Specialty Terminals
W
BS-31-4S-NB thru BS-33-10-NB
C
Block Fork, Nylon Insulated with Insulation Grip
L
E
Data Sheet
Product
Number
Wire
Range
(AWG)
Stud
Size
Thickness
Barrel
Length
Barrel
I.D.
Maximum
Insulation
Diameter
W
C
L
E
BS-31-4S-NB
22-18
4
0.25
0.25
0.84
0.69
0.030
0.25
0.070
0.145
BS-31-6S-NB
22-18
6
0.25
0.25
0.84
0.69
0.030
0..25
0.070
0.145
BS-31-6-NB
22-18
6
0.30
0.25
0.84
0.69
0.030
0.25
0.070
0.145
BS-31-8-NB
22-18
8
0.30
0.25
0.84
0.69
0.030
0.25
0.070
0.145
BS-31-10-NB
22-18
10
0.30
0.25
0.84
0.69
0.030
0.25
0.070
0.145
BS-32-4S-NB
16-14
4
0.25
0.25
0.86
0.71
0.030
0.25
0.090
0.170
BS-32-6S-NB
16-14
6
0.25
0.25
0.86
0.71
0.030
0.25
0.090
0.170
BS-32-6-NB
16-14
6
0.30
0.25
0.86
0.71
0.030
0.25
0.090
0.170
BS-32-8-NB
16-14
8
0.30
0.25
0.86
0.71
0.030
0.25
0.090
0.170
BS-32-10-NB
16-14
10
0.30
0.25
0.86
0.71
0.030
0.25
0.090
0.170
BS-33-6-NB
12-10
6
0.32
0.29
1.03
0.84
0.040
0.25
0.135
0.250
BS-33-8-NB
12-10
8
0.32
0.29
1.03
0.84
0.040
0.25
0.135
0.250
BS-33-10-NB
12-10
10
0.32
0.29
1.03
0.84
0.040
0.25
0.135
0.250
Installation Information
WARNING
LISTED 314R
UNDERWRITERS
LABORATORIES
STANDARD NO. UL 486A
3M FILE NO. E23438
CANADIAN STANDARDS
ASSOCIATION
STANDARD NO. C22.2
NO. 0. 65
3M FILE NO. LR22190
Specifications
Wire Size:
Barrel Seam:
Max. Voltage Rating:
Max. Operating Temp.:
Max. Current:
Insulator Material:
Terminal Material:
Insulation Grip Material:
Plating:
Turn power off before installing or removing terminal. All electrical
work should be done according to appropriate electrical codes.
UL Listed and CSA Certified for use on stranded copper
(AWG) wire only.
Strip away the end 3/8 inch of wire insulation.
See Table Above
Butted with Insulation Grip
600 V Building Wire
1000 V Signs, Fixtures
and Luminaires
221˚F (105˚C)
Same as Wire
Nylon
ETP Copper
Brass
Tin
Make the crimp in the proper station of a recommended
3M crimp tool: TH-440, TH-450 (scissor style), or TR-482,
TR-490 (ratchet style) hand tools.
Barrel Crimp (Electrical)
Insulation Crimp (Mechanical)
Engineering Specification
Crimp-type terminals shall, electrically and
mechanically, connect to a pre-stripped end of a
stranded copper wire and have a flat tongue portion
with a central opening for mounting around a screw or
stud.
The terminal line shall offer tongue variations in hole
(stud) size (6, 8 10, etc.) and configuration (ring, fork,
block fork, flanged block fork, locking fork, etc.): and
barrel variations in wire (AWG) size (22-18, 16-14,
12-10, etc.) and construction (non-insulated brazed
seam, vinyl insulated butted seam, nylon insulated with
insulation grip, etc.). The terminal line shall have
regulatory agency coverage (UL Listing, CSA
Certification). The terminal tongue shall be marked
with the wire range and manufacturer’s symbol ().
The nylon-insulated, block fork terminal with insulation
grip shall be tin-plated, annealed copper, with the
tongue having a specified stud slot (size 4 thru 10) and
a butted seam barrel with a tin plated brass, funnel entry
insulation grip, covered by a molded nylon sleeve, color
coded and sized for a specified (AWG) wire range
(22-18, 16-14, 12-10).
Insulated terminals shall be UL Listed and CSA
Certified for 600 Volts maximum building wire: 1000
Volts maximum in signs, fixtures and luminaires and
have a maximum operating temperature of 221°F
(105°C).
3M is a trademark of 3M.
is a trademark of Underwriters Laboratories.
is a trademark of Canadian Standards Association.
IMPORTANT NOTICE
Before using this product, you must evaluate it and determine if it is suitable for your intended application. You assume all risks and liability
associated with such use.
Warranty; Limited Remedy; Limited Liability. This product will be free from defects in material and manufacture as of the date of purchase.
3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR
FITNESS FOR A PARTICULAR PURPOSE. If this product is defective within the warranty period stated above, your exclusive remedy shall be,
at 3M’s option, to replace or repair the 3M product or refund the purchase price of the 3M product. Except where prohibited by law, 3M will
not be liable for any loss or damage arising from this 3M product, whether direct, indirect, special, incidental or consequential
regardless of the legal theory asserted.
Electrical Products Division
6801 River Place Blvd.
Austin, TX 78726-9000
http://www.3M.com/elpd
Litho in USA.
© 3M 2002 78-8126-0869-9-A