Data sheet
6EP1433-2BA20
SITOP PSU300S/3AC/24VDC/5A
SITOP PSU300S 24 V/5 A Stabilized power supply input: 400-500 V 3 AC
output: 24 V DC/5 A *Ex approval no longer available*
Input
type of the power supply network
3-phase AC
supply voltage at AC
● minimum rated value
400 V
● maximum rated value
500 V
● initial value
340 V
● full-scale value
550 V
design of input wide range input
Yes
operating condition of the mains buffering
at Vin = 400 V
buffering time for rated value of the output current in the
event of power failure minimum
18 ms
operating condition of the mains buffering
at Vin = 400 V
line frequency
● 1 rated value
50 Hz
● 2 rated value
60 Hz
line frequency
47 ... 63 Hz
input current
● at rated input voltage 400 V
0.45 A
● at rated input voltage 500 V
0.4 A
current limitation of inrush current at 25 °C maximum
20 A
I2t value maximum
0.5 A²·s
fuse protection type
none
● in the feeder
Required: 3-pole connected miniature circuit breaker 3 ... 16 A
characteristic C or circuit breaker 3RV2011-1DA10 (setting 3 A) or
3RV2711-1DD10 (UL 489-listed, DIVQ)
Output
voltage curve at output
Controlled, isolated DC voltage
output voltage at DC rated value
24 V
output voltage
● at output 1 at DC rated value
24 V
relative overall tolerance of the voltage
3%
relative control precision of the output voltage
● on slow fluctuation of input voltage
0.1 %
● on slow fluctuation of ohm loading
0.1 %
residual ripple
● maximum
200 mV
voltage peak
● maximum
240 mV
adjustable output voltage
24 ... 28 V
product function output voltage adjustable
Yes
6EP14332BA20
Page 1/3
7/4/2022
Subject to change without notice
© Copyright Siemens
type of output voltage setting
via potentiometer; max. 120 W
display version for normal operation
Green LED for 24 V OK
type of signal at output
Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK"
behavior of the output voltage when switching on
Overshoot of Vout < 5 %
response delay maximum
1.5 s
voltage increase time of the output voltage
● typical
60 ms
● maximum
500 ms
output current
● rated value
5A
● rated range
0 ... 5 A; 6 A up to +45°C; +60 ... +70 °C: Derating 5%/K
supplied active power typical
120 W
product feature
● bridging of equipment
number of parallel-switched equipment resources for
increasing the power
Yes
2
Efficiency
efficiency in percent
89.5 %
power loss [W]
● at rated output voltage for rated value of the output
current typical
14 W
Closed-loop control
relative control precision of the output voltage with rapid
fluctuation of the input voltage by +/- 15% typical
1%
relative control precision of the output voltage load step of
resistive load 50/100/50 % typical
1%
setting time
● load step 50 to 100% typical
3 ms
● load step 100 to 50% typical
3 ms
relative control precision of the output voltage at load step
of resistive load 10/90/10 % typical
3%
setting time
● load step 10 to 90% typical
4 ms
● load step 90 to 10% typical
4 ms
● maximum
10 ms
Protection and monitoring
design of the overvoltage protection
protection against overvoltage in case of internal fault Vout < 35 V
response value current limitation typical
6.6 A
property of the output short-circuit proof
Yes
design of short-circuit protection
Constant current characteristic
enduring short circuit current RMS value
● maximum
overcurrent overload capability in normal operation
8A
overload capability 150 % Iout rated up to 5 s/min
Safety
galvanic isolation between input and output
Yes
galvanic isolation
Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178,
transformer acc. to EN 61558-2-16
operating resource protection class
Class I
protection class IP
IP20
Approvals
certificate of suitability
● CE marking
Yes
● UL approval
Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259;
cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
● CSA approval
Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259;
cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
● cCSAus, Class 1, Division 2
No
● ATEX
No
certificate of suitability
● IECEx
No
● NEC Class 2
No
6EP14332BA20
Page 2/3
7/4/2022
Subject to change without notice
© Copyright Siemens
● ULhazloc approval
No
● FM registration
No
type of certification CB-certificate
Yes
certificate of suitability
● EAC approval
Yes
● C-Tick
Yes
certificate of suitability shipbuilding approval
Yes
shipbuilding approval
ABS, DNV GL
Marine classification association
● American Bureau of Shipping Europe Ltd. (ABS)
Yes
● French marine classification society (BV)
No
● DNV GL
Yes
● Lloyds Register of Shipping (LRS)
No
● Nippon Kaiji Kyokai (NK)
No
EMC
standard
● for emitted interference
EN 55022 Class B
● for mains harmonics limitation
EN 61000-3-2
● for interference immunity
EN 61000-6-2
environmental conditions
ambient temperature
● during operation
-25 ... +70 °C; with natural convection
● during transport
-40 ... +85 °C
● during storage
-40 ... +85 °C
environmental category according to IEC 60721
Climate class 3K3, 5 … 95% no condensation
Mechanics
type of electrical connection
screw-type terminals
● at input
L1, L2, L3, PE: 1 screw terminal each for 0.05 ... 2.5 mm² singlecore/finely stranded
● at output
+, -: 2 screw terminals each for 0.2 ... 2.5 mm²
● for auxiliary contacts
13, 14 (alarm signal): 1 screw terminal each for 0.2 ... 2.5 mm²
width of the enclosure
50 mm
height of the enclosure
125 mm
depth of the enclosure
120 mm
net weight
0.5 kg
product feature of the enclosure housing can be lined up
Yes
fastening method
Snaps onto DIN rail EN 60715 35x7.5/15
electrical accessories
Redundancy module, buffer module, selectivity module, DC UPS
mechanical accessories
Device identification label 20 mm × 7 mm, pale turquoise 3RT19001SB20
MTBF at 40 °C
500 000 h
other information
Specifications at rated input voltage and ambient temperature +25 °C
(unless otherwise specified)
6EP14332BA20
Page 3/3
7/4/2022
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“6EP14332BA20”相匹配的价格&库存,您可以联系我们找货