Current transformer - PACT RCP-4000A-UIRO-D190 - 2906233
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Set consisting of a 4-way signal conditioner with screw connection technology and a Rogowski coil 600 mm in
length/190 mm in diameter for AC current measurement on busbars and power lines.
The signal conditioner outputs 8 different standard signals on the output side and has one switching output.
Key Commercial Data
Packing unit
1 pc
Weight per Piece (excluding packing)
480.0 g
Custom tariff number
85437090
Country of origin
Germany
Technical data
Measuring transducer supply
Nominal supply voltage
24 V DC
Nominal supply voltage range
9.6 V DC ... 30 V DC
Power consumption
≤ 1 W (at IOUT = 20 mA, 9.6 V DC, 600 Ω load)
Measuring coil input data
Frequency measuring range
40 Hz ... 20000 Hz
Position error
100 kΩ
Measuring coil signal output
10/29/2015 Page 1 / 4
https://www.phoenixcontact.com/us/products/2906233
Current transformer - PACT RCP-4000A-UIRO-D190 - 2906233
Technical data
Measuring coil signal output
Output signal (at 50 Hz)
100 mV (no load, at 1,000 A)
Output voltage (in no-load operation)
VOUT = M * dI/dt
Output voltage (sinusoidal, in no-load operation)
100 mV (VOUT = 2 * π * M * f * I (M = 0.318 μH; example: At 50 Hz; I =
1,000 A))
Measuring transducer signal output
Current output signal
0 mA ... 20 mA (via DIP switch)
4 mA ... 20 mA (via DIP switch)
0 mA ... 10 mA (via DIP switch)
2 mA ... 10 mA (via DIP switch)
0 mA ... 21 mA (Can be set via software)
Voltage output signal
0 V ... 10 V (via DIP switch)
2 V ... 10 V (via DIP switch)
0 V ... 5 V (via DIP switch)
1 V ... 5 V (via DIP switch)
0 V ... 10.5 V (Can be set via software)
Load/output load current output
≤ 600 Ω (20 mA)
General data, measuring coil
Length of measuring coil
600 mm
Diameter of measuring coil
8.3 mm ±0.2 mm
Length of signal cable
3000 mm
Conductor structure signal line
2x 0.22 mm (Signal (tinned))
1x 0.22 mm (Shielding (tinned))
Coil material
Elastollan
Housing material
PC
Insulation
double insulation
Rated insulation voltage
1000 V AC (rms CAT III)
600 V AC (rms CAT IV)
Test voltage
10.45 kV (DC / 1 min.)
Basic accuracy