3M™ Fire Barrier Rated Foam FIP 1-Step
Product Data Sheet
1. Product Description
4
4
4
4
SOUND BARRIER
SMOKE SEAL
57
In STC 57-rated
wall assembly
Meets Air Leakage
Requirements
FIRE BARRIER
TEMPERATURE
UP TO 2 HOUR
T
RATED
F
Is a Rated Firestop Foam
Is UL Listed
Meets ASTM E 814
Meets the International Building Code for passive fire protection
L
RATED
FILL, VOID OR
CAVITY MATERIAL
RATED
ATTENTION: CODE OFFICIALS
FIP 1-Step
FILL, VOID OR CAVITY
MATERIAL FOR USE IN
THROUGH-PENETRATION
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE
DIRECTORY 50L6
STC
3M™ Fire Barrier Rated Foam FIP 1-Step is a smoke, sound and firestopping foam for wall and floor
penetrations. Premium two-part, easy-to-handle formulation. Expands up to five times during installation
and bonds to most construction substrates including, but not limited to, concrete, metal, wood, plastic and
cable jacketing. Dries to a flexible solid. During a fire, product maintains a tight firestop against smoke
and flame.
• Re-enterable/repairable
• Sag-resistant formulation
• Excellent adhesion
• Paintable with primer
• Quick cure and eliminates the need for mineral wool and caulk
UP TO 1 HOUR
PLEASE SEE APPROPRIATE UL SYSTEM
FOR ASSOCIATED RATING.
2. Applications
Typical applications include: blank openings, metal pipe, cables, cable tray, insulated pipe, combination penetrations through concrete
floor/wall and gypsum wall board assemblies.
3. Specifications
FIP 1-Step shall be a two-component, ready-to-use, gun-grade, firestopping foam. FIP 1-Step
shall be tested to the criteria of ASTM E 814/UL 1479 Standard Test Method for Fire Tests of
Penetration Firestop Systems, ASTM E 84/UL 723 Standard Test Method for Surface Burning
Characteristics of Building Materials, ASTM E 90 Standard Test Method for Laboratory
Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements, and
ASTM E 413 Classification for Rating Sound Insulation. FIP 1-Step shall meet the requirements
of the IBC, IRC, IFC, IPC, IMC, NFPA 5000, NEC (NFPA 70), NFPA 101 and NBCC.
Typically Specified Divisions
Division 7
Section 07 84 00 – Firestopping
Section 07 27 00 – Air Barriers
Related Sections
Section 07 86 00 – Smoke Seals
Section 07 87 00 – Smoke Containment Barriers
Section 21 00 00 – Fire Suppression
Section 22 00 00 – Plumbing
Section 26 00 00 – Electrical
4. Storage and Shelf Life
Storage:
IP 1-Step should be stored indoors in dry conditions between 40°F and 85°F (5°C and 30°C). Avoid freeze/thaw
F
exposures of the FIP 1-Step while still in the packaging. If product freezes, then product must be fully thawed and
brought to ideal application temperature prior to use (See Section 5).
Shelf Life: FIP 1-Step shelf life is 16 months in original unopened containers from date of packaging when stored above
68°F (20°C) and below 90°F (32.2°C).
Lot numbering: First to fourth digit = Date of Production (YYMM); Fifth digit = 4 (Production Code);
Sixth and Seventh digit = (Batch #); (Note: Expiration Date marked on cartridge)
For technical support relating to 3M™ Fire Protection Products and Systems, call: 1-800-328-1687
For more information on 3M™ Fire Protection Products, visit: www.3M.com/firestop
5. Performance and Typical Physical Properties
Maroon
50° to 120°F (10° to 49°C)
Flame Spread 10,
Smoke Development 50
57 when tested in STC 57 rated
wall assembly
12.85 fl. oz. Cartridge (380mL)