TRIO-UPS-2G/1AC/24DC/10
Uninterruptible power supply
Data sheet
107432_en_02
1
© PHOENIX CONTACT 2018-04-19
Description
The TRIO-UPS-2G uninterruptible power supply (UPS) with
integrated power supply unit is used to ensure that secure
DC power for critical electrical loads continues to be
supplied in the event of disturbances in the power supply
network, e.g. due to mains breakdown or failure. In the event
of such a disturbance, the UPS switches to battery
operation without interruption so that connected loads
continue to be continuously supplied. In this operating
mode, the output voltage is directly dependent on the
battery voltage. When mains power is restored, the UPS
automatically returns to normal operation. The connected
loads are again supplied via the power supply network and
the battery is charged at the same time. The TRIO-UPS-2G
uninterruptible power supply (UPS) is designed specifically
for supplying industrial PCs (IPCs).
Features
–
–
–
–
–
–
Power supply, loading unit and electronic switchover
unit in a device
Wide-range input AC
Adjustable output voltage in mains operation
USB interface for configuration and diagnostics
Adjustable charging parameters for the use of different
types of energy storage
Comprehensive signaling
Technical data (short form)
Input voltage range
100 V AC ... 240 V AC
110 V DC ... 250 V DC
Nominal output voltage (UN)
24 V DC
Nominal output current (IN)
10 A
Buffer period
to 3 h
Residual ripple
< 20 mV
MTBF (IEC 61709, SN 29500)
> 2007013 h (230 V AC, at 25 °C)
> 1210518 h (230 V AC, at 40 °C)
> 575978 h (230 V AC, at 60 °C)
Maximum power dissipation in noload condition
< 3 W (for 230 V AC)
Power loss nominal load max.
< 32 W (for 230 V AC)
Ambient temperature (operation)
-25 °C ... 70 °C ( > 60 °C Derating:
2.5 %/K )
Ambient temperature (start-up type
tested)
-40 °C
Dimensions W/H/D
68 mm / 130 mm / 160 mm
Weight
1.34 kg
Make sure you always use the latest documentation.
It can be downloaded from the product at phoenixcontact.net/products.
TRIO-UPS-2G/1AC/24DC/10
2
Table of contents
1
Description .............................................................................................................................. 1
2
Table of contents ..................................................................................................................... 2
3
Ordering data .......................................................................................................................... 3
4
Technical data ......................................................................................................................... 4
5
Safety and installation notes .................................................................................................. 10
6
Structure................................................................................................................................ 12
7
Mounting and removing ......................................................................................................... 14
8
Device connection ................................................................................................................. 16
9
Device operation ................................................................................................................... 20
10
Method of operation............................................................................................................... 25
11
Battery management ............................................................................................................. 25
12
Signaling................................................................................................................................ 26
13
Interface ................................................................................................................................ 29
14
Derating................................................................................................................................. 29
15
Parallel operation................................................................................................................... 30
107432_en_02
PHOENIX CONTACT 2 / 30
TRIO-UPS-2G/1AC/24DC/10
3
Ordering data
Description
Type
Order No.
Pcs./Pkt.
Uninterruptible power supply with integrated power supply TRIO-UPS-2G/1AC/24DC/10
unit. For lead AGM energy storage with 1.3 Ah to 38 Ah
nominal capacity. Input: 1-phase, output: 24 V DC/10 A.
Push-in connection technology
2907161
1
Accessories
Order No.
Type
Pcs./Pkt.
Energy storage device, lead AGM, VRLA technology, 24 V UPS-BAT/VRLA/24DC/1.3AH 2320296
DC, 1.3 Ah, tool-free battery replacement, automatic
detection, and communication with QUINT UPS-IQ
1
Energy storage device, lead AGM, VRLA technology, 24 V UPS-BAT/VRLA/24DC/3.4AH 2320306
DC, 3.4 Ah, tool-free battery replacement, automatic
detection, and communication with QUINT UPS-IQ
1
Energy storage device, lead AGM, VRLA technology, 24 V UPS-BAT/VRLA/24DC/7.2AH 2320319
DC, 7.2 Ah, tool-free battery replacement, automatic
detection, and communication with QUINT UPS-IQ
1
Energy storage device, lead AGM, VRLA technology, 24 V UPS-BAT/VRLA/24DC/12AH
DC, 12 Ah, tool-free battery replacement, automatic
detection, and communication with QUINT UPS-IQ
2320322
1
Energy storage device, lead AGM, VRLA technology, 24 V UPS-BAT/VRLA/24DC/38AH
DC, 38 Ah, automatic detection, and communication with
QUINT UPS-IQ
2320335
1
Used for communication between an industrial PC and
Phoenix Contact devices with USB-Mini-B connection.
2908217
1
2901664
1
MINI-SCREW-USBDATACABLE
2-piece universal wall adapter for securely mounting the UWA 130
power supply in the event of strong vibrations. The profiles
that are screwed onto the side of the power supply are
screwed directly onto the mounting surface. The universal
wall adapter is attached on the left/right.
Our range of accessories is being continually extended, our current range can be found in the download area.
107432_en_02
PHOENIX CONTACT 3 / 30
TRIO-UPS-2G/1AC/24DC/10
4
Technical data
Input data
Input voltage range
100 V AC ... 240 V AC
110 V DC ... 250 V DC
Derating
< 90 V AC (2.5 %/V)
Current consumption (for nominal values) typical
4.5 A (100 V AC) / 2 A (240 V AC)
4 A (110 V DC) / 1.8 A (250 V DC)
Inrush surge current I2t
< 9 A / < 0.2 A2s
Input fuse slow-blow, internal
6.3 A
Permissible backup fuse
B10
Crest factor
1.5
Input connection data
Connection method
Push-in connection
Conductor cross section, solid
0.2 mm² ... 4 mm²
Conductor cross section, flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG/kcmil
24 ... 12
Stripping length
10 mm
Output data
Derating
> 60 °C (2.5%/K of POut nom.)
Switch-over time
< 20 ms
Output data (mains operation)
Nominal output voltage (UN)
24 V DC
Nominal output current (IN)
10 A
Output data (battery operation)
Nominal output voltage (UN)
UBAT - 0.1 V DC
Nominal output current (IN)
10 A
Output connection data
Connection method
Push-in connection
Conductor cross section, solid
0.2 mm² ... 4 mm²
Conductor cross section, flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG/kcmil
24 ... 12
Stripping length
10 mm
107432_en_02
PHOENIX CONTACT 4 / 30
TRIO-UPS-2G/1AC/24DC/10
Charging process
Battery technology
VRLA
Charge characteristic curve
IU0U
Nominal voltage
24 V DC
Nominal capacity range
1.3 Ah ... 38 Ah
Maximum capacity
140 Ah
Charging voltage maximum
30 V DC
Charge current typical
0.2 A ... 3 A ( -25 °C ... 60 °C )
0 A ( 60 °C ... 70 °C )
Output connection battery
Connection method
Push-in connection
Conductor cross section, solid
0.2 mm² ... 10 mm²
Conductor cross section, flexible
0.2 mm² ... 6 mm²
Conductor cross section AWG/kcmil
24 ... 6
Stripping length
15 mm
Status and diagnostic indicators/signal outputs DC OK
Switching output
Transistor output, active
Output voltage
24 V DC
Continuous load current
20 mA
Status display
LED ( green )
Status and diagnostic indicators/signal outputs Alarm
Switching output
Transistor output, active
Output voltage
24 V DC
Continuous load current
20 mA
Status display
LED ( red )
Status and diagnostic indicators/signal outputs Battery Mode
Switching output
Transistor output, active
Output voltage
24 V DC
Continuous load current
20 mA
Status display
LED ( yellow )
Status and diagnostic indicators/signal outputs Ready
Switching output
Transistor output, active
Output voltage
24 V DC
Continuous load current
20 mA
107432_en_02
PHOENIX CONTACT 5 / 30
TRIO-UPS-2G/1AC/24DC/10
Signal connection data
Connection method
Push-in connection
Conductor cross section, solid
0.2 mm² ... 1.5 mm²
Conductor cross section, flexible
0.2 mm² ... 1.5 mm²
Conductor cross section AWG/kcmil
24 ... 16
Stripping length
8 mm
Remote control ( Remote )
Digital control input (configurable)
Low signal
High signal
Connection to SGnd with < 2.7 kΩ
Open (> 35 kΩ between remote and SGnd)
Battery-operated start (bat. start)
Digital control input low-active
Low signal
High signal
Connection to SGnd with < 2.7 kΩ
Open (> 200 kΩ between bat. start and SGnd)
Interface
USB classification
MINI-USB type B
Device combinations
UPS connection in parallel
yes, with diode module uncoupled
UPS connection in series
no
Energy storage device connection in parallel
yes, max. 5
Power consumption
Maximum power dissipation in no-load condition
3W
Power loss nominal load max.
32 W
General data
Overvoltage category
EN 61010-1
Efficiency (for nominal values)
II
(ICHARGE = 0; IOUT = IN) 90 % ( 120 V AC )
(ICHARGE = 0; IOUT = IN) 91 % ( 230 V AC )
MTBF
> 2007013 h (230 V AC, at 25 °C)
Degree of protection
IP20
Protection class
I
Side element version
Aluminum
Hood version
PC
Dimensions W/H/D (normal mounting position/delivered
condition)
68 mm / 130 mm / 160 mm
Weight
1.34 kg
107432_en_02
PHOENIX CONTACT 6 / 30
TRIO-UPS-2G/1AC/24DC/10
Ambient conditions
Ambient temperature (operation)
-25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
Ambient temperature (start-up type tested)
-40 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Max. permissible relative humidity (operation)
≤ 93 % (At +25°C, non-condensing)
Installation height
≤ 4000 m (> 2000 m, observe derating)
Degree of pollution
2
Vibration (operation)
Pn
5
6
+
2.1
+
2.2
–
2.3
–
2.4
–
2.5
7
DC OK
Alarm
Bat.-Mode
Ready
Remote
Bat.-Start
SGnd
Output
DC 24V 10A
tmax
Custom
(Default 0.5) 1 2 [min]
3
PC-Mode
5
Service 15 10
DC OK
Bat.-Mode
Bat.-Charge
24-28V
Alarm
P>Pn
Input
AC 100-240V
L/+
1.1
N/–
1.2
2
1.3
Input
AC 100-240V
L/+
1.1
N/–
1.2
1
1.3
3.1
3.2
3.3
3.4
3.5
3.6
3.7
130
3
DC OK
Alarm
Bat.-Mode
Ready
Remote
Bat.-Start
SGnd
TRIO DC-UPS Ord. No.2907161
4
+
2.1
+
2.2
–
2.3
–
2.4
–
2.5
68
50
Function elements
115
6.1
Device dimensions and keep-out areas
230
Structure
TRIO DC-UPS Ord. No.2907161
6
Battery 24V
+
4.1
–
4.2
8
Battery 24V
+
4.1
9
–
4.2
10
Figure 2
Keep-out areas
11
160
Figure 1
Function elements
157
5
6
7
8
9
10
11
107432_en_02
45
2
3
4
Designation
Connection terminal blocks input voltage:
input L/N/
Potentiometer, output voltage: 24 V DC ... 28 V DC
LED signaling
Connection terminal blocks output voltage:
Output DC +/Connection terminal blocks: Digital input/output
(24 V DC / 20 mA)
Rotary selector switch
Status and diagnostics indicators
Universal DIN rail adapter (rear of housing)
QR code web link
Battery terminal blocks
USB interface MINI type B
80
No.
1
130
Key
167
Figure 3
Device dimensions
PHOENIX CONTACT 12 / 30
TRIO-UPS-2G/1AC/24DC/10
6.3
Block diagram
L
1.1
Input N
1.2
PE
2.1 +
2.2 +
2.3 - Output
2.4
2.5
-
Active
PFC
1.3
=
=
+ 4.1
External 4.2
Battery
Figure 4
C
3.1
3.2
3.3
3.4
3.5
3.6
3.7
DC OK
Alarm
Bat.-Mode
Ready
Remote
Bat.-Start
SGnd
Block diagram
Key
Element
Meaning
Microprocessor
μC
LED
J
Temperature sensor
Selector switch
Fuse
Decoupling
Switch
Electrically isolated signal transmission
Regulation
Transformer
DC/DC converter with electrical isolation
=
=
107432_en_02
PHOENIX CONTACT 13 / 30
TRIO-UPS-2G/1AC/24DC/10
7
Mounting and removing
7.2
Normal mounting position
The device can be snapped onto all DIN rails
according to EN 60715 and should only be
mounted in the normal mounting position.
NOTE
The device must be installed in a control
cabinet that can be locked and only opened
by specialist staff.
7.1
Convection
NOTE: enable convection
TRIO DC-UPS
Depending on the ambient temperature and
load on the uninterruptible power supply, the
housing can become hot.
In order to ensure sufficient convection, we
recommend a minimum vertical distance of
50 mm to the other devices.
+
2.1
+
2.2
2.3
2.4
2.5
O
DC utpu
24 t
V1
0A
DC
24
OK
-28
V
In
AC pu
10 t
0-2
4
DC
O
Ala K
t.-M rm
od
Re e
a
Re dy
Ba mote
t.-S
tart
SG
nd
Ba
3.1
3.2
3.3
3.4
3.5
3.6
3.7
(D Cu
efa sto
ult m
0.5 1 tm
)
2 [max
PC
in
-M
3 ]
od
Ba
Se e
5
t.
rvic
Ba -Mo
e 1 10
t.-C de
5
ha
rge
Ala
rm
P>
Pn
0V
L /+
1.1
N
/1.2
Ba
tte
1.3
ry
24
V
+
4.1
TRIO DC-UPS
4.2
O
DC utpu
24 t
V1
0A
DC
OK
24
-28
V
In
AC pu
10 t
0-2
4
+
2.1
+
2.2
2.3
2.4
2.5
Figure 6
DC
O
Ala K
t.-M rm
od
Re e
a
Re dy
Ba mote
t.-S
tart
SG
nd
Ba
3.1
3.2
3.3
3.4
3.5
3.6
3.7
(D Cu
efa sto
ult m
0.5 1 tm
)
2 [max
PC
in
-M
3 ]
od
Ba
Se e
5
t.
rvic
Ba -Mo
e 1 10
d
t.
5
-Ch e
arg
e
Ala
rm
P>
Pn
0V
L /+
1.1
N
/1.2
Ba
1.3
tte
ry
24
V
+
4.1
4.2
Figure 5
Convection
7.3
Normal mounting position
Mounting the uninterruptible power supply
Proceed as follows to mount the device:
1. In the normal mounting position the device is mounted
on the DIN rail from above. Make sure that the universal
DIN rail adapter is in the correct position behind the DIN
rail (A).
2. Then press the device down until the universal DIN rail
adapter audibly latches into place (B).
3. Check that the device is securely attached to the DIN
rail.
A
Click
Figure 7
107432_en_02
B
Snapping onto the DIN rail
PHOENIX CONTACT 14 / 30
TRIO-UPS-2G/1AC/24DC/10
7.4
Removing the uninterruptible power supply
Proceed as follows to remove the device:
1. Take a suitable screwdriver and insert this into the lock
hole on the universal DIN rail adapter (A).
2. Release the lock by lifting the screwdriver (B).
3. Carefully swivel the device forward (C) so that the lock
slides back into the starting position.
4. Then separate the device from the DIN rail (D).
D
Figure 9
C
A
Figure 8
7.5
B
Removing from the DIN rail
7.6
Mounting the universal DIN rail adapter
Wall mounting
The UWA 130 universal wall adapter (Order No. 2901664) is
used to attach the uninterruptible power supply directly to
the mounting surface.
The use of the universal wall adapter is recommended under
extreme ambient conditions, e.g., strong vibrations. Thanks
to the tight screw connection between the uninterruptible
power supply and the universal wall adapter or the actual
mounting surface, an extremely high level of mechanical
stability is ensured.
Rotated mounting position (270° Y-axis)
For rotated installation, use the existing universal DIN rail
adapter and the Torx screws available.
The maximum tightening torque of the Torx
screw (Torx® T10) is 0.7 Nm.
To mount the uninterruptible power supply in a rotated
position, fasten the universal DIN rail adapter to the left side
of the housing as follows:
1. Remove the screws for the factory-installed universal
DIN rail adapter using a suitable screwdriver (Torx 10).
2. Remove the universal DIN rail adapter from the rear of
the uninterruptible power supply.
3. Position the universal DIN rail adapter so that the
mounting holes match the hole pattern on the left side of
the housing.
4. Insert the Torx screws into the appropriate hole pattern
on the universal DIN rail adapter so that the necessary
drill holes on the device can be accessed.
5. Screw the universal DIN rail adapter onto the device.
107432_en_02
The UWA 130 is attached to the
uninterruptible power supply by means of the
Torx screws of the universal wall adapter.
The maximum tightening torque of the Torx
screw (Torx® T10) is 0.7 Nm.
Make sure you use suitable mounting material
when attaching to the mounting surface.
PHOENIX CONTACT 15 / 30
TRIO-UPS-2G/1AC/24DC/10
7.6.1
Mounting the UWA 130 2-piece universal wall
adapter
Proceed as follows to disassemble the universal DIN rail
adapter that comes pre-mounted:
1. Remove the screws for the universal DIN rail adapter
using a suitable screwdriver (Torx 10).
2. Remove the universal DIN rail adapter from the rear of
the uninterruptible power supply.
3. Position the two-piece universal wall adapter on the
right and left side of the housing.
4. Insert the Torx screws into the appropriate hole pattern
on the universal wall adapter so that the necessary
mounting holes of the device can be accessed.
5. Screw the universal wall adapter onto the device.
8
Device connection
8.1
Push-in connection technology
The connection terminal blocks feature front-side Push-in
connection technology. The device wiring is performed by
plugging in, without tools.
8.1.1
Plug in connecting cable
The wiring is carried out by simply plugging the connecting
cable into the contact opening provided. Insert the
connecting cable as far as it will go.
A
Figure 11
8.1.2
Insert connecting cable (push-in connection
technology)
Loosen the connecting cable
To disconnect the wiring, take a suitable screwdriver and
insert it into the opening for release. Then carefully pull the
connecting cable out of the contact opening.
Figure 10
B
Mounting the UWA 130 universal wall adapter
A
Figure 12
8.2
Release connecting cable (push-in connection
technology)
Conductor cross sections
L [mm]
Input, Output
[mm²]
AWG
0,2-4
0,2-2,5
24-12
10
Battery
0,2-10
0,2-6
24-8
15
Signals
0,2-1,5
0,2-1,5
24-16
8
Figure 13
107432_en_02
[mm²]
Conductor cross sections
PHOENIX CONTACT 16 / 30
TRIO-UPS-2G/1AC/24DC/10
8.3
AC input
The supply voltage is connected via "Input AC" connection
terminal blocks.
Input AC 100-240V
L
N
PE
TRIO DC-UPS
Figure 15
O
DC utpu
24 t
V1
0A
+
2.1
+
2.2
2.3
2.4
2.5
DC
OK
24
-28
V
In
AC pu
10 t
0-2
4
8.3.2
DC
O
Ala K
t.-M rm
od
Re e
a
Re dy
Ba mote
t.-S
tart
SG
nd
Ba
3.1
3.2
3.3
3.4
3.5
3.6
3.7
(D Cu
efa sto
ult m
0.5 1 tm
)
2 [max
PC
in
-M
3 ]
od
e
Ba
t.-M Servic 5
Ba
e 1 10
od
t.
5
-Ch e
arg
e
Ala
rm
P>
Pn
L /+
1.1
N
/1.2
Ba
1.3
tte
ry
Schematic diagram, switching the input
terminals
The uninterruptible power supply can be operated on singlephase AC or DC power grids in accordance with the nominal
input voltage. Connection is via the INPUT L+/N-/
connection terminal blocks.
Input
AC 100-240V
TN-S
TN-C
N/–
1.2
24
L
N
PE
V
+
4.1
4.2
+
-
L/+
N/-
+
-
Input voltage connection terminal blocks: input
L/N/
TT
Protection of the primary side
iT
L
N
If loads must not be supplied in the event of a
mains voltage dip or failure, they must be
connected directly to the input of the
uninterruptible power supply as an unbuffered
AC load.
8.3.1
L
N
PEN
1.3
L/+
N/-
Figure 14
N/-
Mains connection
L1/+
1.1
0V
L/+
L/+
N/-
Figure 16
+
-
L
N
L/+
N/-
+
-
Network types
It must be possible to switch the device off using a suitable
disconnection device outside the power supply. For
example, the primary-side line protection is suitable for this
(see technical data).
An internal, approved AC/DC fuse is available as device
protection. Additional device protection is not required.
If an internal fuse trips, this is due to a device
fault. In this case, the device must be
inspected in the factory. Opening the device
or repairing it yourself is prohibited.
107432_en_02
PHOENIX CONTACT 17 / 30
TRIO-UPS-2G/1AC/24DC/10
8.4
DC output
8.5
Buffered output voltage is connected via "Output DC"
connection terminal blocks.
+
+
2.2
–
2.3
–
2.4
–
Battery 24V
The battery module is connected to the uninterruptible
power supply via the "Battery 24V" terminals.
+
2.1
+
O
DC utpu
24 t
V1
0A
2.2
2.3
2.4
2.5
DC
OK
24
-28
V
In
AC pu
10 t
0-2
4
DC
O
Ala K
t.-M rm
od
Re e
a
Re dy
Ba mote
t.-S
tart
SG
nd
Ba
3.1
3.2
3.3
3.4
3.5
3.6
3.7
(D Cu
efa sto
ult m
0.5 1 tm
)
2 [max
PC
in
-M
3 ]
od
e
Ba
t.-M Servic 5
Ba
e 1 10
od
t.
5
TRIO DC-UPS
TRIO DC-UPS
2.1
2.4
2.5
O
DC utpu
24 t
V1
0A
2.5
DC
Output
DC 24V 10A
24
-Ch e
arg
e
Ala
rm
P>
Pn
OK
-28
V
In
AC pu
10 t
0-2
4
L /+
1.1
N
/1.2
L /+
1.1
(D Cu
efa sto
ult m
0.5 1 tm
)
2 [max
PC
in
-M
3 ]
Ba
tte
1.3
ry
24
V
Battery 24V
Ba
V
Output voltage connection terminal blocks:
Output DC +/-
The uninterruptible power supply is electronically shortcircuit-proof and idling-proof. In the event of an error, the
output voltage is limited.
It must be ensured that all output cables are dimensioned
appropriately for the maximum output current or have
separate protection.
The connecting cables on the secondary side should have
large cross sections to keep the voltage drops in the cables
as low as possible.
Output DC 24V 10A
4.1
–
4.2
Protection of the secondary side
107432_en_02
+
24
4.2
+
4.1
Figure 18
ry
+
4.1
4.2
Figure 17
3.1
3.2
3.3
3.4
3.5
3.6
3.7
od
Ba
Se e
5
t.
rvic
Ba -Mo
e 1 10
t.-C de
5
ha
rge
Ala
rm
P>
Pn
tte
1.3
8.4.1
DC
O
Ala K
t.-M rm
od
Re e
a
Re dy
Ba mote
t.-S
tart
SG
nd
Ba
0V
0V
N
/1.2
+
2.1
+
2.2
2.3
+
+
R Load
Figure 19
Connection terminal blocks Battery 24V
NOTE: Risk of short circuit
The fuse of the rechargeable battery module
must be removed when installing or replacing
the module.
The batteries are sealed, maintenance-free
lead-AGM batteries that are intended for
ambient temperatures from 0°C ... 40°C. The
service life is six to nine years at an ambient
temperature of 20°C. To ensure immediate
availability, all batteries are delivered fully
charged. The batteries should be placed in
service within no more than nine months at
20°C ... 30°C, or six months at 30°C ... 40°C.
-
Schematic diagram, switching the output
terminals
PHOENIX CONTACT 18 / 30
TRIO-UPS-2G/1AC/24DC/10
8.6
Connection terminal block signaling
Example:
The uninterruptible power supply has the signal outputs:
– DC OK
– Alarm (can be inverted via software)
– Bat. Mode (can be inverted and parameterized via
software)
– Ready (can be inverted and parameterized via
software)
DC OK
Alarm
Bat.-Mode
Ready
Remote
Bat.-Start
SGnd
Figure 21
8.7
Signal inputs activated
Installation of individual components
WARNING
TRIO DC-UPS
Provide a switch/circuit breaker close to the
device at the AC input, DC output and at the
battery terminals, which are labeled as the
disconnecting device for this device.
O
DC utpu
24 t
V1
0A
+
2.1
+
2.2
2.3
2.4
2.5
DC
OK
24
-28
V
In
AC pu
10 t
0-2
4
DC
O
Ala K
t.-M rm
od
Re e
a
Re dy
Ba mote
t.-S
tart
SG
nd
Ba
(D Cu
efa sto
ult m
0.5 1 tm
)
2 [max
PC
in
-M
3 ]
od
Ba
Se e
5
t.
rvic
Ba -Mo
e 1 10
d
t.
5
-Ch e
arg
e
Ala
rm
P>
Pn
3.1
3.2
3.3
3.4
3.5
3.6
3.7
DC OK
Alarm
Bat.-Mode
Ready
Remote
Bat.-Start
SGnd
3.1
3.2
3.3
3.4
3.5
3.6
3.7
NOTE
As so-called wear parts, batteries are not
provided with a warranty. Deep discharge and
storage beyond the permitted temperature
range lead to irreversible damage to batteries.
0V
L /+
1.1
N
/1.2
Ba
1.3
tte
ry
24
Follow the documentation for the individual
components during installation.
V
+
4.1
4.2
Figure 20
Signal inputs and outputs
The signal outputs are non-isolated (DC output voltage)
active outputs. The signal ground (SGnd) or ground
connection for the output voltage serves as the reference
potential.
The uninterruptible power supply also features the signal
inputs:
– Remote (can be inverted via software)
– Bat.-Start
The signal inputs are activated as soon as they are
connected to the signal ground.
TRIO
DC-UPS
Input
AC
L N
Output
DC
+ -
Energy
storage
Battery
DC
+ -
+ -
Buffered
DC load
Protective conductor
Figure 22
Schematic design
The image is a schematic representation of
the design and does not contain all parts.
Observe the installation instructions.
107432_en_02
PHOENIX CONTACT 19 / 30
TRIO-UPS-2G/1AC/24DC/10
9
Device operation
UIN
Basic settings for commissioning can be made directly via
the rotary selection switch on the device. Advanced settings
can be made via the UPS-CONF PC software.
UOUT
The latest software version is to be found in
the product download area.
t0
Use a suitable screwdriver to set the rotary
selector switch.
1
tmax
[min]
2
Custom
3
(Default 0.5)
5
PC-Mode
Service
Figure 23
10
15
Figure 24
t1: after the preset buffer time has expired, the output is
switched off
Refer to the following diagram for possible buffer times for
varying discharge currents.
30
Rotary selector
switch setting
1, 2, 3, 5, 10, 15
Custom (default
0.5)
(unlimited)
10
1
60
10 = 1,3Ah
= 3,4Ah
= 7,2Ah
= 12Ah
= 38Ah
1
1
0
2
Rotary selector switch
Setting the buffer time
t0: mains power failure
Time [h]
You can set the following functions via the rotary selector
switch on the front of the device:
– Buffer period
– PC mode
– Service mode
9.1.1
t
Setting the operating mode
Time [min.]
9.1
t1
3
4
5
6
7
8
9
10
Current [A]
Figure 25
Buffer time/discharge current diagram
Meaning
The UPS switches off after the set
buffer time.
The UPS switches off after the
individual buffer time set via UPSCONF.
If a buffer time is not set, the UPS
shuts down after 30 seconds.
Buffering with the total stored energy.
An alarm is generated as soon as the
voltage of the energy storage falls
below 20.4 V (default).
Refer to the following diagram for information on how the
device behaves in buffer mode:
107432_en_02
PHOENIX CONTACT 20 / 30
TRIO-UPS-2G/1AC/24DC/10
9.1.2
4. PC idle time
PC mode
In PC mode, you can individually parameterize the
chronological sequence of the UPS functions via the UPSCONF configuration software.
To access the PC mode of the UPS, set the rotary selector
switch to PC mode.
The following components are required for the
PC mode function:
Data cable MINI-SCREW-USB-DATACABLE
(Order No. 2908217)
Only if the PC is shut down and the mains supply is restored
in the meantime is the output voltage interrupted for the
reset time and the PC then started automatically.
1+2
4
UOUT
PC
Configuration software UPS-CONF (Order
No. 2320403)
t0
In the event of a mains failure, one PC can continue to work,
perform a controlled shutdown, and restart automatically.
3
UIN
Figure 27
t2
t1
t3 t4
t
1. Delay time
t0: mains power failure
If the mains supply is not restored during the delay time, the
PC is shut down.
t1: delay time and program runtime have expired, PC will be
shut down
t2: mains restored while PC is shutting down
2. Program start
t3: the PC has shut down and the output will be switched off,
PC idle time starts
After the delay time has expired, it is possible to start a
program.
t4: the PC idle time has expired, PC is starting back up
3. PC shutdown
If the Remote contact is opened in PC mode,
the preset delay time is skipped in the event of
a mains failure.
The time required for PC shutdown is set here.
1+2
3
UIN
9.1.3
Service mode
UOUT
When working in a system, it may be necessary to switch the
uninterruptible power supply unit over to service mode.
PC
To access the Service mode of the UPS, set the rotary
selector switch to Service.
t0
Figure 26
t1
t2
t
t0: mains power failure
t1: delay time and program runtime have expired, PC will be
shut down
t2: the PC has shut down, the output will be switched off
107432_en_02
You can enter the service mode only if input
voltage is present. If the supply voltage fails
while in service mode, the uninterruptible
power supply switches to battery operation
with unlimited buffer time. The signaling then
corresponds to the signaling for battery
operation.
In this operating mode, DC battery connection
terminal blocks are deactivated using
software. The active signal output is always
activated when the unit is switched over to
service mode.
PHOENIX CONTACT 21 / 30
TRIO-UPS-2G/1AC/24DC/10
Energy storage device replacement
WARNING
When connecting the batteries take note of
the polarity.
Do not short circuit the pole terminals.
The batteries are maintenance free and may
not be opened.
NOTE
When replacing batteries, always use new
batteries from the same production batch.
When storing the battery modules, observe
the latest startup date and recharge, if
necessary. The batteries may only be
recharged in an uninterruptible power supply.
The switch to energy storage is done according to the UPSBAT/VRLA/24DC/3.4AH example:
1. Set the rotary selector switch to Service.
2. Press the locking lugs on the housing top and open the
front cover of the housing.
3. Remove the fuses (see figure: Removing fuse).
4. Remove the cabling of the battery blocks.
5. Remove the batteries.
6. Install the new batteries.
7. Connect the cabling of the battery blocks.
8. Install the fuses (see figure: Inserting fuse).
9. Close the front cover until the locking lugs snap into the
top.
10. Secure the housing to prevent it from being opened.
11. Exit Service mode.
12. Set the buffer time or PC mode.
Figure 28
107432_en_02
Figure 29
Insert fuse
Notes on disposal
Do not dispose of the UPS and battery
modules in household waste! They should be
disposed of according to the currently
applicable national regulations.
You can return used batteries and
accumulators to Phoenix Contact or the
manufacturer.
Remove fuse
PHOENIX CONTACT 22 / 30
TRIO-UPS-2G/1AC/24DC/10
9.2
Remote
Remote
UIN
UOUT
TRIO DC-UPS
t0
O
DC utpu
24 t
V1
0A
+
2.1
+
2.2
2.3
2.4
2.5
DC
OK
24
-28
V
In
AC pu
10 t
0-2
4
DC
O
Ala K
t.-M rm
od
Re e
a
Re dy
m
o
Ba
t.-S te
tart
SG
nd
Ba
(D Cu
efa sto
ult m
0.5 1 tm
)
2 [max
PC
in
-M
3 ]
od
Ba
Se e
5
t.
rvic
Ba -Mo
e 1 10
t.-C de
5
ha
rge
Ala
rm
P>
Pn
3.1
3.2
3.3
3.4
3.5
3.6
3.7
DC OK
Alarm
Bat.-Mode
Ready
Remote
Bat.-Start
SGnd
3.1
3.2
3.3
3.4
3.5
3.6
3.7
0V
L /+
1.1
N
/1.2
Ba
1.3
tte
ry
24
V
Figure 31
t1
t
t0: remote signal is set in mains operation
t1: no input voltage, output will be switched off
If the Remote signal is set in battery operation, battery
operation is exited immediately. The UPS output is switched
off. This procedure cannot be reversed. The UPS is only
activated once the input voltage is applied.
+
4.1
4.2
Remote
UIN
Figure 30
Signal inputs and outputs
You can use the Remote signal terminal to:
1. Suppress and exit battery operation.
2. Perform controlled shutdown of the PC in battery
operation.
To perform these steps, you must connect the Remote
signal terminal to the SGnd signal terminal.
This sets the UPS internal Remote signal.
1. Remote deactivates battery operation
You can deactivate battery operation using this function.
This function is always active when a buffer time has been
preset.
UOUT
t0
Figure 32
t1
t2
t
t0: no input voltage
t1: remote signal is set in battery operation, output will be
switched off
t2: input voltage restored, output will be switched on
This function is the default setting in PC mode.
In mains operation, the Remote signal is indicated by the
flashing green LED (see Signaling section).
In the event of mains failure, battery operation is not started.
107432_en_02
PHOENIX CONTACT 23 / 30
TRIO-UPS-2G/1AC/24DC/10
If PC Mode operating mode is set, then in this case the PC
shuts down immediately (see section Remote starts
immediate PC shutdown).
2. Remote starts immediate PC shutdown only in
battery operation
You can perform immediate shutdown of the PC when
battery operation is entered via the UPS-CONF
configuration software.
9.4
This setting only applies in PC mode.
The Remote signal is indicated by the flashing green LED
(see Signaling section).
If the Remote signal is set in mains operation, the PC is shut
down when battery operation is entered. The delay time
under Item 1 is skipped (see section PC mode).
Remote
UIN
UOUT
PC
t0
Figure 33
t1
t2
t
t0: remote signal is set in mains operation
t1: no input voltage, PC shutdown begins immediately
t2: the PC has shut down, the output will be switched off
Once the PC has shut down in battery
operation, the uninterruptible power supply
output is switched off. This procedure cannot
be reversed. The uninterruptible power supply
is not activated until the input voltage is
applied.
9.3
Battery start (Bat.-Start)
Software configuration
You can request the current device status via the UPSCONF software. Furthermore, you can change the settings
of certain parameters within a defined value range and reset
them to the default settings. Please refer to the respective
setting options in the following table:
Parameter
Field of application
Connected nominal
battery capacity
Initial charging current
Compensation endof-charge voltage
Conservation end-ofcharge voltage
Temperature
compensation
Signaling threshold of
alarm - maximum
charging time
exceeded
End-of-discharge
voltage
Signaling threshold of
alarm - battery voltage
Continuous signaling
after battery discharge
Continuous signaling
after timeout
Value range
1.3 ... 140 Ah
Default setting
/
7,2 Ah
0.2 ... 3 A
25 ... 30 V DC
2 A
28 V DC
25 ... 30 V DC
27.6 V DC
-200 ... 0 mV/K
-42 mV/K
4 ... 200 h
18 h
18 ... 24 V DC
19.2 V DC
18 ... 30 V
20.4 V DC
0 ... 600 min
10 min
0 ... 600 min
10 min
In addition to parameter setting options, the software also
features setting options for signaling, for communication
parameters, and for the remote contact.
You can use the Bat.-Start signal terminal to start the UPS
without supply voltage on the input side and create an
autonomous supply for the load. To do this, you must
connect the Bat.-Start signal terminal to the SGnd signal
terminal.
The output voltage provided at the load matches the battery
voltage.
The maximum duration of the autonomous supply for the
load depends on the charging state of the battery.
The signaling corresponds to the signaling for battery
operation (see Signaling section).
To exit autonomous operation, you must disconnect the
Bat.-Start signal terminal and the SGnd signal terminal.
107432_en_02
PHOENIX CONTACT 24 / 30
TRIO-UPS-2G/1AC/24DC/10
Method of operation
10.1
Output characteristic curve
was prior to time point t1. If the request to supply the load still
exists when the time intervals t2 to t3 have expired (at least
4 * tBoost), a new cyclical switching of the dynamic power
reserve occurs, to a total of 70%.
UOUT [V]
The uninterruptible power supply works with a dynamic
power reserve – the dynamic boost – in accordance with the
U/I characteristic curve shown in the illustration. In the event
of a secondary-side short circuit or overload, the output
current is limited to 1.5 x IN. The device does not switch off,
but instead continues to supply the output current. The
secondary voltage is then reduced until the short circuit is
eliminated. The U/I characteristic curve with the dynamic
power reserve makes it possible to provide high switch-on
currents of capacitive loads or inductive loads reliably.
IOUT [A]
10
Idyn. Boost
100%
80%
dyn. Boost
t1
Figure 35
t ≥5 s
UN
5s
t2
20s
t3
5s
t4
20s
...
t5
t [s]
Schematic diagram of dynamic boost behavior
U < 0,9 x UN
The permanent output power PN is limited at
an ambient temperature of 60 °C. Observe all
the maximum output powers for the
respective operating conditions.
IN
1,5 x IN
IOUT [A]
Figure 34
–
–
–
–
–
U/I characteristic curve with dynamic load
reserve
UN = 24 V
IN = 10 A
Idyn. BOOST = 15 A
PN = 240 W
Pdyn. BOOST = 360 W
10.2
Dynamic Boost
The following example is used to explain how the
uninterruptible power supply dynamic boost functions.
Example:
The uninterruptible power supply supplies a connected
base load of 80% until time point t1 (see illustration,
schematic diagram of the dynamic boost behavior). If an
additional load is activated while the device is in operation,
the dynamic boost is requested for the period of time t1 to t2.
The uninterruptible power supply provides the maximum
dynamic power reserve of an additional
70% (ΔPdyn. boost = 1.5 x IN x UN - P initial load).
11
Battery management
The TRIO-UPS battery management is divided into two tests
that are performed cyclically during normal operation.
11.1
Battery presence test
The battery presence test is used to detect whether a
correctly installed battery is present. If this is not the case,
the test fails and the green and red LED control lamps come
on and stay on.
11.2
Quality check of battery
The battery quality test is a life cycle test.
When the maximum charging time has been exceeded,
conclusions can be drawn regarding the maximum service
life of the battery, for example. If an event arises, the green
and red LED control lamps come on and stay on.
11.3
Battery charging
The device has a maximum charging current of 3 A.
Refer to the following table for the times required to recharge
a fully discharged battery.
As such, the requested overall total power corresponds to
150% of the nominal power. This power can be accessed for
at least 5 s in the event that the output voltage remains the
same. On reaching time point t2, the dynamic boost is once
more returned to the output value of the base load for
thermal offloading of the uninterruptible power supply. In this
case, the base load amounts to the same value of 80%, as it
107432_en_02
PHOENIX CONTACT 25 / 30
TRIO-UPS-2G/1AC/24DC/10
Battery
2320296
UPS-BAT/VRLA/
24DC/ 1.3AH
UPS-BAT/VRLA/
24DC/3.4AH
UPS-BAT/VRLA/
24DC/7.2AH
UPS-BAT/VRLA/
24DC/12AH
UPS-BAT/VRLA/
24DC/38AH
2320319
2320322
2320335
Output
DC
+ -
07:00
15:30
DC OK
O
DC utpu
24 t
V1
0A
+
2.1
+
2.2
2.3
2.4
2.5
DC
O
Ala K
t.-M rm
od
Re e
a
Re dy
Ba mote
t.-S
tart
SG
nd
Ba
(D Cu
efa sto
ult m
0.5 1 tm
)
2 [max
PC
in
-M
3 ]
DC
OK
24
-28
V
In
AC pu
10 t
0-2
4
3.1
3.2
3.3
3.4
3.5
3.6
3.7
od
Ba
Se e
5
t.
rvic
Ba -Mo
e 1 10
t.-C de
5
ha
rge
Ala
rm
P>
Pn
Bat.-Mode
Bat.-Charge
Alarm
P>Pn
0V
L /+
1.1
N
/1.2
Ba
tte
ry
1.3
24
V
+
4.1
4.2
Figure 37
LED indicators
PSU
Energy storage
Battery
DC
+ -
+ -
Output
DC
+ -
Input
AC
L N
Buffered
DC load
Figure 36
Various LED indicators are available for visual function
monitoring of uninterruptible power supplies. Moreover,
active signal outputs can be used to forward this data to a
higher-level control system.
05:30
You can support the main charging operation by connecting
an additional power supply unit to the battery in parallel to
the UPS. This can speed up the changing process by as
much as 30%. If you use this procedure, note the following:
– The output voltage of the additional power supply unit
must be less than the minimum float charge end
voltage. When using Phoenix Contact VRLA batteries,
they should be set to 26.5 V (measured at the battery
connection terminal block, without load)
– The aggregate charging current may not exceed the
maximum permissible charging current for the battery
– To prevent any current from flowing back into the power
supply unit, install a diode decoupling module
Input
AC
L N
Signaling
05:00
Note: The actual charging times may deviate
from the information provided in the table, e.g.
due to ambient temperature differences.
TRIO
DC-UPS
12
Schematic design - charging the battery with
additional power supply unit
TRIO DC-UPS
2320306
Recharging times
[hr.], [TA = 25 °C,
Icmax]
04:00
TRIO DC-UPS
Order
No.
O
DC utpu
24 t
V1
0A
+
2.1
+
2.2
2.3
2.4
2.5
DC
OK
24
-28
V
In
AC pu
10 t
0-2
4
DC
O
Ala K
t.-M rm
od
Re e
a
Re dy
Ba mote
t.-S
tart
SG
nd
Ba
3.1
3.2
3.3
3.4
3.5
3.6
3.7
(D Cu
efa sto
ult m
0.5 1 tm
)
2 [max
PC
in
-M
3 ]
od
Ba
Se e
5
t.
rvic
Ba -Mo
e 1 10
t.-C de
5
ha
rge
Ala
rm
P>
Pn
DC OK
Alarm
Bat.-Mode
Ready
Remote
Bat.-Start
SGnd
3.1
3.2
3.3
3.4
3.5
3.6
3.7
0V
L /+
1.1
N
/1.2
1.3
Ba
tte
ry
24
V
+
4.1
4.2
Figure 38
107432_en_02
Signal inputs and outputs
PHOENIX CONTACT 26 / 30
TRIO-UPS-2G/1AC/24DC/10
12.1
LED indicators and signal outputs
For UPS signaling and the corresponding states, please
refer to the table below.
Switching output
Status LED
Green
Yellow
Note
Bat.-Mode
Ready
Alarm
(active low)
low
low
low
Device off
low or high
low
high
Initialization, LED test (~2 sec.) / battery operation,
battery failure
low
high
high
Mains operation, battery is fully charged
low
low or high
high
Mains operation, battery charging in process
high
low
high
Battery mode
low
low
low
Mains operation, battery failure
low
low
low
Mains operation, service mode for battery change
low
high
high
Mains operation, battery is fully charged, remote
contact is shortet to SGnd
high
low
high
Mains operation, battery charging in process,
remote contact is shortet to SGnd
low
low
low
Mains operation, battery failure, remote contact is
shortet to SGnd
D = 50%
low
low
low
Mains operation, service mode for battery change,
remote contact is shortet to SGnd
D = 90%
low
high
high
Overload in mains operation, battery is fully charged
high
low
low
Battery operation, battery failure
low
low
high
Overload in battery operation
low
high
high
Signaling time after cut off in battery mode
Red
D = 50%
D = 50%
D = 50%
D = 90%
D = 90%
D = 10%
D = 10%
LED flashing
LED on
LED off
D = 50%
D = 90%
100%
Figure 39
107432_en_02
t
Signal states
PHOENIX CONTACT 27 / 30
TRIO-UPS-2G/1AC/24DC/10
12.2
Signal outputs
12.3
Signal inputs
DC OK
Remote
If the output voltage is in the valid range (>90% of the
nominal output voltage), the signal output is active.
You can activate and trigger various functions using the
remote signal input. For additional information, please refer
to the "Remote device operation" section.
A digital transistor output is available as a signal contact.
This signal is indicated visually by a green LED.
The signal status can be inverted using the UPS-CONF
configuration software.
Alarm
A change made to the remote function using
the UPS-CONF configuration software is not
applied until a corresponding status change of
the remote signal input or device restart has
been carried out.
In the event of an alarm, the signal output is active (low
level). The signal status can be inverted via the UPS-CONF
configuration software.
A digital transistor output is available as a signal contact.
This signal is indicated visually by a red LED.
Possible alarms include:
– Overload
– Battery fault
– Service mode active
Bat.-Mode
Bat.-Start
You can use the Bat.-Start signal terminal to start the UPS
without supply voltage on the input side and create an
autonomous supply for the load.
For additional information, please refer to the section
"Device operation, battery start".
If the connected load is being supplied by the battery, the
signal output is active. The signal status can be inverted via
the UPS-CONF configuration software.
A digital transistor output is available as a signal contact.
This signal is indicated visually by a yellow LED.
You can assign other additional information to this signal
output using the UPS-CONF configuration software.
Ready
When the connected energy storage system is fully
charged, the signal output is active. The signal status can be
inverted via the UPS-CONF configuration software.
A digital transistor output is available as a signal contact.
You can assign other additional information to this signal
output using the UPS-CONF configuration software.
107432_en_02
PHOENIX CONTACT 28 / 30
TRIO-UPS-2G/1AC/24DC/10
13
Interface
14
Derating
13.1
USB interface MINI type B
14.1
Ambient temperature
The uninterruptible power supply is equipped with a USB
Mini type B interface for data transmission.
+
2.1
+
2.2
2.3
DC
24
OK
-28
DC
O
A K
Ba larm
t.-M
od
Re e
a
Re dy
Ba mote
t.-S
tart
SG
nd
2.4
2.5
O
DC utpu
24 t
V1
0A
V
In
AC pu
10 t
0-2
4
IOUT [A]
TRIO DC-UPS
A data cable is required for communicating with a PC or a
higher-level controller.
The device provides both the IN nominal output current and
the Idyn. BOOST dynamic output current at ambient
temperatures up to +60 °C. For ambient temperatures
above +60°C, the ambient power must be decreased by
2.5% per Kelvin increase in temperature. For ambient
temperatures above +70°C or in the event of a thermal
overload, the device does not switch off. The output power
will be decreased by enough to allow device protection.
Once the device has cooled down, the output power will be
increased again.
1,5 x IN
3.1
3.2
3.3
3.4
3.5
3.6
dyn. Boost
3.7
(D Cu
efa sto
ult m
0.5 1 tm
)
2 [max
PC
in
-M
3 ]
od
Ba
Se e
5
t.
rvic
Ba -Mo
e 1 10
t.-C de
5
t ≥5 s
IN
ha
rge
Ala
rm
P>
Pn
0V
L /+
1.1
N
/1.2
Ba
tte
1.3
ry
24
V
+
4.1
0
-25
4.2
Figure 42
14.2
USB interface MINI type B (bottom of device)
13.1.1 MINI-SCREW-USB-DATACABLE
The uninterruptible power supply unit is connected to the
USB PC connection with data cable MINI-SCREW-USBDATACABLE (Order No. 2908217) via USB interface mini
type B.
2
3
40
60
Temperature-dependent derating
Installation height
200
175
150
125
100
75
50
25
0
= PN 100 % 60 °C
= PDyn. 150 % 60 °C
0
1000
2000
3000
1
Figure 41
No.
1
2
3
MINI-SCREW-USB-DATACABLE
[°C]
The uninterruptible power supply can be operated at an
installation height of up to 2000 m without any limitations.
Different data applies for installation locations above
2000 m due to the differing air pressure and the reduced
convection cooling associated with this.
POut [%]
Figure 40
20
4000
5000
H [m]
Figure 43
Altitude-dependent derating
Designation
Mini type B USB connector with screw connection
USB plug type A
Cable length: 3 m
107432_en_02
PHOENIX CONTACT 29 / 30
TRIO-UPS-2G/1AC/24DC/10
15
15.2
Parallel operation
Devices of the same type can be connected in parallel to
increase both redundancy and power. No further
adjustments to the default setting are necessary.
To ensure symmetrical current distribution, we recommend
that all cable connections from the power supply unit to the
busbar are the same length, and have the same conductor
cross-section.
Depending on the system, a protective circuit should be
installed at each individual device output (e.g. decoupling
diode or DC fuse) for parallel connection of more than two
devices. This prevents high return currents in the event of a
secondary device fault.
15.1
Increasing power
When two uninterruptible power supplies are connected in
parallel, the output current is increased to 2 x IN. Parallel
connection for increased power is used when extending
existing systems. If the individual uninterruptible power
supply does not cover the current consumption of the most
powerful load, parallel connection of uninterruptible power
supplies is recommended.
To increase performance, it is imperative that
both UPS devices be supplied from the same
energy storage system.
Redundant operation
Redundant circuits are suitable for supplying systems which
place particularly high demands on operational reliability. If
a fault occurs in the primary circuit of the first uninterruptible
power supply unit, the second device automatically takes
over the complete power supply without interruption, and
vice versa. For this purpose, the power supply units to be
connected in parallel must be large enough to ensure that
the total current requirements of all loads can be fully met by
one power supply unit. External decoupling diodes or
ORING modules are required for 100 % redundancy.
+
+
-
-
IN
+
+
-
IN
IN
+
–
+
Figure 46
IN
+
–
–
Σ = 2 x IN
Performance increase with decoupling via
diode module
+
+
-
IN
IN
+
–
Σ = IN
+ –
Figure 44
Redundancy operation with decoupling via
diode module
+
Figure 47
+
+
-
-
IN
–
Σ = 2 x IN
Performance increase with decoupling via
ORING module
IN
+
–
+ –
Figure 45
107432_en_02
Σ = IN
Redundancy operation with decoupling via
ORING module
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
phoenixcontact.com
30 / 30