Data sheet
6EP7133-6AE00-0BN0
SIMATIC ET 200SP PS/1AC/24VDC/10A
SIMATIC ET 200SP PS 24V/10A
Stabilized power supply Input:
120/230 V AC Output: 24 V
DC/10 A
Input
Input
● Note
1-phase AC
Automatic range selection
supply voltage
● 1 at AC rated value
120 V
● 2 at AC rated value
230 V
input voltage
● 1 at AC
85 ... 132 V
● 2 at AC
170 ... 264 V
Wide-range input
No
Overvoltage resistance
2.3 × Vin rated, 1.3 ms
Mains buffering
at Vin = 93/187 V
Mains buffering at Iout rated, min.
20 ms; at Vin = 93/187 V
Rated line frequency 1
50 Hz
Rated line frequency 2
60 Hz
Rated line range
47 ... 63 Hz
input current
● at rated input voltage 120 V
4.34 A
● at rated input voltage 230 V
1.92 A
Switch-on current limiting (+25 °C), max.
60 A
I²t, max.
6.3 A²·s
Built-in incoming fuse
T 6.3 A/250 V (not accessible)
Protection in the mains power input (IEC 898)
recommended LS switch: B/C 10 A/6 A
Output
Output
Controlled, isolated DC voltage
Rated voltage Vout DC
24 V
Total tolerance, static ±
3%
Static mains compensation, approx.
0.1 %
Static load balancing, approx.
1%
Residual ripple peak-peak, max.
150 mV
Residual ripple peak-peak, typ.
50 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)
240 mV
Spikes peak-peak, typ. (bandwidth: 20 MHz)
150 mV
Adjustment range
22.8 ... 28 V
6EP71336AE000BN0
Page 1/2
12.18.2020
Subject to change without notice
© Copyright Siemens
product function output voltage adjustable
Yes
Output voltage setting
via potentiometer
Status display
Green LED for 24 V OK
Signaling
Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK"
On/off behavior
Overshoot of Vout < 3 %
Startup delay, max.
0.3 s
Voltage rise, typ.
30 ms
Rated current value Iout rated
10 A
Current range
0 ... 12 A
● Note
supplied active power typical
10 A up to +60°C; +60 ... +70 °C: Derating 3%/K
240 W
short-term overload current
● on short-circuiting during the start-up typical
30 A
● at short-circuit during operation typical
30 A
duration of overloading capability for excess current
● on short-circuiting during the start-up
750 ms
● at short-circuit during operation
800 ms
Parallel switching for enhanced performance
Yes
Numbers of parallel switchable units for enhanced
performance
2
Efficiency
Efficiency at Vout rated, Iout rated, approx.
90 %
Power loss at Vout rated, Iout rated, approx.
26 W
power loss [W] during no-load operation maximum
2.8 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %), max.
0.3 %
Dynamic load smoothing (Iout: 10/90/10 %), Uout ± typ.
3%
Load step setting time 10 to 90%, typ.
1 ms
Load step setting time 90 to 10%, typ.
1 ms
Protection and monitoring
Output overvoltage protection
protection against overvoltage in case of internal fault Vout < 31.8 V
Current limitation
14 ... 15 A
property of the output short-circuit proof
Yes
Short-circuit protection
Constant current characteristic
enduring short circuit current RMS value
● typical
14.1 A
overcurrent overload capability in normal operation
overload capability 150 % Iout rated up to 5 s/min
Overload/short-circuit indicator
-
Safety
Primary/secondary isolation
Yes
galvanic isolation
Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
Protection class
Class I
leakage current
● maximum
3.5 mA
● typical
1 mA
Degree of protection (EN 60529)
IP20
Approvals
CE mark
Yes
UL/cUL (CSA) approval
cULus-Listed (UL61010-2-201, CSA C22.2 No.142), cCSAus (CSA
C22.2 No. 60950-1, UL 60950-1)
certificate of suitability NEC Class 2
No
CB approval
Yes
Marine approval
BV, DNV GL
EMC
Emitted interference
EN 61000-6-3 Class B
Supply harmonics limitation
EN 61000-3-2
Noise immunity
EN 61000-6-2
environmental conditions
6EP71336AE000BN0
Page 2/3
12.18.2020
Subject to change without notice
© Copyright Siemens
ambient temperature
● during operation
— Note
-30 ... +70 °C
with natural convection
● during transport
-40 ... +85 °C
● during storage
-40 ... +85 °C
Humidity class according to EN 60721
Climate class 3K3, 5 … 95% no condensation
Mechanics
Connection technology
Push-in terminals
Connections
● Supply input
L, N, PE: 1 push-in terminal each for 0.2 ... 2.5 mm² single-core/finely
stranded
● Output
+, -: 2 push-in terminals each for 0.2 ... 2.5 mm²
● Auxiliary
Signaling contact: 2 push-in terminals for 0.2 ... 2.5 mm²
● signaling contact
2 push-in terminals for 0.2 ... 2.5 mm²
product function
● removable terminal at input
Yes
● removable terminal at output
Yes
width of the enclosure
160 mm
height of the enclosure
117 mm
depth of the enclosure
74 mm
required spacing
● top
50 mm
● bottom
50 mm
● left
0 mm
● right
0 mm
Weight, approx.
0.7 kg
product feature of the enclosure housing can be lined up
Yes
Installation
Snaps onto DIN rail EN 60715 35x7.5/15
electrical accessories
Redundancy module, buffer module, selectivity module, DC UPS
MTBF at 40 °C
1 114 510 h
other information
Specifications at rated input voltage and ambient temperature +25 °C
(unless otherwise specified)
6EP71336AE000BN0
Page 3/3
12.18.2020
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“6EP71336AE000BN0”相匹配的价格&库存,您可以联系我们找货