Data sheet
3RV2111-1HA10
Circuit breaker size S00 for motor protection, CLASS 10 with overload relay
function A-release 5.5...8 A N-release 104 A screw terminal Standard
switching capacity
product brand name
SIRIUS
product designation
Circuit breaker
design of the product
For motor protection with overload relay function
product type designation
3RV2
General technical data
size of the circuit-breaker
S00
size of contactor can be combined company-specific
S00, S0
product extension auxiliary switch
Yes
power loss [W] for rated value of the current
● at AC in hot operating state
9.25 W
● at AC in hot operating state per pole
3.1 W
insulation voltage with degree of pollution 3 at AC rated
value
690 V
surge voltage resistance rated value
6 kV
shock resistance according to IEC 60068-2-27
25g / 11 ms
mechanical service life (switching cycles)
● of the main contacts typical
100 000
● of auxiliary contacts typical
100 000
electrical endurance (switching cycles) typical
100 000
reference code according to IEC 81346-2
Q
Substance Prohibitance (Date)
10/01/2009
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
ambient temperature
● during operation
-20 ... +60 °C
● during storage
-50 ... +80 °C
● during transport
-50 ... +80 °C
relative humidity during operation
10 ... 95 %
Main circuit
number of poles for main current circuit
3
adjustable current response value current of the
current-dependent overload release
5.5 ... 8 A
operating voltage
● rated value
20 ... 690 V
● at AC-3 rated value maximum
690 V
● at AC-3e rated value maximum
690 V
operating frequency rated value
50 ... 60 Hz
operational current rated value
8A
operational current
● at AC-3 at 400 V rated value
3RV21111HA10
Page 1/5
8A
7/4/2022
Subject to change without notice
© Copyright Siemens
● at AC-3e at 400 V rated value
8A
operating power
● at AC-3
— at 230 V rated value
1.5 kW
— at 400 V rated value
3 kW
— at 500 V rated value
4 kW
— at 690 V rated value
5.5 kW
● at AC-3e
— at 230 V rated value
1.5 kW
— at 400 V rated value
3 kW
— at 500 V rated value
4 kW
— at 690 V rated value
5.5 kW
operating frequency
● at AC-3 maximum
15 1/h
● at AC-3e maximum
15 1/h
Auxiliary circuit
design of the auxiliary switch
laterally
number of NC contacts for auxiliary contacts
0
number of NO contacts for auxiliary contacts
0
number of CO contacts for auxiliary contacts
0
operational current of auxiliary contacts at AC-15
● at 24 V
1.5 A
● at 230 V
1.5 A
operational current of auxiliary contacts at DC-13
● at 24 V
1A
Protective and monitoring functions
product function
● ground fault detection
No
● phase failure detection
Yes
trip class
CLASS 10
design of the overload release
thermal
breaking capacity maximum short-circuit current (Icu)
● at AC at 240 V rated value
100 kA
● at AC at 400 V rated value
100 kA
● at AC at 500 V rated value
42 kA
● at AC at 690 V rated value
6 kA
breaking capacity operating short-circuit current (Ics)
at AC
● at 240 V rated value
100 kA
● at 400 V rated value
100 kA
● at 500 V rated value
42 kA
● at 690 V rated value
4 kA
response value current of instantaneous short-circuit trip
unit
104 A
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value
8A
● at 600 V rated value
8A
yielded mechanical performance [hp]
● for single-phase AC motor
— at 110/120 V rated value
0.33 hp
— at 230 V rated value
1 hp
● for 3-phase AC motor
— at 200/208 V rated value
2 hp
— at 220/230 V rated value
2 hp
— at 460/480 V rated value
5 hp
— at 575/600 V rated value
5 hp
contact rating of auxiliary contacts according to UL
C600 / R300
Short-circuit protection
product function short circuit protection
3RV21111HA10
Page 2/5
Yes
7/4/2022
Subject to change without notice
© Copyright Siemens
design of the short-circuit trip
magnetic
design of the fuse link
● for short-circuit protection of the auxiliary switch
required
fuse gL/gG: 6 A, quick: 10 A
design of the fuse link for IT network for short-circuit
protection of the main circuit
● at 400 V
gL/gG 50 A
● at 500 V
gL/gG 40 A
● at 690 V
gL/gG 35 A
Installation/ mounting/ dimensions
mounting position
any
fastening method
screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 60715
height
97 mm
width
65 mm
depth
97 mm
required spacing
● for grounded parts at 400 V
— downwards
30 mm
— upwards
30 mm
— at the side
9 mm
● for live parts at 400 V
— downwards
30 mm
— upwards
30 mm
— at the side
9 mm
● for grounded parts at 500 V
— downwards
30 mm
— upwards
30 mm
— at the side
9 mm
● for live parts at 500 V
— downwards
30 mm
— upwards
30 mm
— at the side
9 mm
● for grounded parts at 690 V
— downwards
50 mm
— upwards
50 mm
— backwards
0 mm
— at the side
30 mm
— forwards
0 mm
● for live parts at 690 V
— downwards
50 mm
— upwards
50 mm
— backwards
0 mm
— at the side
30 mm
— forwards
0 mm
Connections/ Terminals
type of electrical connection
● for main current circuit
screw-type terminals
● for auxiliary and control circuit
screw-type terminals
arrangement of electrical connectors for main current
circuit
Top and bottom
type of connectable conductor cross-sections
● for main contacts
— solid or stranded
2x (0,75 ... 2,5 mm²), 2x 4 mm²
— finely stranded with core end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● at AWG cables for main contacts
2x (18 ... 14), 2x 12
type of connectable conductor cross-sections
● for auxiliary contacts
— solid or stranded
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
— finely stranded with core end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● at AWG cables for auxiliary contacts
3RV21111HA10
Page 3/5
2x (20 ... 16), 2x (18 ... 14)
7/4/2022
Subject to change without notice
© Copyright Siemens
tightening torque
● for main contacts with screw-type terminals
0.8 ... 1.2 N·m
● for auxiliary contacts with screw-type terminals
0.8 ... 1.2 N·m
design of screwdriver shaft
Diameter 5 to 6 mm
size of the screwdriver tip
Pozidriv size 2
design of the thread of the connection screw
● for main contacts
M3
● of the auxiliary and control contacts
M3
Safety related data
B10 value
● with high demand rate according to SN 31920
5 000
proportion of dangerous failures
● with low demand rate according to SN 31920
50 %
● with high demand rate according to SN 31920
50 %
failure rate [FIT]
● with low demand rate according to SN 31920
50 FIT
T1 value for proof test interval or service life according to
IEC 61508
10 y
protection class IP on the front according to IEC
60529
IP20
touch protection on the front according to IEC 60529
finger-safe, for vertical contact from the front
display version for switching status
Handle
Certificates/ approvals
General Product Approval
Declaration of Conformity
Confirmation
KC
Test Certificates
Marine / Shipping
Type Test Certificates/Test Report
Special Test Certificate
Marine / Shipping
other
Confirmation
other
Railway
Vibration and Shock
Confirmation
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RV2111-1HA10
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RV2111-1HA10
3RV21111HA10
Page 4/5
7/4/2022
Subject to change without notice
© Copyright Siemens
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RV2111-1HA10
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RV2111-1HA10&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RV2111-1HA10/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RV2111-1HA10&objecttype=14&gridview=view1
last modified:
3RV21111HA10
Page 5/5
6/25/2022
7/4/2022
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“3RV2111-1HA10”相匹配的价格&库存,您可以联系我们找货
免费人工找货