUS system data in the IBS SYS INTRO G4 UM E user manual
24 V Module Supply (Communications Power and Sensor Supply; UL and US)
Nominal value
24 V DC
Tolerance
-15%/+20% according to EN 61131-2
Ripple
±5% according to EN 61131-2
Permissible range
19.2 V DC to 30.0 V DC
Current consumption at UL
See "Current Consumption at UL and US"
Current consumption at US
See "Current Consumption at UL and US"
Power dissipation at UL
See "Power Consumption at UL and US" on page 7
Power dissipation at US
See "Power Consumption at UL and US" on page 7
Safety equipment for UL
Transient surge protection via arresters, serial protection against polarity
reversal
Safety equipment for US
Transient surge protection via arresters, serial protection against polarity
reversal, channel-specific short-circuit protection with single-channel
diagnostics
Connection
Via power connectors
Diagnostics
Single-channel diagnostics in the process data
Failure indication via group error LED at PWR slot
Single-channel failure indication via LED at slot for the sensors
Electronically Protected Initiator Supply UIS (via Supply of US)
Nominal value UIS
24 V DC
Nominal current IIS per channel
50 mA
Protection
Internal, channel-specific electronic fuse,
short-circuit-proof with single-channel diagnostics
7280_en_02
PHOENIX CONTACT
6
ILB IB AI4 AO2
Current Consumption at UL and US
Typical
Maximum
Current consumption at UL
No-load operation of outputs and AI mode
100 mA
130 mA
RTD nominal load
100 mA
130 mA
AO U nominal load (UOUT1 and UOUT2 = 10 V with RL = 2 kΩ)
110 mA
140 mA
AO I nominal load (IOUT1 and IOUT2 = 20 mA with RL = 0 Ω)
135 mA
175 mA
Current consumption at US
IiS = 0 mA (no load)
12 mA
20 mA
IiS = 4 x 20 mA (nominal load)
92 mA
100 mA
IiS = 4 x 50 mA (maximum full load)
212 mA
220 mA
No-load operation of outputs and AI mode; IiS = 0 mA (no load)
112 mA
150 mA
AO U nominal load and AI nominal load; IiS = 4 x 20 mA
202 mA
240 mA
AO I nominal load and AI nominal load; IiS = 4 x 20 mA
227 mA
275 mA
AO I nominal load and AI full load; IiS = 4 x 50 mA
347 mA
395 mA
Total current consumption at UL and US
Power Consumption at UL and US
(Current Consumption at Voltages UL and US;
Specifications for Nominal Operation (UL = 24 V; US = 24 V Without Load), Full Load Same as Nominal Operation
But With US Under Load)
Typical Supply of Control AO Load
Marginal
Typical Supply
Typical Power
Cabinet Power Supply Unit
Conditions
Current
Dissipation
P24V_Supply
Typical power supply
P24V_Supply in U nominal operation
U mode of the analog outputs
(UOUT1,2 = 10 V with RL = 10 K)
IS = 0 mA
125 mA
3.00 W
Typical power supply
P24V_Supply in I nominal operation
I mode of the analog outputs
(IOUT1,2 = 20 mA, with Rb = 0 Ω)
IS = 0 mA
150 mA
3.60 W
Typical power supply
P24V_Supply in nominal operation
U mode of the analog outputs
(UOUT1,2 = 10 V with RL = 10 K)
IS = 4 x 20 mA
200 mA
4.80 W
Typical power supply
P24V_Supply at full load
I mode of the analog outputs
(IOUT1,2 = 20 mA, with Rb = 0 Ω)
IS = 4 x 20 mA
230 mA
5.45 W
Typical power supply
P24V_Supply in nominal operation
U mode of the analog outputs
(UOUT1,2 = +10 V with RL = 10 K)
IS = 4 x 50 mA
325 mA
7.75 W
Typical power supply
P24V_Supply at full load
I mode of the analog outputs
(IOUT1,2 = 20 mA, with Rb = 0 Ω)
IS = 4 x 50 mA
350 mA
8.35 W
Analog Inputs
Number
4 differential analog inputs
Measured value resolution
16 bits (15 bits + sign bit)
Measured value representation
In the following formats:
IB IL
RT
S7-compatible
Standardized representation
(15 bits with sign bit)
(15 bits with sign bit)
(15 bits with sign bit)
(15 bits with sign bit)
For measured value representation, please refer to the notes on page 24 and onwards.
Filtering
RFI filtering; passive TP 1st order
Filter time of the A/D converter
4.5 ms (default) or 1.1 ms; adjustable for each channel
Conversion time of the A/D converter
180 µs
Channel conversion times and process data update time
See "Channel Conversion Times and Process Data Update Time" on page 39
Limit frequency (-3 dB) of the input filters
120 Hz (for 4.5 ms filter default) or 450 Hz (for 1.1 ms filter)
Transient protection
Yes, via arresters
Signal connection method
2, 3, and 4-wire connection; shielded, twisted pair cable
Overload protection
Yes, ±30 V DC, minimum
7280_en_02
PHOENIX CONTACT
7
ILB IB AI4 AO2
Differential Analog Voltage Inputs
Number
4
Input range
0 V to 10 V; ±10 V; 0 V to 5 V; ±5 V
Input resistance
276 kΩ, typical
Open circuit response
Goes to 0 V
Maximum permissible voltage between analog voltage inputs and functional
earth ground
±50 V DC
Differential Analog Current Inputs
Number
4
Input range
0 mA to 20 mA; ±20 mA; 4 mA to 20 mA
Input resistance
107 Ω, typical
Open circuit response
Goes to 0 mA
Maximum permissible current per current input
Electronic overload protection
Overload protection at the analog current inputs
Yes, ±30 V DC, minimum
Analog RTD Inputs
Number
4
Input range
Pt 100, Pt 500, Pt 1000, Ni 100, Ni 1000, Ni 1000 L&S,
0 Ω to 3200 Ω, 0 Ω to 9500 Ω
Sensor supply current
231 mA, typical
Analog Outputs
Number
2
Voltage output range
0 V to 10 V; ±10 V; 0 V to 5 V; ±5 V
Current output range
0 mA to 20 mA; ±20 mA; 4 mA to 20 mA
Measured value resolution
16 bits (15 bits + sign bit)
Measured value representation
In the following formats:
IB IL
RT
S7-compatible
Standardized representation
(15 bits with sign bit)
(15 bits with sign bit)
(15 bits with sign bit)
(15 bits with sign bit)
For measured value representation, please refer to the notes on page 24 and onwards.
Conversion time of the D/A converters
70 µs, typical
Resolution of the D/A converters
16 bits
Process data update time
See "Channel Conversion Times and Process Data Update Time" on page 39
Output load
Voltage output
RLmin = 2 kΩ
Current output
RLB = 0 Ω to 500 Ω
Transient protection
Yes, internally via arresters
Signal connection method
2-wire termination; shielded, twisted pair cable
Short-circuit protection
Voltage output
Current output
Yes, permanent electronic short-circuit protection
Yes, permanent electronic short-circuit protection
Enabling function
Yes, internal electronic
Optical indicators
5% output LED, channel-specific
7280_en_02
PHOENIX CONTACT
8
ILB IB AI4 AO2
Permissible Cable Lengths
Permissible cable lengths
250 m
Reference conditions
The specifications refer to nominal operation observing the installation
instructions.
The specifications refer to the following reference cable type:
Shielded power station cable: LiYCY; 2 x 2 x 0.5 mm2; VDE0812
The ambient conditions and the local conditions in the system can result in special requirements for the installation of cables. These must
be observed accordingly.
For the integration of shielded I/O cables in an equipotential bonding concept for the automation system, the following applies in principle:
Shielded analog I/O cables may only be connected directly to functional earth ground potential at a single point.
This results in the prevention of voltage equalization currents via the analog cable. Additional information is available on request.
Other:
In order to observe the tolerance of RTD inputs, make allowance for the effects of the connecting cable and connection method (2, 3, and
4-wire technology).
Limit Values for Temperature Measurement
Sensor Type
Nominal Range
Lower Limit
Upper Limit
Pt DIN
-200°C
+850°C
Ni DIN
-60°C
+180°C
Ni 1000 L&S
-50°C
+160°C
In the event of underrange or overrange of the nominal range, the "Underrange" or "Overrange" error message is generated.
Tolerances at TA = 25°C
AI Measuring Range
Absolute (Typical)
Absolute (Maximum)
Relative (Typical)
Relative (Maximum)
0 V to 5 V, ±5 V
±5.0 mV
±20 mV
0.10%
±0.40%
0 V to 10 V, ±10 V
±6.0 mV
±25 mV
0.06%
±0.25%
0 mA to 20 mA, ±20 mA,
4 mA to 20 mA
±12 µA
±50 µA
0.06%
±0.25%
Pt 100 (-200°C ... +850°C)
±0.3 K
±1.6 K
0.03%
±0.19%
Pt 500 (-200°C ... +850°C)
±0.2 K
±1.4 K
0.02%
±0.17%
Pt 1000 (-200°C ... +850°C)
±0.2 K
±1.3 K
0.02%
±0.15%
Ni 100 (-60°C ... +180°C)
±0.2 K
±0.9 K
0.11%
±0.50%
Ni 1000 (-60°C ... +180°C)
±0.1 K
±0.5 K
0.08%
±0.28%
Ni 1000 L&S (-50°C ... +160°C)
±0.1 K
±0.3 K
±0.02%
±1.6%
0 Ω to 3200 Ω
±0.4 Ω
±2.75 Ω
0.01%
±0.18%
0 Ω to 9500 Ω
±2.0 Ω
±12.0 Ω
0.02%
±0.13%
AO Output Range
Absolute (Typical)
Absolute (Maximum)
Relative (Typical)
Relative (Maximum)
0 V to 5 V, ±5 V
±10 mV
±30 mV
0.20%
±0.60%
0 V to 10 V, ±10 V
±10 mV
±30 mV
0.10%
±0.30%
0 mA to 20 mA, ±20 mA,
4 mA to 20 mA
±20 µA
±60 µA
0.10%
±0.30%
The data contains the offset error, gain error, and linearity error. All percentage tolerance values refer to the relevant measuring range final
value. Unless otherwise stated, nominal operation (nominal voltage US = UL = 24 V, preferred mounting position, default format "IB IL", default
filter setting (4.5 ms), identical measuring range setting for channels, etc.) is used as the basis. For RTD inputs, the tolerances are specified
in 4-wire connection method, the installation instructions should be implemented accordingly. Please also observe the values for temperature
drift and the tolerances influenced by electromagnetic interference. The maximum tolerance values represent the worst-case measurement
inaccuracy. They contain the theoretical maximum possible tolerances in the measuring ranges. Moreover, the theoretical maximum possible
tolerances of the calibration and test equipment have been taken into consideration.
7280_en_02
PHOENIX CONTACT
9
ILB IB AI4 AO2
Tolerance and Temperature Response at TA = -25°C to +60°C
AI Measuring Range
Drift (Typical)
Drift (Maximum)
0 V to 5 V, ±5 V
±15 ppm/K
±35 ppm/K
0 V to 10 V, ±10 V
±15 ppm/K
±35 ppm/K
0 mA to 20 mA, ±20 mA, 4 mA to 20 mA
±20 ppm/K
±50 ppm/K
Pt 100 (-200°C ... +850°C)
±40 ppm/K
±100 ppm/K
Pt 500 (-200°C ... +850°C)
±35 ppm/K
±90 ppm/K
Pt 1000 (-200°C ... +850°C)
±30 ppm/K
±80 ppm/K
Ni 100 (-60°C ... +180°C)
±60 ppm/K
±110 ppm/K
Ni 1000 L&S (-50°C ... +180°C)
±20 ppm/K
±50 ppm/K
Ni 1000 (-60°C ... +180°C)
±20 ppm/K
±50 ppm/K
0 Ω to 3200 Ω
±20 ppm/K
±60 ppm/K
0 Ω to 9500 Ω
±25 ppm/K
±50 ppm/K
AO Output Range
Drift (Typical)
Drift (Maximum)
0 V to 5 V, ±5 V, 0 V to 10 V, ±10 V
±55 ppm/K
±95 ppm/K
0 mA to 20 mA, ±20 mA, 4 mA to 20 mA
±50 ppm/K
±90 ppm/K
The values refer to the relevant measuring range final value.
The values refer to nominal operation in the recommended mounting position (horizontal wall mounting).
Formula for Calculating the Tolerance Influenced by Temperature
Typical temperature drift
Drifttyp = Δϑ x TCtyp * MFV
Where:
Maximum temperature drift
Drifttyp
Typical temperature drift
Δϑ
Temperature difference between the ambient temperature of
the module TA and +25°C
TCtyp
Typical temperature coefficient in ppm/K
MFV
Measuring range final value (e.g., +850°C for Pt 100)
Driftmax = Δϑ x TCmax * MFV
Where:
Example
Driftmax
Maximum temperature drift
Δϑ
Temperature difference between the ambient temperature of
the module TA and +25°C
TCmax
Maximum temperature coefficient in ppm/K
MFV
Measuring range final value (e.g., +850°C for Pt 100)
Sensor = Pt 100; ambient temperature TA = +40°C
Δϑ = +15 K
TCtyp = ±40 ppm/K (typical); TCmax = ±100 ppm/K
Measuring range final value Pt 100 MFV = +850°C
Drifttyp = Δϑ x TCtyp x MFV = 15 K x ±40 ppm/K x 850°C = ±0.51°C
Driftmax = Δϑ x TCmax x MFV = 15 K x ±100 ppm/K x 850°C = ±1.28°C
The maximum drift is a worst-case value (theoretical assumption).
7280_en_02
PHOENIX CONTACT
10
ILB IB AI4 AO2
Tolerances Influenced by Electromagnetic Interference
Current
Analog Input
Voltage
RTD
Analog Output
Current
Voltage
Electromagnetic fields
EN 61000-4-3
IEC 61000-4-3
< ±1.5%
< 0.2 %
< ±2.0%
< ±0.5%
< ±0.5%
Fast transients (burst)
EN 61000-4-4/
IEC 61000-4-4
< ±1.5%
< 0.2 %
< ±2.0%
< ±0.5%
< ±0.5%
Conducted interference
EN 61000-4-6
IEC 61000-4-6
< ±1.5%
< 0.2 %
< ±2.0%
< ±0.5%
< ±0.5%
Under the influence of high-frequency electromagnetic interference phenomena caused by radio transmission systems in close proximity,
additional tolerances can occur. The values specified refer to nominal operation in the event of direct interference to components without
additional shielding such as a steel cabinet, etc.
This information is valid for device firmware ID HW/FW 04/100 or later.
The tolerances specified above can be reduced through additional shielding for the I/O module (e.g., use of a shielded control box/control
cabinet, etc.). Please refer to the recommended measures in the Inline system manual for your bus system.
Signal Rise Times: Voltage Output 0 V to 10 V (Typical Values)
10% to 90%
0% to > 99%
Ohmic load RL = 2 k Ω
160 µs
240 µs
Ohmic/capacitive load RL = 2k Ω/CL = 10 nF
160 µs
240 µs
Ohmic/capacitive load RL = 2k Ω/CL = 220 nF
170 µs
240 µs
Ohmic/inductive load RL = 2k Ω/LL = 3.3 mH
170 µs
240 µs
Signal Rise Times: Current Output 0 mA to 20 mA (Typical Values)
10% to 90%
0% to > 99%
Ohmic load RL = 500 Ω
450 µs
730 µs
Ohmic/capacitive load RL = 500 Ω/CL = 10 nF
460 µs
750 µs
Ohmic/capacitive load RL = 500 Ω/CL = 220 nF
770 µs
1.3 ms
Ohmic/inductive load RL = 500 Ω/LL = 3.3 mH
610 µs
1.1 ms
Ohmic/capacitive load RL = 50 Ω/CL = 100 nF
11 ms
20.7 ms
Signal Rise Times: Current Output 4 mA to 20 mA (Typical Values)
10% to 90%
0% to > 99%
Ohmic load RL = 500 Ω
400 µs
810 µs
Ohmic/capacitive load RL = 500 Ω/CL = 10 nF
470 µs
840 µs
Ohmic/capacitive load RL = 500 Ω/CL = 220 nF
800 µs
1.4 ms
Ohmic/inductive load RL = 500 Ω/LL = 3.3 mH
590 µs
990 µs
Approvals
For the latest approvals, please visit www.download.phoenixcontact.com.
7280_en_02
PHOENIX CONTACT
11
ILB IB AI4 AO2
4
Internal Circuit Diagram
µC
REF
Supervisor
AI/RTD1...4
U/I
U/I
4x
OPC/SRE
Supervisor
U
3.3 V
15 V
5V
5V
24 V
24 V
24 V
5V
I
24 V
US
ELF
24 V
UL
GNDUS
GNDUL
Shield
IN
INTERBUS
OUT
AGND
FE
PWR
AI
RTD
AO1/2
7280A020
Figure 2
Internal wiring of the terminal points
Key:
U/I
R E F
µ C
Universal output driver with integrated output
shutdown
Reference voltage
Microprocessor
Amplifier
OPC / SRE
Protocol chip with register expansion
Constant current source
Optocoupler
Power supply unit with electrical isolation
S u p e r v is o r
Hardware monitoring
E L F
Electronic fuse
Digital/analog converter
7280_en_02
PHOENIX CONTACT
12
ILB IB AI4 AO2
5
Electrical Isolation
Incoming
remote bus
(5 V DC)
Communications power
(primary)
24 V DC
UL
Electrical isolation
between area
A and B
A
Logic area and outgoing
remote bus
(3.6 V DC/5 V DC)
Microprocessor,
protocol chip
UL (24 V DC)
B
Analog inputs
Analog I/O
(5 V DC/±15 V DC)
Analog outputs
Supply of
initiator supply
UIS1
UIS2
UIS3
UIS4
Initiator supply UIS
Analog inputs
(24 V DC)
US (24 V DC)
24 V DC
US
7280A004
FE potential
Figure 3
6
Electrical isolation of the individual function areas
Local Diagnostic and Status Indicators
Designation
Color
Meaning
UL
Green
Communications power
RC
Green
Remote bus cable check
BA
Green
Bus active
RD
Yellow
Outgoing remote bus disabled
TR
Green
PCP communication active
US
Green
SF
Red
Group error
E1 to E4
Red
Channel-specific error
indication (sensor supply short
circuit or open circuit)
Yellow
Analog output value is ≥ 5% of
the positive measuring range
final value
BUS
E1
UL
BA
RC
RD
US
BUS1
BUS2
PWR
TR
E2
E3
E4
1
SF
2
AI1
RTD1
AI2
RTD2
AI3
RTD3
AI4
RTD4
AO1/2
PWR
Sensor supply
AI
AO
7280B002
Figure 4
7280_en_02
1, 2
Diagnostic and status indicators
PHOENIX CONTACT
13
ILB IB AI4 AO2
6
7
8
9
AO1/2
5
RTD4
RTD3
4
AI4
AI3
3
RTD2
2
AI2
1
RTD1
Connection of INTERBUS, Supply, Analog Sensors, and Actuators
AI1
7
10
11
12
GND
US US UIS UIS I1+ - 24VGND I2+ - 24VGND I3+ - 24VGND I4+ UL UL U1+U1- I11
1.1
2
1
1
2.1
1.2
2
2
1.3
3
1.4
4
BUS
- U2+ U2- I2-
7280_en_02
U3+ U3- I3-
-
U4+ U4- I4-
-
I1 I2
GNDGND I1+ I1- U1- U1+ I2+ I2- U2- U2+ I3+ I3- U3- U3+ I4+ I4- U4- U4+ AGND
UL US
1
2
1.1
1
1
2.1
2.2
1.2
2
2
2.2
3
2.3
1.3
3
3
2.3
4
2.4
1.4
4
4
2.4
FE
1
IN OUT
INTERBUS
2
1.1
1
1
2.1
1.2
2
2
2.2
1.3
3
3
2.3
1.4
4
4
2.4
PWR
Figure 5
-
U1 U2
AI, RTD, AO
7280B003
Terminal point assignment of the connectors
PHOENIX CONTACT
14
ILB IB AI4 AO2
7.1
Terminal Point Assignment of the INTERBUS Connectors
Terminal Point Assignment
Remark/Wire Color in the INTERBUS Standard Cable
Connector 1 (BUS 1) Incoming Remote Bus
Receive
1.1
DO1
2.1
DO1
Receive
Transmit
1.2
DI1
2.2
DI1
Transmit
1.3
F-GND
Reference potential
2.3
1.4, 2.4
Shield
Shield potential is connected with a capacitor to functional earth
ground (FE) of the potential jumper.
Connector 2 (BUS 2) Outgoing Remote Bus
Transmit
1.1
DO2
2.1
DO2
Transmit
Receive
1.2
DI2
2.2
DI2
Receive
1.3
R-GND
Reference potential
2.3
1.4, 2.4
Shield
Shield potential is connected directly to functional earth ground (FE)
of the potential jumper.
7.2
Green
Yellow
Pink
Gray
Brown
Not used
Green
Yellow
Pink
Gray
Brown
Not used
Terminal Point Assignment of the Power Connector
Terminal Point Assignment
Connector 3 (PWR)
1.1, 2.1
24 V supply US
1.2, 2.2
24 V communications power UL
1.3,
GND UL
2.3
GND US
1.2, 2.4
FE
7.3
Terminal Point Assignment of the Connectors for the Analog Inputs
(AI; connectors 4, 6, 8, and 10 in Figure 5 on page 14)
Terminal Point
Connector 4 Connector 6
(AI1)
(AI2)
1.1
1.1
2.1
2.1
1.2
1.2
2.2
2.2
1.3
1.3
2.3
2.3
1.4, 2.4
1.4, 2.4
7280_en_02
Connector 8
(AI3)
1.1
2.1
1.2
2.2
1.3
2.3
1.4, 2.4
Connector 10
(AI4)
1.1
2.1
1.2
2.2
1.3
2.3
1.4, 2.4
Signal
Assignment
UISx (24 V)
GNDiSx
Ux+
UxIx+
IxShield
Initiator supply for channel x
Ground of UiSx
Positive voltage input for channel x
Negative voltage input for channel x
Positive current input for channel x
Negative current input for channel x
Shield connection
x = 1 to 4
PHOENIX CONTACT
15
ILB IB AI4 AO2
7.4
Terminal Point Assignment of the Connectors for the Analog RTD Inputs
(RTD; connectors 5, 7, 9, and 11 in Figure 5 on page 14)
Terminal Point
Signal
Connector 5 Connector 7 Connector 9 Connector 11
(RTD1)
(RTD2)
(RTD3)
(RTD4)
1.1
1.1
1.1
1.1
Ix+
2.1
1.2
2.1
1.2
2.1
1.2
2.1
1.2
–
Ix-
2.2
1.3
2.3
1.4, 2.4
2.2
1.3
2.3
1.4, 2.4
2.2
1.3
2.3
1.4, 2.4
2.2
1.3
2.3
1.4, 2.4
–
UxUx+
Shield
7.5
Assignment
Positive constant current supply for RTD sensor
channel x
Reserved
Negative constant current supply for RTD
sensor channel x
Reserved
Negative voltage input for RTD sensor channel x
Positive voltage input for RTD sensor channel x
Shield connection
x = 1 to 4
Terminal Point Assignment of the Connectors for the Analog Outputs
(AO, connector 12 in Figure 5 on page 14)
Terminal
Signal
Point
Connector 12
(AO)
1.1
U1/I1
2.1
U2/I2
1.2
U1/I1
2.2
U2/I2
1.3
2.3
1.4, 2.4
AGND
AGND
Shield
Assignment
Voltage or current output
channel 1
Voltage or current output
channel 2
Voltage or current output
channel 1
Voltage or current output
channel 2
Analog ground channel 1
Analog ground channel 2
Shield connection
The relevant unused terminal point for voltage
or current output of a channel can be used for
test purposes.
7280_en_02
PHOENIX CONTACT
16
ILB IB AI4 AO2
8
Connection Notes
Always connect the analog sensors using shielded, twisted pair cables.
Connect the shielding to the module using the shield connection clamp. The clamp connects the shield to FE
on the module side. Avoid connection to FE from both sides.
The module is supplied with a shield connector and a standard connector for each input channel. The shield
connection can be used for the standard signal (current/voltage) as well as for the RTD signal.
The module has an FE spring (metal clip) on the bottom of the electronics base. This spring establishes an
electrical connection to the
DIN rail. Use grounding terminals to connect the DIN rail to protective earth ground. The module is grounded
when it is snapped onto the DIN rail.
To ensure reliable functional earth grounding of the module even when the DIN rail is dirty or the metal
clip is damaged, always ground the module via the FE terminal point (see Figure 6).
Connection Examples
IN
OUT
+
Figure 6
-
AI RTD AI RTD AI RTD AI RTD AO
4 5 6 7 8 9 10 11 12
U
UL
- U-
+
INTERBUS
3
S
-
OUT2
2
+
1
+
9
7280B005
General connection example
Ideal current source
Application: Passive 2-wire transmitter
The numbers above the module illustration
indicate the connector slots.
OUT2
Variable resistor
7280_en_02
General actuator
PHOENIX CONTACT
17
ILB IB AI4 AO2
+
Connection Examples for Analog Inputs
-
+
9.1
-
Ideal current source
Ideal voltage source
AI
AI
2
1
24VGND
1
1
U+ U2
-
3
4
4
+
3
1
1
U+ U2
2
I+ I-
IS
2
24VGND
+
1
2
US
I+ I3
3
4
4
7280A009
7280A006
Figure 7
Voltage measurement
-
Figure 10
Differential mode voltage measurement,
e.g., for shunt, jumpering, and battery
charging applications
AI
1
2
AI
24VGND
1
1
1
2
U+ U2
I+ I3
-
24VGND
1
1
U+ U-
3
2
4
+
4
7280A007
Figure 8
2
I+ I3
3
4
4
Current measurement
GND
- 24 V
+
2
7280A010
Figure 11
Active transmitter (4 mA to 20 mA)
AI
1
2
24VGND
1
1
U+ U2
I+ I3
3
4
4
+
2
7280A008
Figure 9
7280_en_02
Passive transmitter (4 mA to 20 mA)
PHOENIX CONTACT
18
ILB IB AI4 AO2
9.2
Connection Examples for RTD Inputs
9.3
Connection Examples for Analog Outputs
RTD
1
AO
2
1
I+ RES
1
1
I-
I+
RL
1
I-
RES
2
2
U1 U2
2
I1
RL
U- U+
1
I1 I2
2
2
I2
OUT1
OUT2
3
3
3
3
4
4
4
4
7280B011
Figure 12
RTD 2-wire connection
with connector compensation
7280A014
Figure 15
Please refer to the connection notes for the
RTD 2-wire connection in "RTD 2-Wire
Connection With Connector Compensation" on
page 41.
Analog current output
AO
1
2
U1
1
1
I1
RTD
1
U1
2
2
3
3
4
4
OUT1
2
OUT2
U2
I+ RES
1
1
RL
I+
I-
I- RES
2
2
7280A015
RL
U- U+
3
3
4
4
U- (I = 0 µA)
RL
Figure 16
Analog voltage output
7280A012
Figure 13
RTD 3-wire connection
RTD
1
I+ RES
1
2
U+ (I = 0 µA)
2
RL
I+
1
I- RES
RL
2
RL
U- U+
3
3
4
4
RL
I-
U- (I = 0 µA)
7280A013
Figure 14
7280_en_02
RTD 4-wire connection
PHOENIX CONTACT
19
ILB IB AI4 AO2
10
Programming Data
ID code
F3hex (243dec)
Length code
05hex
Process data channel
80 bits
Input address area
5 words
Output address area
5 words
Parameter channel (PCP)
1 word
Register length (bus)
6 words
11
Process Data
The device has 5 process data words and 1 PCP word.
OUT
OUT1
Control word
OUT2
Channel 1
OUT3
Channel 2
OUT4
Channel 3
OUT5
Channel 4
IN
IN1
Status word
IN2
Channel 1
IN3
Channel 2
IN4
Channel 3
IN5
Channel 4
Figure 17
7280_en_02
7280A026
Order of the process data words
PHOENIX CONTACT
20
ILB IB AI4 AO2
11.1
Assignment of the Process Data to the Terminal Points for the "Read and Write Analog Values"
Command
Assignment of the Terminal Points for Connector 12 to the Process Data Output Words
(Word.bit) view
Word
Bit
(Byte.bit) view
Word 2:
Channel AO1
Word 3:
Channel AO2
Word x
15 14 13 12 11 10 9
8
7
6
5
Byte 0
Byte
6
5
4
3
4
3
2
1
0
Byte 1
Bit
7
2
1
0
Signal
Terminal point 1.1: Voltage output
Terminal point 1.2: Current output
Signal reference
Terminal point 1.3: Analog ground
Shielding (FE)
Terminal point 1.4, 2.4
Signal
Terminal point 1.1: Voltage output
Terminal point 1.2: Current output
Signal reference
Terminal point 1.3: Analog ground
Shielding (FE)
Terminal point 1.4, 2.4
7
6
5
4
3
2
1
0
6
5
4
3
2
1
0
2
1
0
Assignment of the Terminal Points to the Process Data Input Words
(Word.bit) view
Bit
(Byte.bit) view
Bit
7280_en_02
15 14 13 12 11 10 9
8
7
Byte 0
Byte
AI
Signal
Word 2:
Channel 1 (connector 4) Signal reference
Word 3:
Channel 2 (connector 6)
Shielding (FE)
Word 4:
Channel 3 (connector 8)
Word 5:
Channel 4 (connector 10)
RTD
Word 2:
Channel 1 (connector 5)
Word 3:
Channel 2 (connector 7)
Word 4:
Channel 3 (connector 9)
Word 5:
Channel 4 (connector 11)
Word x
Word
7
6
5
4
3
Byte 1
2
1
0
7
6
5
4
3
Terminal point 1.2: Positive voltage input
Terminal point 1.3: Positive current input
Terminal point 2.2: Negative voltage input
Terminal point 2.3: Negative current input
Terminal point 1.4, 2.4
Signal
Terminal point 2.3: Voltage input for RTD sensor
Signal reference
Terminal point 1.3 (negative voltage input for RTD sensor)
Constant current
supply
Terminal point 1.1 (positive constant current supply)
Terminal point 1.2 (negative constant current supply)
Shielding (FE)
Terminal point 1.4, 2.4
PHOENIX CONTACT
21
ILB IB AI4 AO2
12
OUT Process Data Words
Five OUT process data words are available.
The first output word (OUT1) represents the control word, the following words (OUT2 to OUT5) each refer to an analog
channel. They are used for channel-specific configuration and to output analog values. As confirmation for a control word
action, the first input word contains a partial copy of the control word.
OUT1
Bit
Assignment
15
14
Byte 0
13
12
11
10
Command code
9
8
7
0
6
0
5
0
Byte 1
4
3
0
0
2
0
1
0
0
0
Bit 15 to bit 8 (command code)
0
1
Bit 15 to Bit 8
0 0 0 0
0
0
OUT1
40xxhex
Command Function
Configure device.
The channel parameters of the four channels are configured in OUT2 to
OUT5.
Read configuration.
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
0
0
1
0
0
0
0
0
0
1
0
0
0
0
0
0
1
0
0
1
1
0
0
0
The configuration of each channel is displayed channel-by-channel in
IN2.
Configuration channel 1
Configuration channel 2
Configuration channel 3
Configuration channel 4
Read and write analog values.
0
1
0
1
1000hex
1100hex
1200hex
1300hex
0
1
0
The analog values for the input channels are displayed in IN2 to IN5.
The analog values for the output channels are displayed in OUT2 and
OUT3.
0000hex OUT process data not transmitted, the analog outputs are not modified.
0100hex The analog outputs accept the value specified via OUT2 and OUT3.
3C00hex Read device data.
The firmware version and the device ID are displayed in IN2, see "Input
Words IN2 to IN5" on page 23.
7280_en_02
PHOENIX CONTACT
22
ILB IB AI4 AO2
13
IN Process Data Words
13.1
Input Word IN1 (Status Word)
OUT1
Bit
Assignment
15
EB
Byte 0
13
12
11
10
9
Mirrored command code*
14
8
7
0
6
0
5
0
Byte 1
4
3
0
0
2
0
1
0
0
0
Error bit:
EB = 0
EB = 1
No error has occurred.
An error has occurred.
The error bit is available as a group error message. Possible errors and their effects are listed in "Diagnostics" on page 38.
* Mirrored command code:
A command code mirrored from the control word. Here, the MSB is suppressed.
13.2
Input Words IN2 to IN5
The measured values, firmware version or configuration are transmitted to the controller board or the computer via
IN process data words IN2 to IN5 according to the configuration.
IN1*
IN2
IN3
IN4
Configure device.
IN5
Configuration data following transmission to the channels
Configuration data
Configuration data
Configuration data
channel 2
channel 3
channel 4
Read configuration.
40xxhex
Configuration data
channel 1
1000hex
1100hex
1200hex
1300hex
Configuration channel 1
Configuration channel 2
Configuration channel 3
Configuration channel 4
00xxhex
01xxhex
Measured value of the
analog input channel 1
3C00hex Firmware version and
device ID, see below
Not relevant
Not relevant
Not relevant
Read and write analog values.
Measured value of the
Measured value of the
analog input channel 2
analog input channel 3
Measured value of the
analog input channel 4
Read device data.
Not relevant
Not relevant
Not relevant
* Input data IN1 contains the error bit and the mirrored command code.
Example for "Read device data":
IN2
Bit
Assignment (hex)
Meaning
7280_en_02
15
14
13
1
12
11
10
9
8
2
Firmware Version 1.23
7
6
5
3
4
3
2
1
0
4
Device ID 4hex
PHOENIX CONTACT
23
ILB IB AI4 AO2
14
Formats for the Representation of Measured Values (IN2 to IN5)
14.1
Format: "IB IL" (Default Setting)
The measured value is represented in bits 14 to 0. An additional bit (bit 15) is available as a sign bit.
Measured value representation in "IB IL" format (15 bits)
MSB
15
14
SB
SB
13
12
11
10
9
8
7
6
Analog value
5
4
3
2
1
LSB
0
Sign bit
This format supports extended diagnostics. Values > 8000hex and < 8100hex indicate an error. Following an error message
in the status word (error bit), the following errors/messages are displayed in words IN2 to IN5:
Input Data Word (hex)
8001
8002
8004
8020
8040
8080
Errors
Overrange
Open circuit
Measured value invalid
Sensor and/or analog supply not present
Module faulty
Underrange
Significant Measured Values
Input Data Word
(Two's Complement)
hex
8001
7F00
7530
0001
0000
FFFF
8AD0
8100
8080
8002
7280_en_02
dec
Overrange
32512
30000
1
0
-1
-30000
-32512
Underrange
Open circuit
0 V to 10 V
UInput
±10 V
UInput
0 V to 5 V
UInput
±5 V
UInput
0 mA to
20 mA
IInput
V
V
V
V
mA
> +10.837
> +10.837
> +5.419
> +5.419 > +21.6747
+10.837
+10.837
+5.419
+5.419
+21.6747
+10.0
+10.0
+5.0
+5.0
+20.0
+333.33 μV +333.33 μV +166.67 μV +166.67 μV +0.6667 μA
≤0
0
≤0
0
≤0
–
-333.33 μV
–
-166.67 μV
–
–
-10.0
–
-5.0
–
–
-10.837
–
-5.419
–
–
< -10.837
–
< -5.419
–
–
–
–
–
–
±20 mA
IInput
mA
> +21.6747
+21.6747
+20.0
+0.6667 μA
0
-0.6667 μA
-20.0
-21.6747
< -21.6747
–
4 mA to
20 mA
IInput
mA
> +21.339733
+21.339733
+20.0
+4.0005333
+4.0 ... +3.2
–
–
–
–
< +3.2
PHOENIX CONTACT
24
ILB IB AI4 AO2
Input Data Word
(Two's Complement)
hex
dec
8001
Overrange
251C
9500
03E8
1000
0001
1
0000
0
FFFF
-1
FC18
-1000
8080
Underrange
R: 0 ... 3.2 kΩ
RInput
Ω
> 3200
–
100.0
+0.1
≤0
–
–
–
R: 0 ... 9.5 kΩ
RInput
Ω
> 10000
9500
1000
+1.0
≤0
–
–
–
Pt and Ni
°C
> Limit value
–
+100.0
+0.1
0
-0.1
-100.0
< Limit value
For the limit values, please refer to "Limit Values for Temperature Measurement" on page 9.
Output Data Word
hex
dec
8001
Overrange
7FFF to 7F01
–
7F00
+32512
7530
+30000
3A98
+15000
0001
+1
0000
0
FFFF
-1
C568
-15000
8AD0
-30000
8100
-32512
80FF to 8000
–
without 8001,
8080, 8002
8080
Underrange
8002
Line break
7280_en_02
0 V to 10 V
UOutput
±10 V
UOutput
0 V to 5 V
UOutput
±5 V
UOutput
0 mA to
±20 mA
4 mA to
20 mA
IOutput
20 mA
IOutput
IOutput
V
V
V
V
mA
V
mA
+10.837
+10.837
+5.419
+5.419
+21.6764
+10.837
+21.3397
+10.837
+10.837
+5.419
+5.419
+21.6764 +21.6764 +21.3397
+10.837
+10.837
+5.419
+5.419
+21.6764 +21.6764 +21.3397
+10.0
+10.0
+5.0
+5.0
+20.0
+20.0
+20.0
+5.0
+5.0
+2.5
+2.5
+10.0
+10.0
+12.0
+333.33 μV +333.33 μV +166.67 μV +166.67 μV +0.6667μA +0.6667μA +4.000533
0
0
0
0
0
0
+4.0
0
-333.33 μV
0
-166.67 μV
0
-0.6667μA
+4.0
0
-5.0
0
-2.5
0
-10.0
+4.0
0
-10.0
0
-5.0
0
-20.0
+4.0
0
-10.837
0
-5.419
0
-21.6764
+4.0
HOLD
HOLD
HOLD
HOLD
HOLD
HOLD
HOLD
0
HOLD
-10.837
HOLD
0
HOLD
-5.419
HOLD
0
HOLD
-10.837
HOLD
HOLD
0
PHOENIX CONTACT
25
ILB IB AI4 AO2
14.2
Format: "RT"
The measured value is represented in bits 14 to 0. An additional bit (bit 15) is available as a sign bit.
Measured value representation in "RT" format (15 bits)
MSB
15
14
SB
SB
13
12
11
10
9
8
7
6
Analog value
5
4
3
2
1
LSB
0
Sign bit
Significant Measured Values
Input Data Word
hex
7FFF
0001
0000
FFFF
8001
dec
32767
+1
0
-1
-32767
Output Data Word
hex
7FFF
0001
0000
FFFF
8001
7280_en_02
dec
+32767
+1
0
-1
-32767
0 V to 10 V
UInput
±10 V
UInput
V
≥ +10.0
+305.18 μV
≤0
–
–
V
≥ +10.0
+305.18 μV
0
-305.18 μV
≤ -10.0
0 V to 10 V
UOutput
±10 V
UOutput
V
+10.0
+305.18 μV
≤0
0
0
V
+10.0
+305.18 μV
0
-305.18 μV
-10.0
0 V to 5 V
UInput
V
≥ +5.0
+152.6 μV
≤0
–
–
0 V to 5 V
UOutput
V
+5.0
+152.6 μV
≤0
0
0
±5 V
UInput
V
≥ +5.0
+152.6 μV
0
-152.6 μV
≤ -5.0
±5 V
UOutput
V
+5.0
+152.6 μV
0
-152.6 μV
-5.0
0 mA to
20 mA
IInput
mA
≥ +20.0
+0.610 μA
≤0
–
–
0 mA to
20 mA
IOutput
mA
+20.0
+0.610 μA
≤0
0
0
±20 mA
IInput
mA
≥ +20.0
+0.610 μA
0
-0.610 μA
≤ -20.0
±20 mA
IOutput
V
+20.0
+0.610 μA
≤0
-0.610 μA
-20.0
4 mA to
20 mA
IInput
mA
≥ +20.0
+4.000488 µA
4.0
–
< 3.7
4 mA to
20 mA
IOutput
mA
+20.0
+4.000488
+4.0
+4.0
+4.0
PHOENIX CONTACT
26
ILB IB AI4 AO2
14.3
Format: "S7-Compatible"
The measured value is represented in bits 14 to 0. An additional bit (bit 15) is available as a sign bit.
Measured value representation in "S7-compatible" format
MSB
15
14
SB
SB
13
12
11
10
9
8
7
6
Analog value
5
4
3
2
1
LSB
0
Sign bit
Significant Measured Values
Input Data Word
hex
7FFF
7EFF
6C00
0001
0000
FFFF
F940
8000
9400
8100
8000
dec
Overrange
+32511
+27648
+1
0
-1
-1728
Line break
-27648
-32519
Underrange
0 V to 10 V
UInput
±10 V
UInput
0 V to 5 V
UInput
±5 V
UInput
0 mA to
±20 mA
4 mA to
20 mA
IInput
20 mA
IInput
IInput
V
V
V
V
mA
mA
mA
> +11.759
> +11.759
> +5.879
> +5.879
> +23.5157 > +23.5157 > +22.8142
+11.759
+11.759
+5.879
+5.879
+23.5157
+23.5157
+22.8142
+10.0
+10.0
+5.0
+5.0
+20.0
+20.0
+20.0
+361.69 μV +361.69 μV +180.85 μV +180.85 μV +0.7234 μA +0.7234 μA +4.000578
≤0
0
≤0
0
≤0
0
+4.0
–
-361.69 μV
–
-180.85 μV
–
-0.7234 μA +3.999422
–
-0.625
–
-0.3125
–
-1.25
+3.0
–
–
–
–
–
–
< +1.1852
–
-10
–
-5.0
–
-20.0
–
–
-11.759
–
-5.879
–
-23.516
–
–
< -11.759
–
< -5.879
–
< -23.516
–
Formula for Calculating the Measured Value from the Process Data Input Value for the 4 mA to 20 mA Measuring
Range
Measured value = PD IW x 0.0005787 mA + 4 mA
PD IW = Process data
Example 1
PD IW
Value x resolution
+ 4 mA
Measured value
6C00hex = 27648dec
27648 x 0.0005787 mA = 16 mA
16 mA + 4 mA = 20 mA
20 mA
Example 2
PD IW
Value x resolution
+ 4 mA
Measured value
F940hex -> FFFFhex - F940hex + 1 = -1728dec
-1728 x 0.0005787 mA = -1 mA
-1 mA + 4 mA = 3 mA
3 mA
7280_en_02
PHOENIX CONTACT
27
ILB IB AI4 AO2
Input Data Word
(Two's Complement)
hex
dec
7FFF
Overrange
251C
9500
03E8
1000
0001
1
0000
0
FFFF
-1
FC18
-1000
8000
Underrange
Output Data Word
hex
7FFF
to 7F00
7EFF
6C00
5100
1
0
FFFF
E501
E500
AF00
9400
8100
80FF
to 8000
7280_en_02
dec
Overrange
+32511
+27648
+20736
+1
0
-1
-6911
-6912
-20736
-27648
-32511
Underrange
R: 0 ... 3.2 kΩ
RInput
Ω
> 3200
–
100.0
0.1
≤0
–
–
–
R: 0 ... 9.5 kΩ
RInput
Ω
> 10000
9500
1000
1
≤0
–
–
–
0 V to 10 V
UOutput
±10 V
UOutput
0 V to 5 V
UOutput
±5 V
UOutput
V
0
V
0
V
0
V
0
0 mA to
20 mA
IOutput
mA
0
Pt and Ni
°C
> Limit value
–
+100.0
+0.1
0
-0.1
-100.0
< Limit value
±20 mA
IOutput
mA
0
4 mA to
20 mA
IOutput
mA
0
+11.7589
+11.7589
+5.8800
+5.8800
+23.5150
+23.5150
+22.8100
+10.0000
+10.0000
+5.0000
+5.0000
+20.0
+20.0
+20.0
+7.5000
+7.5000
+3.7500
+3.7500
+15.0
+15.0
+16.0
+361.69 μV +361.69 μV +180.845 μV +180.845 μV +0.7234 μA +0.7234 μA +4.000578
0
0
0
0
0
0
+4.0
0
-361.69 μV
0
-180.845 μV
0
-0.7234 μA +3.99942
0
-2.4996
0
-1.2498
0
-4.99942 +0.578 μA
0
-2.5000
0
-1.2500
0
-5.0
0
0
-7.5000
0
-3.7500
0
-15.0
0
0
-10.0000
0
-5.0000
0
-20.0
0
0
-11.7589
0
-5.8800
0
-23.5157
0
0
0
0
0
0
0
0
PHOENIX CONTACT
28
ILB IB AI4 AO2
14.4
Format: "Standardized Representation"
The data is represented in bits 14 to 0. An additional bit (bit 15) is available as a sign bit.
In this format, data is standardized to the measuring range and represented in such a way that it indicates the corresponding
value without conversion. In this format one bit has the value of 1 mV or 1 μA.
Measured value representation in "standardized representation" format
MSB
15
14
SB
SB
13
12
11
10
9
8
7
6
Analog value
5
4
3
2
1
LSB
0
Sign bit
This format supports extended diagnostics. Values > 8000hex and < 8100hex indicate an error. Following an error message
in the status word (error bit), the following errors/messages are displayed in words IN2 to IN5:
Input Data Word (hex)
8001
8002
8004
8020
8040
8080
Errors
Overrange
Open circuit
Measured value invalid
Analog supply not present
Module faulty
Underrange
Significant Measured Values
Input Data Word
hex
8001
4E20
2710
1388
0001
0000
FFFF
EC78
D8F0
B1E0
8080
8002
7280_en_02
dec
Overrange
+20000
+10000
+5000
+1
0
-1
-5000
-10000
-20000
Underrange
Open circuit
0 V to 10 V
UInput
±10 V
UInput
0 V to 5 V
UInput
±5 V
UInput
V
> +10.837
–
+10.0
+5.0
+0.001
≤0
–
–
–
–
–
–
V
> +10.837
–
+10.0
+5.0
+0.001
0
-0.001
-5.0
-10.0
–
< -10.837
–
V
> +5.419
–
–
+5.0
+0.001
≤0
–
–
–
–
–
–
V
> +5.419
–
–
+5.0
+0.001
0
-0.001
-5.0
–
–
< -5.419
–
0 mA to
±20 mA
4 mA to
20 mA
IInput
20 mA
IInput
IInput
mA
mA
mA
> +21.6747 > +21.6747 ≥ +21.339
+20.0
+20.0
–
+10.0
+10.0
+14.0
+5.0
+5.0
+9.0
0.001
0.001
+4.001
≤0
0
+4.0 ... +3.2
–
-0.001
–
–
-5.0
–
–
-10.0
–
–
-20.0
–
–
< -21.6747
–
–
–
< +3.2
PHOENIX CONTACT
29
ILB IB AI4 AO2
Input Data Word
(Two's Complement)
hex
dec
8001
Overrange
251C
9500
03E8
1000
0001
1
0000
0
FFFF
-1
FC18
-1000
8080
Underrange
Output Data Word
hex
8001
7FFF to
54AB
54AA
4E20
2710
1388
0001
0000
FFFF
EC78
D8F0
B1E0
AB56
AB55
to 8100
80FF to
8000 without
8001, 8080,
8002
8080
8002
7280_en_02
R: 0 ... 3.2 kΩ
RInput
Ω
> 3200
–
100.0
+0.1
≤0
–
–
–
R: 0 ... 9.5 kΩ
RInput
Ω
> 10000
9500
1000
+1.0
≤0
–
–
–
0 V to 10 V
UOutput
±10 V
UOutput
0 V to 5 V
UOutput
±5 V
UOutput
dec
Overrange
–
V
+10.837
+10.837
V
+10.837
+10.837
V
+5.419
+5.419
+21674
+20000
+10000
+5000
1
0
-1
-5000
-10000
-20000
-21674
–
+10.837
+10.837
+10.0
+5.0
+1 mV
0
0
0
0
0
0
0
+10.837
+10.837
+10.0
+5.0
+1 mV
0
-1 mV
-5.0
-10.0
-10.837
-10.837
-10.837
–
HOLD
Underrange
Line break
0
HOLD
Pt and Ni
°C
> Limit value
–
+100.0
+0.1
0
-0.1
-100.0
< Limit value
V
+5.419
+5.419
0 mA to
20 mA
IOutput
mA
+21.674
+21.674
±20 mA
IOutput
mA
+21.674
+21.674
4 mA to
20 mA
IOutput
mA
+21.3397
+21.3397
+5.419
+5.419
+5.419
+5.0
+1 mV
0
0
0
0
0
0
0
+5.419
+5.419
+5.419
+5.0
+1 mV
0
-1 mV
-5.0
-5.419
-5.419
-5.419
-5.419
+21.674
+20.0
+15.0
+5.0
+1 μA
0
0
0
0
0
0
0
+20.0
+20.0
+10.0
+5.0
+1 μA
0
-1 μA
-5.0
-10.0
-20.0
-21.674
-21.674
+21.3397
+21.3397
+14.0
+9.0
+4.001
+4.0
+4.0
+4.0
+4.0
+4.0
+4.0
+4.0
HOLD
HOLD
HOLD
HOLD
HOLD
HOLD
-10.837
HOLD
0
HOLD
-5.419
HOLD
0
HOLD
-21.674
HOLD
HOLD
0
PHOENIX CONTACT
30
ILB IB AI4 AO2
15
Configuration
Module configuration is only required if the channels are not to be operated with the default values (see "Parameters for
Configuration" on page 32).
You can either configure the module via process data or via PCP and transmit analog values accordingly.
If the module has been configured via PCP, subsequent configuration via process data is only possible if configuration via
process data is permitted with the "Config Table" PCP object. To do this, in the "AO format, AI format, system bits" element
set "Conf" bit = 1. As long as "Conf" = 0, the error bit is set in the status word when an attempt is made to configure via
process data.
16
Configuration via Process Data
Five OUT process data words are available.
The first output word represents the control word, the following words each refer to an analog channel. As confirmation for
a control word action, the first input word contains a partial copy of the control word.
For the device configuration, channel-specific parameter data is set in the relevant channel output words. Once
configuration has been completed, and depending on the format set, the measured values in the corresponding input words
are either transmitted to the controller board or to the computer.
Bit
16.1
15 to 8
40hex
7
0
6
0
OUT1
5 4
0 PF
3 2
AO
format
1
OUT2
OUT3
OUT4
OUT5
Configuration
AI1/AO1
Configuration
AI2/AO2
Configuration
AI3
Configuration
AI4
0
AI
format
Output Word OUT1 (Control Word) for Command Code 40xxhex (Configure Device)
OUT1
Bit
Assignment
15
14
Byte 0
13
12
11
10
Command code 40hex
9
8
7
0
6
0
5
0
Byte 1
4
3
2
PF AO format
1
0
AI format
Bit 4
Code (bin) PF (Peripheral Fault in the Event of Sensor Error)
0
Not permitted (default)
1
Permitted
Bit 3 and bit 2
Code (bin)
00
01
10
11
AO Format
IB IL (15 bits) (default)
RT
S7-compatible
Standardized representation
Bit 1 and bit 0
Code (bin)
00
01
10
11
7280_en_02
AI Format
IB IL (15 bits) (default)
RT
S7-compatible
Standardized representation
PHOENIX CONTACT
31
ILB IB AI4 AO2
16.2
Output Words OUT2 to OUT5 (Configuration)
Each channel can be configured independently of the other channels. The first channel is configured via the second output
word, the second channel via the third output word, etc.
If the format "IB IL" is set, the error code "measured value invalid" is output during configuration.
If the configuration is invalid, a corresponding error message is output in the status word. The configuration is stored in a
volatile memory.
For command 40xxhex, specify the parameters for the appropriate channels 1 to 4 in OUT2 to OUT5. The parameter words
are only evaluated by this command.
Configuration words for analog inputs and outputs:
OUTx (x = 2 to 5)
Byte
Bit
Assignment
–
–
–
–
–
15
14
Wire
Byte 0
13
12
11
AO reset Res.
behavior
10
9
8
AO output range
"Wire" indicates the number of wires for a resistance
measurement. It is only relevant for the "Linear R ...",
"Pt ...", and "Ni ..." AI measuring range options (codes
7hex to Ehex).
"AO reset behavior" indicates the status of the analog
outputs in the event of an INTERBUS reset and
following power up. The failsafe value must be
specified retentively via the Config Table PCP object.
"AO output range" indicates the range for the analog
outputs.
"AI filter" indicates the time for the digital filter.
"AI measuring range" indicates the range for the
analog inputs.
An error message is generated during configuration due to
the following reasons:
– A reserved value was used.
– Current or voltage is configured for "AI measuring
range" AND 3 or 4-wire is configured for "Wire".
– Configuration has already been carried out via PCP.
7
Res.
6
AI
filter
5
Byte 1
4
3
2
1
AI measuring range
0
Parameters for Configuration
The values displayed in bold are default settings.
Bit 15 and bit 14
Code (bin)
00
01
10
11
Wire
2-wire (default)
3-wire
4-wire,
2-wire with connector compensation
Reserved
Bit 13 and bit 12
Code (bin)
00
01
10
11
AO Reset Behavior
Hold (default)
Reset
Failsafe value
Reserved
Bit 10 to bit 8
Code (bin)
000
001
010
011
100
101
110
111
Code (hex)
0
1
2
3
4
5
6
7
AO Output Range
0 V to 10 V (default)
±10 V
0 V to 5 V
±5 V
0 mA to 20 mA
±20 mA
4 mA to 20 mA
Reserved
Bit 6
Code (bin) AI Filter
0
4.5 ms (default)
1
1.1 ms
7280_en_02
PHOENIX CONTACT
32
ILB IB AI4 AO2
Bit 5 to bit 0
Code
(dec)
0
1
2
3
4
5
6
7
8
16.3
AI Measuring Range
(bin)
00 0000
00 0001
00 0010
00 0011
00 0100
00 0101
00 0110
00 0111
00 1000
(hex)
0
1
2
3
4
5
6
7
8
0 V to 10 V (default)
±10 V
0 V to 5 V
±5 V
0 mA to 20 mA
±20 mA
4 mA to 20 mA
Linear R: 0 Ω to 3200 Ω
Linear R: 0 Ω to 9500 Ω
Code
(dec)
9
10
11
12
13
14
AI Measuring Range
(bin)
00 1001
00 1010
00 1011
00 1100
00 1101
00 1110
(hex)
9
A
B
C
D
E
F - 3F
Pt 100 DIN
Pt 500 DIN
Pt 1000 DIN
Ni 100 DIN
Ni 1000 DIN
Ni 1000 L&S
Reserved
Example for the Module Configuration via Process Data
For easy module configuration a function block can be downloaded at www.phoenixcontact.com.
All input channels are configured differently.
PF
Not
permitted
AO
Format
IB IL
AI
Format
IB IL
OUTx Channel Wire
OUT2
OUT3
OUT4
OUT5
AI1/AO1
AI2/AO2
AI3
AI4
Step
1
Process Data
OUT1 = 0000hex
2
Wait until
IN1 = 0000hex
OUT5 = 800Bhex
OUT4 = 8009hex
OUT3 = 0144hex
OUT2 = 0400hex
OUT1 = 4000hex
Wait until
IN1 = 4000hex
3
4
7280_en_02
2-wire
2-wire
4-wire
2-wire with
connector
compensation
Configuration Value
OUT1 (hex)
xx00
AO Reset AO Output
Behavior Range
Hold
0 mA to 20 mA
Hold
±10 V
–
–
–
–
Filter Time AI Measuring Range Configuration Value
OUTx (hex)
4.5 ms
0 V to 10 V
0400
1.1 ms
0 mA to 20 mA
0144
4.5 ms
Pt 100 DIN
8009
4.5 ms
Pt 1000 DIN
800B
Meaning
Ensures that the
following values for
OUT2 and OUT3 are
not evaluated as an
analog output
Awaiting confirmation
Step Process Data
5
OUT1 = 0000hex
6
7
Specified configuration
8
Awaiting confirmation
9
Wait until
IN1 = 0000hex
OUT3 = analog value AO2
OUT2 = analog value AO1
OUT1 = 0100hex
Wait until
IN1 = 0100hex
Measured value channel 1 = IN2,
...,
Measured value channel 4 = IN5
OUT1 = 0100hex
Meaning
Requesting the
measured
values of
channels 1 to 4
Awaiting
confirmation
Outputting
analog values
Awaiting
confirmation
Reading
measured
values
PHOENIX CONTACT
33
ILB IB AI4 AO2
17
Configuration via PCP
By default upon delivery, the device is configured according to the default settings (see "Parameters for Configuration" on
page 32).
In PCP mode, the device is configured with the "Config Table" object.
Index
0080hex
N:
L:
Data Type
Array of Unsigned 16
N
7
Number of elements
Length of an element in bytes
L
2
Meaning
Device configuration
rd:
wr:
Read access permitted
Write access permitted
Object Name
Config Table
Rights
rd/wr
Config Table Object
Configure the device using this object.
Object Description
Object
Config Table
Access
Read, write
Data type
Array of Unsigned 16
7 x 2 bytes
Index
0080hex
Subindex
00hex
01hex
02hex
03hex
04hex
05hex
06hex
07hex
Write all elements
Configuration channel 1 (AI1, AO1)
Configuration channel 2 (AI2, AO2)
Configuration channel 3 (AI3)
Configuration channel 4 (AI4)
AO format, AI format, system bits
Failsafe value AO1
Failsafe value AO2
Length (bytes)
0Ehex
02hex
Subindex 00hex
Subindex 01hex to 07hex
Data
Device configuration
Element Value Range
The "Configuration channel x" elements have the following structure:
Bit
Assignment
15
14
Wire
13
12
AO reset
11
Res.
OUTx (x = 2 to 5)
10
9
8
7
6
AO output range
AI filter
5
4
3
2
1
AI measuring range
0
For the value ranges for the individual parameters, please refer to Section "Parameters for Configuration" on page 32.
The "AO format, AI format, system bits" element has the following structure:
Bit
Assignment
7280_en_02
15
0
14
0
13
0
12
0
11
10
AO format
9
8
AI format
7
0
6
0
5
0
4
0
3
0
2
PF
1
0
AOV Conf
PHOENIX CONTACT
34
ILB IB AI4 AO2
For the value ranges for the "AO format" and "AI format" parameters, please refer to Section "Parameters for Configuration"
on page 32.
"PF"
If bit 2 = 1, a peripheral fault is generated in the event of a sensor problem (overrange, underrange, open circuit).
"AOV"
If bit 1 = 1, the "Analog Out Values" object may be written. This specifies that analog values for AO1 and AO2 are specified
via PCP and not via process data.
"Conf"
If bit 0 = 1, configuration via process data is permitted (command code 40xxhex).
The format of the failsafe value must be the Inline format.
If an invalid configuration is specified, a negative confirmation is generated with error message 08hex, 00hex or xx30hex. The
low byte of the additional error code is 30hex (value is out of range), the high byte contains the number of the affected
element.
Example: Config Table is completely written with data (subindex 00) and the entry for channel 2 is invalid. In this case, the
additional error code is equal to 0230hex.
18
PCP Communication
For information on PCP communication, please refer to the IBS SYS PCP G4 UM E and
IBS PCP COMPACT UM E user manuals.
18.1
Object Dictionary
Index
0080hex
0081hex
0085hex
0018hex
N:
L:
Data Type
Array of Unsigned 16
Array of Unsigned 16
Array of Unsigned 16
Record
Number of elements
Length of an element in bytes
7280_en_02
N
7
4
2
6
L
2
2
2
17
Meaning
Device configuration
Input Data
Output data
Diagnostic status
rd:
wr:
Read access permitted
Write access permitted
Object Name
Config Table
Analog In Values
Analog Out Values
DiagState
Rights
rd/wr
rd
rd/wr
rd
PHOENIX CONTACT
35
ILB IB AI4 AO2
18.2
Object Description
Config Table Object
Configure the device using this object. See "Config Table Object" on page 34.
Analog In Values Object
The elements of this object contain the analog values of the channels in the format that was selected for this channel.
Object Description
Object
Analog In Values
Access
Read
Data type
Array of Unsigned 16
Index
0081hex
Subindex
00hex
01hex
02hex
03hex
04hex
Read all elements
Analog value channel 1 (AI1)
Analog value channel 2 (AI2)
Analog value channel 3 (AI3)
Analog value channel 4 (AI4)
Length (bytes)
08hex
02hex
Subindex 00hex
Subindex 01hex to 04hex
Data
Analog values of the channels (input data)
4 x 2 bytes
Analog Out Values Object
The elements of this object specify the analog values of the output channels in the format that was selected for the relevant
channel.
Write access must be enabled in order to ensure error-free writing. To do this, in the "Config Table" object in element 5 set
bit 1 (AOV) = 1.
If write access is not enabled, a negative write confirmation will be generated with error message 08, 00, 0022hex (Service
cannot be executed at present).
Object Description
Object
Analog Out Values
Access
Read/write
Data type
Array of Unsigned 16
Index
0085hex
Subindex
00hex
01hex
02hex
Read/write all elements
Analog value channel 1 (AO1)
Analog value channel 2 (AO2)
Length (bytes)
04hex
02hex
Subindex 00hex
Subindex 01hex to 02hex
Data
Analog values of the channels (output data)
7280_en_02
2 x 2 bytes
PHOENIX CONTACT
36
ILB IB AI4 AO2
DiagState Object
The elements of this object contain the current diagnostic status of the device.
Object Description
Object
DiagState
Access
Read
Data type
Record
Index
0018hex
Subindex
00hex
Read all elements
01hex
Consecutive no.
Unsigned 16 (2 bytes)
02hex
Priority
Unsigned 8 (1 byte)
03hex
Channel
Unsigned 8 (1 byte)
04hex
Code
Unsigned 16 (2 bytes)
05hex
MoreFollows
Unsigned 8 (1 byte)
06hex
Text
OctetString (10 bytes)
Length (bytes)
11hex
01hex
02hex
0Ahex
Subindex 00hex
Subindex 02hex, 03hex, 05hex
Subindex 01hex, 04hex
Subindex 06hex
Data
Diagnostic status of the device
Consecutive no.
Priority
Channel
Code
MoreFollows
Text
7280_en_02
Meaning
Unique, consecutive error number since the
last power up reset or history reset
Priority of the message
Possible Values
0 to 65535
If Code = 0000hex, Priority = 00hex
otherwise Priority = 02hex
If Code = 0000hex, Channel = 00hex
otherwise Channel = 01hex to 04hex
Error code
0000hex: No error
8910hex: Overrange
8920hex: Underrange
7710hex: Cable break
5160hex: Power supply error
5010hex: Hardware fault
00hex = No additional information is available 00hex
for this error.
The first 10 characters of the status message. If Code = 0000hex,
Default: "Status OK"
Text = "Status OK"
otherwise text contains error-specific information
PHOENIX CONTACT
37
ILB IB AI4 AO2
19
Diagnostics
Error Table With Diagnostic Data and Status Indicators
Error Type
Diagnostic Data
Status Indicators
Sensor Supply
Sensor supply failure or sensor Message in the process data:
supply voltage too low
Indication of error code 8020hex in the measured value
(only for "IB IL" and "standardized representation" format)
US LED is OFF,
SF LED lights up red,
E1 to E4 LEDs light up
red
Sensor supply short circuit
SF LED lights up red,
Ex LED lights up red
Message in the process data:
Indication of error code 8020hex in the measured value
(only for "IB IL" and "standardized representation" format)
Analog Inputs
Open circuit during temperature Message in the process data:
measurement or in the range
Indication of error code 8002hex in the measured value
(only for "IB IL" and "standardized representation" format)
from 4 mA to 20 mA
Ex LED lights up red
Analog Outputs
Output value channel 1 ≥ 5% of
measuring range final value
LED 1 lights up yellow
Output value channel 2 ≥ 5% of
measuring range final value
LED 2 lights up yellow
General
Voltage failure of the internal
analog device supply
(5 V and 15 V)
Message in the process data:
Indication of error code 8020hex in the measured value
(only for "IB IL" and "standardized representation" format)
Faulty configuration
Message in the process data
Additional peripheral fault message sent to the control system
Module faulty
Message in the process data:
(e.g., due to component failure) Indication of error code 8040hex in the measured value
(only for "IB IL" and "standardized representation" format)
Overrange of the measuring
range
Message in the process data:
Indication of error code 8001hex in the measured value
(only for "IB IL" and "standardized representation" format)
Additional peripheral fault message sent to the control
system, if this is permitted
Underrange of the measuring
range
Message in the process data:
Indication of error code 8080hex in the measured value
(only for "IB IL" and "standardized representation" format)
Additional peripheral fault message sent to the control
system, if this is permitted
In the event of a message in the process data, the error bit is always set.
7280_en_02
PHOENIX CONTACT
38
ILB IB AI4 AO2
20
Channel Conversion Times and Process Data Update Time
The process data update time is determined from the sum of the channel conversion times for all four channels. The analog
outputs must be maintained within these times.
The conversion time of a channel is determined from the channel parameterization and combines the filter time plus special
additional times.
Channel conversion time = (Filter time + Time for resistance measurement + Measuring time for 4-wire connection)
x 3-wire factor
Filter Time
Filter 1: 4.5 ms
Filter 2: 1.1 ms
Time for Resistance
4-Wire Measuring Time
3-Wire Factor
Measurement
0.2 ms for all resistance 1 ms, if resistor is connected in 4-wire 2 ms, if resistor is connected in
measurements
technology
3-wire technology; otherwise 1 ms
Example:
Channel 1: Measuring range 0 V to 10 V, filter time = 4.5 ms
Channel 2: Measuring range 0 mA to 20 mA, filter time = 1.1 ms
Channel 3: Measuring range Pt 100, filter time = 4.5 ms, 4-wire
Channel 4: Measuring range Pt 1000, filter time = 4.5 ms, 2-wire with connector compensation
Channel
Configuration
[hex]
Filter Time
Time for
Resistance
Measurement
1
0000
4.5 ms
0 ms
2
0044
1.1 ms
0 ms
3
8009
4.5 ms
0.2 ms
4
800B
4.5 ms
0.2 ms
Process data update time = total of all channel conversion times
4-Wire
Measuring
Time*
0 ms
0 ms
1 ms
1 ms
3-Wire Factor
1
1
1
1
Channel
Conversion
Time
4.5 ms
1.1 ms
5.7 ms
5.7 ms
17 ms
* 4-wire measuring time also applies for 2-wire with connector compensation
Analog Conversion Time According to the Example Above:
Channel 3
Channel 1
Channel 2
0
2
Figure 18
7280_en_02
4
Channel 1
...
Channel 4
6
8
10
12
14
16
18
20
7285B021
Analog conversion time according to the example above
PHOENIX CONTACT
39
ILB IB AI4 AO2
21
Behavior of the Analog Outputs in
the Event of INTERBUS Reset and
Power Up
Both analog outputs behave independently of each other.
Event
INTERBUS
reset
AO Reset
Behavior
Hold
Reset
Failsafe
Power up
Hold
Reset
Failsafe
Response
Analog value is held
If AO output range 4 mA to
20 mA is configured, 4 mA is
output, otherwise 0 mA or 0 V
is output
The failsafe value for the
corresponding channel that is
specified in the "Config Table"
object is output
Output of 0 V
0 V or 0 mA
0 V or 0 mA
22
The extent of systematic and random errors (signal/noise
ratio) is greatly influenced by the connection method and
filter time selected. The lowest level of systematic and
random deviations can be achieved by selecting 4-wire
technology and a filter time of 4.5 ms.
22.1
–
–
–
–
–
–
7280_en_02
Notes on Systematic and Random
Errors During Resistance and
Temperature Measurement
Measures to Optimize Tolerances
Set the filter time to 4.5 ms (default setting).
Reduce random errors through additional application
filtering.
Minimize a large part of systematic errors through
user-specific system calibration.
Short circuit unused RTD channels.
Increase the sensor ground (connect sensor ground,
e.g., to a metal block).
Attention: Connect only one end of the shielding.
For 2-wire connection, use the version with connector
compensation.
PHOENIX CONTACT
40
ILB IB AI4 AO2
22.2
Connection Method
RTD 4-Wire Connection
The contact resistance of the connections and the cable
resistances have virtually no effect due to the 4-wire
connection technology.
RTD
1
U+ (I = 0 µA)
2
I+ RES
1
I+
1
I- RES
RL
2
RL
2
I-
U- U+
3
3
4
4
U- (I = 0 µA)
7285A018
Figure 19
22.3
RTD 4-wire connection
RTD 3-Wire Connection
RTD 2-Wire Connection With Connector Compensation
2-wire technology is a more cost-effective connection
method. The long U+ and U- cables to the sensor are no
longer needed here. They are jumpered directly at the
connector. The temperature-related voltage is not directly
measured at the sensor and therefore not falsified by the
two cable resistances RL. This connection method is ideal
for sensors with high R0 (e.g., Pt 1000, Ni 1000).
With 2-wire connection with connector compensation,
minimized tolerances can be achieved through:
– Parameterization of the terminal on a 4-wire
connection
– Direct jumpering of the U+ and U- connections at the
live measuring cables
A larger conductor cross section and sensors with higher
R0 further improve the tolerances of these connection
versions.
RTD
1
With 3-wire technology, the effect of the cable resistance on
the measured result in the terminal is minimized by multiple
measuring of the temperature-related voltage and
corresponding calculations. With this connection method,
one cable can be eliminated.
RTD
1
1
I2
RL
I+
I-
RES
2
U- U+
3
3
4
4
RL
7280B011
1
RL
2
U- U+
3
3
4
4
Figure 21
I+
I-
I- RES
2
1
2
I+ RES
1
2
I+ RES
RTD 2-wire connection
with connector compensation
RL
U- (I = 0 µA)
7285A017
Figure 20
7280_en_02
RTD 3-wire connection
PHOENIX CONTACT
41
ILB IB AI4 AO2
22.4
Systematic Errors During Temperature Measurement With 2-Wire Technology
With 2-wire connection method, the cable resistances are
in series for the sensor resistance and result in systematic
measuring errors. This is described in greater detail below.
1 5 .0
K
1 2 .0
D T
9 .0
(1 )
(2 )
6 .0
2.5
K
2.0
DT
1.5
1.0
0.5
0.0
-30
(3 )
3 .0
0 .0
0 .0
2 .5
5 .0
7 .5
1 0 .0
1 2 .5
1 5 .0
1 7 .5 m
l
2 0 .0
-20
-10
0
+10
+20
+30
+40
+50 °C +60
TA
7285A023
Figure 24
Systematic temperature measuring error ΔT
depending on the cable temperature TA
5 7 5 5 1 0 1 4
Systematic temperature measuring error ΔT
depending on the cable length l
Figure 22
Curves depending on the cable cross section A
Temperature measuring error for A = 0.14 mm2
Temperature measuring error for A = 0.25 mm2
Temperature measuring error for A = 0.50 mm2
(1)
(2)
(3)
(Measuring error valid for: copper cable χ = 57 m/Ωmm2,
TA = 25°C and Pt 100 sensor)
(Measuring error valid for: copper cable χ = 57 m/Ωmm2,
l = 5 m, A = 0.25 mm2, and Pt 100 sensor)
All diagrams show that the increase in cable resistance
causes the measuring error.
A considerable improvement is made through the use of
Pt 1000 sensors. Due to the 10-fold higher temperature
coefficient α (α = 0.385 Ω/K for Pt 100 to α= 3.85 Ω/K for
Pt 1000) the effect of the cable resistance on the
measurement is decreased by factor 10. All errors in the
diagrams above would be reduced by factor 10.
Figure 22 clearly shows the effect of the cable length on the
cable resistance and therefore on the measuring error. The
solution is to use the shortest possible sensor cables.
6.0
K
5.0
DT 4.0
3.0
2.0
1.0
0.0
Figure 23 shows the effect of the cable cross section on the
cable resistance. Cables with a cross section of less than
0.5 mm2 cause errors to increase exponentially.
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
2
0.8 0.9 mm 1.0
A
7285A022
Figure 23
Systematic temperature measuring error ΔT
depending on the cable cross section A
Figure 24 shows the effect of the ambient temperature on
the cable resistance. This parameter does not play a great
role and can hardly be influenced but it is mentioned here
for the sake of completeness.
(Measuring error valid for: copper cable χ = 57 m/Ωmm2,
TA = 25°C, l = 5 m, and Pt 100 sensor)
7280_en_02
PHOENIX CONTACT
42
ILB IB AI4 AO2
The formula for calculating the cable resistance is as
follows:
L
=
L
=
R
R
R
L 2 0
l
c x A
1
x ( 1 + 0 .0 0 4 3
x T A)
K
1
x ( 1 + 0 .0 0 4 3
K
x T A)
Where:
Cable resistance in Ω
Cable resistance at 20°C in Ω
Cable length in m
Specific electrical resistance of copper in
Ωmm2/m
A
Cable cross section in mm2
0.0043 1/K Temperature coefficient for copper
Ambient temperature (cable temperature)
TA
in °C
RL
RL20
l
χ
Since there are two cable resistances in the measuring
system (forward and return), the value must be doubled.
The absolute measuring error in Kelvin [K] according to DIN
can be obtained for platinum sensors using the average
temperature coefficient α (α = 0.385 Ω/K for Pt 100;
α = 3.85 Ω/K for Pt 1000).
© PHOENIX CONTACT 02/2007
7280_en_02
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
Phone: +49 - 52 35 - 30 0 • Fax: +49 - 52 35 - 34 12 00
www.phoenixcontact.com
43