Data Sheet
April 2010
Compact Power Line
CP1800AC52 Front-End Power Supply
Input: 100-120/200-240 Vac; Outputs: ±(44-58) Vdc at 1800W; +5 Vdc at 4W
Features
Compact 1-RU form factor providing 20 W/in3
Constant power from 48 – 58 Vdc
1800W from nominal 200 – 240 Vac
1200W from nominal 100 – 120 Vac
Output voltage programmable from 44V – 58 Vdc;
Applications
48Vdc distributed power architectures
Power over Ethernet
Routers/Switches
VoIP/Soft Switches
LAN/WAN/MAN applications
File servers
Indoor wireless
Telecommunications equipment
Enterprise Networks
SAN/NAS/iSCSI applications
Advanced workstations
output defaulted to 52V
PMBus compliant dual I2C and RS485 serial bus
communications
Power factor correction (meets EN/IEC 61000-3-2
and EN 60555-2 requirements)
DC Output over-voltage and over-current
protection
AC Input over-voltage and under-voltage protection
Over-temperature warning and protection
Redundant, parallel operation with active load
sharing and redundant +5V Aux power
Remote ON/OFF
Hot insertion/removal (hot plug)
Four front panel LED indicators
UL* Recognized to UL60950-1, CAN/ CSA† C22.2
No. 60950-1, and VDE‡ 0805-1 Licensed to
IEC60950-1
CE mark meets 2006/95/EC directive§
Variable-speed fan control
The CP1800AC52 Front-End Power Supplies in the Compact Power Line platform are specifically
designed to operate as an integral part of a complete distributed power system. The high-density, front-toback airflow rectifier is designed for minimal space utilization and is highly expandable for future growth.
The rectifier is provided with RS485 and dual-redundant I2C communications busses that allow it to be
used in a broad range of applications. The flexible feature set makes this front-end rectifier an excellent
choice for applications requiring modular ac-to-dc bulk intermediate voltages, such as in distributed power.
*
†
‡
§
UL is a registered trademark of Underwriters Laboratories, Inc.
CSA is a registered trademark of Canadian Standards Association.
VDE is a trademark of Verband Deutscher Elektrotechniker e.V.
This product is intended for integration into end-user equipment. All the required procedures for CE marking of end-user
equipment should be followed. (The CE mark is placed on selected products.)
** ISO is a registered trademark of the International Organization of Standards.
*** For PoE applications, order the CP2000AC54PE, which is 100% factory hipot-tested per IEEE802.3af.
Data Sheet
Compact Power Line
CP1800AC52 Front-End Power Supply
Specifications
Input
Parameter
Min
Typ
Startup Input Voltage
1200W Operation
1800W Operation
Max
Units
The power supply automatically configures its
operating mode based on the voltage level it
reads on first turn ON. (This information is
retained as long as internal bias is maintained.)
85
175
Operating Voltage Range
1200W Configuration
1800W Configuration
1800W Configuration
85
175
150
Permitted Excursions
275
300
Surges
300
325
Input Frequency
44
Input Current
120/200/240
200/240
275
275
175
66
Notes
Vac
If started within low input line range.
If started within high input line range.
Will derate to 80% of full load; will shutdown
below 150Vac.
May not meet all requirements, but will
maintain output regulation.
May shut down but will not get damaged.
Hz
13.3
11.2
9.8
8.2
A
25
Apk
Measured at 25°C for all line conditions; does
not include X-Capacitors charging.
Input Leakage Current
1.5
mA
Measured at 265Vac, 60Hz
Power Factor
0.98
Inrush Transient
Efficiency
At 100 Vac
At 120 Vac
At 200 Vac
At 240 Vac
From 50% to 100% load.
90
93
%
Holdup Time
15
ms
At 100 Vac with Vout > 52V and Pout > 50%.
At 230 Vac with Vout > 52V and Pout > 50%.
Measurement starts at zero crossing of the ac
voltage. Alarm issued via PFW signal going LO
5 ms prior to output voltages going out of limits.
Measurements made at 75% full load and
voltage allowed to decay to 49.5V. Holdup time
is inversely proportional to delivered output
load.
For loads below 1200W.
20
Main Output
Parameter
Min
Typ
Maximum Output Power
Output Voltage Setpoint
Setpoint Accuracy
Overall Regulation
Output Voltage Range
Maximum Output Current
Current Share
Lineage Power
Max
Units
1200
1800
W
At low-line input from 100-120Vac nominal.
At high-line input from 200-240Vac nominal.
Vdc
Output floats with respect to frame ground.
52
-1
+1
%
-2
+2
%
44
58
Vdc
23
34.6
A
10
%FL
Notes
Includes all variations due to specified load
range, drift, and environmental conditions.
Set either by I2C, RS485, or analog margining.
At 1200W, 52V and 100-120Vac.
At 1800W, 52V and 200-240Vac.
Single-wire connection. Maintains tolerance to
average of all other rectifiers. Loads > 50% FL
2
Data Sheet
Compact Power Line
CP1800AC52 Front-End Power Supply
Specifications (continued)
Output (continued)
Parameter
Min
Typ
Output Ripple
RMS (5Hz to 20MHz)
Peak-to-Peak (5Hz to 20MHz)
Psophometric Noise
Max
Units
250
500
2
mVrms
mVpk-pk
mVrms
5,000
F
2
s
ms
s
%
External Bulk Load Capacitance
0
Turn-On
Delay
Rise Time1 - Standard (PMBus)
-Telecom (RS-485)2
Overshoot
5
100
5
Load Step Response
I
V
Response Time
Power Limit
50
3.5
20
48
58
%FL
Vdc
ms
60
Monotonic Turn_On from 30% to 100%
of Vnom above -5°C operation.
Monotonic Turn_On from 60% to 100%
of Vnom below -5°C operation.
I/t slew rate 1A/µs.
Settling time to within regulation
requirements.
Adc
Below 36Vdc, hiccup will commence
with an ON time of less than 4 seconds.
The ON time duty cycle is about 10%. A
latched shutdown can be selected using
I2C instructions.
Vdc
In the default state, three restarts within
a 1 minute window will be attempted.
Using I2C instructions a latched
shutdown mode can be selected.
°C
Before shutdown. The default state will
shut down and restart automatically
when the unit sufficiently cools down.
Using I2c instructions a latched
shutdown mode can be selected. [Note:
There is only a single latched shutdown
command. If set, all three protection
modes; OV, OC and OT, are
reconfigured simultaneously].
Over-temperature Warning
5
External capacitance can be increased
but the power supply will not meet its
turn-ON rise time requirement.
Limited to 1200W at 100 - 120 Vac.
Limited to 1800W at 200 - 240 Vac.
Over-voltage Protection
58
Measured with 20MHz bandwidth under
any condition of loading. Minimum load
is 1A.
Vdc
Over-current Protection
37
Notes
1. Below -5°C, the rise time is approximately 5 minutes to protect the bulk capacitors.
2. Complies with GR947 which calls for a minimum rise time proportional to output load.
Auxiliary Output
Parameter
Min
Typ
Power
3.75
Output Voltage Setpoint
Overall Regulation
5
-5
Ripple and Noise
50
Over-voltage Clamp
Output Current
Over-current Limit
Lineage Power
Max
Units
Notes
W
Vdc
5
%
100
mVpk-pk
7
Vdc
0.005
0.75
Adc
110
175
%FL
20MHz bandwidth
3
Data Sheet
Compact Power Line
CP1800AC52 Front-End Power Supply
Specifications (continued)
Physical
Length (in./mm)
13.85 / 351.8
Width (in./mm)
4.00 / 101.6
Height (in./mm)
1.66 / 42.2
Weight (lb / kg)
4.6 / 2.1
Output (continued)
Parameter
Max
Units
Operating Temperature
Min
-5
Typ
55
°C
Extended Operating
Temperature
55
75
°C
Storage Temperature
Notes
The rectifier will start up to -40°C.
With 2%/°C power derating above 55°C.
-40
85
°C
Humidity
5
95
%
Relative humidity, non-condensing
Altitude
-60
-200
4000
13000
m
ft
For operation above 2500m (5000 ft.),
maximum operating temperature is derated
by 2°C per 305m (1000 ft.).
Shock and Vibration
Operational Test
Test Levels
Drop and Tip Over
Earthquake Rating
IEC 68-2
IEC 721-3-2
IEC 68-2-31
4
Acoustic Noise
Zone
45
Per Telcordia GR-63-CORE, all floors,
when installed in CP Shelf.
Noise is proportional to fan speed, load and
ambient temperature.
dBA
Harmonic Emissions
Per EN/IEC61000-3-2
Radiated Emissions*
FCC and CISPR22 (EN55022) - Class B
Conducted Emissions - ac
FCC and CISPR22 (EN55022) Class B
Telcordia GR-1089-CORE - Class A
Conducted Emissions - dc
Telcordia GR-1089-CORE and CISPR22 (EN55022) - Class A
ESD
Error free per EN/IEC 61000-4-2 Level 3 (6 kV contact discharge, 8 kV air
discharge).
Radiated Immunity
Error free per EN/IEC 61000-4-3 Level 3 (10 V/m).
Electrical Fast Transient
Burst
Error free per EN/IEC 61000-4-4 Level 3 (2 kV, 5 kHz repetition rate)
Lightning Surge
Error Free
Damage Free
EN/IEC61000-4-5 Level 4 (4 kV common mode, 2 kV differential mode).
ANSI C62.41 Level A3 (6 kV common and differential mode)
Conducted Immunity
Error free per EN/IEC 61000-4-6 Level 3 (10Vrms).
Reliability (calculated)
Isolation
Input-Chassis/Signals
Input - Output
Output-Chassis
Service Life
400,000
1500
3000
500
10
Hours
At ambient of 25°C at full load per Telcordia
SR-332, Reliability Prediction for Electronic
Equipment, Method I Case III.
Vrms
Vrms
Vdc
Per EN60950.
Years
25°C ambient, full load excluding fans.
Consult factory for testing to this requirement
Internal Lineage standard
*Radiated emissions compliance was met using a Lineage shelf. This shelf includes output common and differential mode
capacitors that assist in meeting compliance.
Lineage Power
4
Data Sheet
Status and Control
The rectifier provides three means for
monitor/control: analog, PMBus compliant I2C, or
RS485 for interfacing to Lineage controllers or
battery plants.
Details of analog controls are provided in this data
sheet under Signal Definitions. Tyco Electronics will
provide separate application notes on PMBus
protocol for users to interface to the CPL rectifiers.
Contact your local Tyco representative for details.
Hot Plug
When rapidly extracting and reinserting modules
care should be taken to allow for discharging the
internal bias supply so that a predictable restart
could be achieved. The way to ensure that the
circuit sufficiently discharges is to observe the
spinning of the fans after an extraction. The unit
should not be reinserted until the fans stop
spinning.
Control Definitions
All signals are referenced to Logic GRD unless
otherwise noted. See the Signal Definitions Table
at the end of this document for further description
of all the signals.
Input Signals
Margining: Setpoint of the rectifier can be changed
via this input pin. Programming can be either a
voltage source or a resistance divider. Accuracy is
dependent on the overall divider if resistive
programming is used. The margining pin is
connected to 3.3Vdc via a 10k resistor inside the
rectifier. See graphs below.
Compact Power Line
CP1800AC52 Front-End Power Supply
Module Present Signal: This signal has dual
functionality. It can be used to alert the system
when a module is inserted. Has a 500 resistor in
series between this signal and Logic GRD. An
external pull-up should not raise the voltage on the
pin above 0.25Vdc. If raised the pin is raised to
5Vdc the write_protect feature of the EEPROM is
enabled.
Protocol Select: Establishes the communications
mode of the power supply, between analog/I2C and
RS-485 modes. For RS485, connect 10k pulldown resistor to 54_OUT(-DC).
Enable: On/Off control when either PMBus
communications or analog functions are utilized as
configured by the Protocol pin. This pin must be
pulled low to turn ON the main output of the power
supply. The power supply will turn OFF if either the
Enable or the ON/OFF pin is released. The Enable
function does not work with the RS-485 protocol.
This signal is referenced to Logic_GRD.
ON/OFF: This is a short pin utilized for hot-plug
applications to ensure that the power supply turns
OFF before the power pins are disengaged. It also
ensures that the power supply turns ON only after
the power pins have been engaged. Must be
connected to 54_OUT (-DC).
Output Signals
Alert #: PMBus interrupt signal.
Fault: This signal goes LO for any failure that
requires rectifier replacement. Some of these faults
may be due to:
Fan failure
Over-temperature condition
Over-temperature shutdown
Over-voltage shutdown
Internal Rectifier Fault
Power Capacity: A HI on this pin indicates rectifier
configured for 1800W operation; a LO indicates
rectifier configured for 1200W operation.
An open circuit on this pin reverts the voltage level
back to the original setting.
Lineage Power
5
Data Sheet
Compact Power Line
CP1800AC52 Front-End Power Supply
Alarm Table
Monitoring Signals
(Referenced to Logic_GRD)
Module
Fault
OTW
PFW
Present
HI
HI
HI
LO
Power Supply LED State
AC OK
DC OK
Service
Fault
Green
Green
Amber
Red
1
1
0
0
Condition
OK
Thermal Alarm
(5C before shutdown)
Thermal Shutdown
Defective Fan
Blown AC Fuse in Unit
No AC
很抱歉,暂时无法提供与“108994546”相匹配的价格&库存,您可以联系我们找货