Data sheet
TRS 120VUC 2CO
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
www.weidmueller.com
Product image
Similar to illustration
• 2 CO contacts
• Contact material: AgNi
• Unique multi-voltage input from 24 to 230 V UC
• Input voltages from 5 V DC to 230 V UC with coloured
marking: AC: red, DC: blue, UC: white
General ordering data
Version
Order No.
Type
GTIN (EAN)
Qty.
TERMSERIES, Relay module, Number of contacts:
2, CO contact AgNi, Rated control voltage: 120
V UC ±10 %, Continuous current: 8 A, Screw
connection, Test button available: No
1123530000
TRS 120VUC 2CO
4032248905744
10 pc(s).
Creation date November 3, 2022 6:16:04 PM CET
Catalogue status 25.10.2022 / We reserve the right to make technical changes.
1
Data sheet
TRS 120VUC 2CO
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
www.weidmueller.com
Technical data
Dimensions and weights
Depth
Height
Width
Net weight
87.8 mm
89.6 mm
12.8 mm
57 g
Depth (inches)
Height (inches)
Width (inches)
3.457 inch
3.528 inch
0.504 inch
-40 °C...85 °C
5-95% relative humidity,
Tu = 40°C, without
condensation
Operating temperature
-40 °C...60 °C
Output current derating (ohmic)
Connection cross-section AWG, max.
Tightening torque, max.
Rated current AC
Power rating
Pull-in/drop-out current, typ.
Protective circuit
Coil voltage of the replacement relay
Continuous current
Max. switching voltage, DC
AC switching capacity (resistive), max.
Switch-on delay
Contact type
Min. switching power
Temperatures
Storage temperature
Humidity
Environmental Product Compliance
REACH SVHC
Lead 7439-92-1
Rated data UL
Ambient temperature (operational), max. 60 °C
Connection cross-section AWG, min.
AWG 26
Type of conductor
rigid copper conductor,
flexible copper conductor
Pollution severity level
2
6 A @ 60 °C, 8 A @ 50 °C
AWG 14
0.4 Nm
Control side
Rated control voltage
Rated current DC
Pull-in/drop-out voltage, typ.
120 V UC ±10 %
3.5 mA
83 V / 28 V AC
90 V / 22 V DC
Green LED
Status indicator
Coil voltage of the replacement relay
deviating from the rated control voltage Yes
3.5 mA
420 mVA / 420 mW
2.5 mA / 0.7 mA AC
2.6 mA / 0.58 mA DC
Rectifier
110 V DC
Load side
Rated switching voltage
Max. switching frequency at rated load
Inrush current
DC switching capacity (resistive), max.
Switch-off delay
Mechanical service life
250 V AC
0.1 Hz
15 A / 4 s
192 W @ 24 V
≤ 9 ms
30 x 106 switching cycles
8A
250 V
2000 VA
< 11 ms
2 CO contact (AgNi)
1 mA @ 24 V, 10 mA @ 10
V, 100 mA @ 5 V
General data
Operating altitude
Rail
Test button available
Mechanical switch position indicator
Colour
UL94 flammability rating component
≤ 2000 m, above sea level
TS 35
No
No
black
Component
UL94 flammability rating
Component
UL94 flammability rating
Housing
V-0
Retaining clip
V-0
Creation date November 3, 2022 6:16:04 PM CET
Catalogue status 25.10.2022 / We reserve the right to make technical changes.
2
Data sheet
TRS 120VUC 2CO
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
www.weidmueller.com
Technical data
Insulation coordination
Rated voltage
Surge voltage category
Dielectric strength for control side - load
side
Dielectric strength of neighbouring
contacts
Dielectric strength of open contact
Impulse withstand voltage
300 V
III
3.51 kVeff /1 min.
Pollution severity
Clearance and creepage distances for
control side - load side
Type of isolation at input and output
2
≥ 6 mm
reinforced insulation
Type of isolation at neighbouring
contacts
Dielectric strength to mounting rail
Protection degree
IEC 61810-1
E141197
Certificate No. (DNVGL)
Screw connection
0.4 Nm
0.14 mm²
Stripping length, rated connection
8 mm
Clamping range, rated connection
1.5 mm²
Clamping range, max.
2.5 mm²
Wire connection cross section AWG,
max.
AWG 14
Wire cross-section, solid, max.
2.5 mm²
Wire cross-section, solid, max. (AWG) AWG 14
Wire connection cross section, finely
stranded, max.
2.5 mm²
Wire cross-section, finely stranded, max.
(AWG)
AWG 16
Wire connection cross-section, finely
stranded with wire-end ferrules DIN
46228/4, max.
2.5 mm²
Conductor cross-section, flexible, AEH
(DIN 46228-1), max.
1.5 mm²
Wire cross-section, finely stranded, two
clampable wires, max.
1 mm²
Twin wire-end ferrules, max.
1 mm²
Gauge to IEC 60947-1
A1, B1
ETIM 7.0
ECLASS 9.0
ECLASS 10.0
ECLASS 12.0
2.5 kVeff / 1 Min.
1 kVeff / 1 min
6 kV (1.2/50 µs)
Basic insulation
4 kVeff / 1 Min.
IP20
Further details of approvals / standards
Standards
Certificate no. (cULus)
TAA00001E5
Connection data
Wire connection method
Tightening torque, max.
Clamping range, min.
Wire connection cross section AWG,
min.
Wire cross-section, solid, min.
Wire cross-section, solid, min. (AWG)
Wire connection cross section, finely
stranded, min.
Wire cross-section, finely stranded, min.
(AWG)
Wire connection cross-section, finely
stranded with wire-end ferrules DIN
46228/4, min.
Conductor cross-section, flexible, AEH
(DIN 46228-1), min.
Wire connection cross section, finely
stranded, two clampable wires, min.
Twin wire-end ferrules, min.
Blade size
AWG 26
0.14 mm²
AWG 26
0.14 mm²
AWG 26
0.25 mm²
0.25 mm²
0.5 mm²
0.5 mm²
size PH0
Classifications
ETIM 6.0
ETIM 8.0
ECLASS 9.1
ECLASS 11.0
EC001437
EC001437
27-37-16-01
27-37-16-01
EC001437
27-37-16-01
27-37-16-01
27-37-16-01
Approvals
Approvals
ROHS
UL File Number Search
Certificate no. (cULus)
Conform
UL Website
E141197
Creation date November 3, 2022 6:16:04 PM CET
Catalogue status 25.10.2022 / We reserve the right to make technical changes.
3
Data sheet
TRS 120VUC 2CO
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
www.weidmueller.com
Technical data
Downloads
Approval/Certificate/Document of
Conformity
Engineering Data
Engineering Data
User Documentation
Catalogues
Brochures
EU Konformitätserklärung / EU Declaration of Conformity
CAD data -- STEP
EPLAN, WSCAD, Zuken E3.S
Beipackzettel / Package Insert – multilingual
Catalogues in PDF-format
Creation date November 3, 2022 6:16:04 PM CET
Catalogue status 25.10.2022 / We reserve the right to make technical changes.
4
Data sheet
TRS 120VUC 2CO
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
www.weidmueller.com
Drawings
Wiring diagram
Graph
Graph
DC load limit curve
Resistive load
Dimensional drawing
Electrical service life230 V AC resistive load
230 V AC resistive load
Creation date November 3, 2022 6:16:04 PM CET
Catalogue status 25.10.2022 / We reserve the right to make technical changes.
5
Data sheet
TRS 120VUC 2CO
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
www.weidmueller.com
Drawings
Miscellaneous
Type codes
Creation date November 3, 2022 6:16:04 PM CET
Catalogue status 25.10.2022 / We reserve the right to make technical changes.
6