Data sheet
3RV2711-4AD10
Circuit breaker size S00 for system protection with approval circuit breaker
UL 489, CSA C22.2 No.5-02 A-release 15 A N-release 208 A screw
terminal Standard switching capacity
product brand name
SIRIUS
product designation
Circuit breaker
design of the product
For system protection according to UL 489/CSA C22.2 No. 5
product type designation
3RV2
General technical data
size of the circuit-breaker
S00
product extension auxiliary switch
Yes
power loss [W] for rated value of the current
● at AC in hot operating state
9.25 W
● at AC in hot operating state per pole
3.1 W
insulation voltage with degree of pollution 3 at AC rated
value
690 V
surge voltage resistance rated value
6 kV
shock resistance according to IEC 60068-2-27
25g / 11 ms
mechanical service life (switching cycles)
● of the main contacts typical
100 000
● of auxiliary contacts typical
100 000
electrical endurance (switching cycles) typical
100 000
reference code according to IEC 81346-2
Q
Substance Prohibitance (Date)
10/01/2009
Ambient conditions
installation altitude at height above sea level maximum
2 000 m
ambient temperature
● during operation
-20 ... +60 °C
● during storage
-50 ... +80 °C
● during transport
-50 ... +80 °C
relative humidity during operation
10 ... 95 %
Main circuit
number of poles for main current circuit
3
operating voltage
● rated value
20 ... 690 V
● at AC-3 rated value maximum
690 V
● at AC-3e rated value maximum
690 V
operating frequency rated value
50 ... 60 Hz
operational current rated value
15 A
operational current
● at AC-3 at 400 V rated value
15 A
● at AC-3e at 400 V rated value
15 A
operating power
3RV27114AD10
Page 1/4
7/6/2022
Subject to change without notice
© Copyright Siemens
● at AC-3
— at 230 V rated value
4 kW
— at 400 V rated value
7.5 kW
— at 500 V rated value
7.5 kW
— at 690 V rated value
11 kW
● at AC-3e
— at 230 V rated value
4 kW
— at 400 V rated value
7.5 kW
— at 500 V rated value
7.5 kW
— at 690 V rated value
11 kW
operating frequency
● at AC-3 maximum
15 1/h
● at AC-3e maximum
15 1/h
Auxiliary circuit
number of NC contacts for auxiliary contacts
0
number of NO contacts for auxiliary contacts
0
number of CO contacts for auxiliary contacts
0
Protective and monitoring functions
product function
● ground fault detection
No
● phase failure detection
No
design of the overload release
thermal
breaking capacity maximum short-circuit current (Icu)
● at AC at 240 V rated value
100 kA
● at AC at 400 V rated value
55 kA
● at AC at 500 V rated value
10 kA
● at AC at 690 V rated value
4 kA
● at 480 AC Y/277 V according to UL 489 rated value
65 kA
breaking capacity operating short-circuit current (Ics)
at AC
● at 240 V rated value
100 kA
● at 400 V rated value
30 kA
● at 500 V rated value
5 kA
● at 690 V rated value
2 kA
response value current of instantaneous short-circuit trip
unit
208 A
Short-circuit protection
product function short circuit protection
Yes
design of the short-circuit trip
magnetic
design of the fuse link for IT network for short-circuit
protection of the main circuit
● at 240 V
gG 80 A
● at 400 V
gG 63 A
● at 500 V
gG 50 A
● at 690 V
gG 40 A
Installation/ mounting/ dimensions
mounting position
any
fastening method
screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 60715
height
144 mm
width
45 mm
depth
97 mm
required spacing
● for grounded parts at 400 V
— downwards
30 mm
— upwards
30 mm
— at the side
30 mm
● for live parts at 400 V
— downwards
30 mm
— upwards
30 mm
3RV27114AD10
Page 2/4
7/6/2022
Subject to change without notice
© Copyright Siemens
— at the side
30 mm
● for grounded parts at 500 V
— downwards
30 mm
— upwards
30 mm
— at the side
30 mm
● for live parts at 500 V
— downwards
30 mm
— upwards
30 mm
— at the side
30 mm
● for grounded parts at 690 V
— downwards
70 mm
— upwards
70 mm
— backwards
0 mm
— at the side
30 mm
— forwards
0 mm
● for live parts at 690 V
— downwards
70 mm
— upwards
70 mm
— backwards
0 mm
— at the side
30 mm
— forwards
0 mm
Connections/ Terminals
type of electrical connection
● for main current circuit
screw-type terminals
arrangement of electrical connectors for main current
circuit
Top and bottom
type of connectable conductor cross-sections
● for main contacts
— solid or stranded
1 ... 10 mm², max. 2x 10 mm²
— finely stranded with core end processing
1 ... 16 mm², max. 6 + 16 mm²
● at AWG cables for main contacts
2x (14 ... 10)
tightening torque
● for main contacts with screw-type terminals
2.5 ... 3 N·m
design of screwdriver shaft
Diameter 5 to 6 mm
size of the screwdriver tip
Pozidriv size 2
design of the thread of the connection screw
● for main contacts
M4
Safety related data
B10 value
● with high demand rate according to SN 31920
5 000
proportion of dangerous failures
● with low demand rate according to SN 31920
50 %
● with high demand rate according to SN 31920
50 %
failure rate [FIT]
● with low demand rate according to SN 31920
50 FIT
T1 value for proof test interval or service life according to
IEC 61508
10 y
protection class IP on the front according to IEC
60529
IP20
touch protection on the front according to IEC 60529
finger-safe, for vertical contact from the front
display version for switching status
Handle
Certificates/ approvals
General Product Approval
Confirmation
3RV27114AD10
Page 3/4
7/6/2022
KC
Subject to change without notice
© Copyright Siemens
Declaration of Conformity
Test Certificates
Type Test Certificates/Test Report
Marine / Shipping
other
Confirmation
Marine / Shipping
Special Test Certificate
Railway
Vibration and Shock
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RV2711-4AD10
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RV2711-4AD10
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RV2711-4AD10
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RV2711-4AD10&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RV2711-4AD10/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RV2711-4AD10&objecttype=14&gridview=view1
last modified:
3RV27114AD10
Page 4/4
6/25/2022
7/6/2022
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“3RV27114AD10”相匹配的价格&库存,您可以联系我们找货