Data sheet
Current monitoring relays CM-SRS.2
For single-phase AC/DC currents
The CM-SRS.2 is an electronic current monitoring
relay that monitors single-phase mains (DC or AC)
for over- and undercurrent from 3 mA to 15 A.
Characteristics
–– Monitoring of DC and AC currents (3 mA to 15 A)
–– TRMS measuring principle
–– One device includes 3 measuring ranges
–– Over- or undercurrent monitoring configurable
–– Hysteresis adjustable (3-30 %)
–– Tripping delay TV adjustable (0 s; 0.1-30 s)
–– 3 control supply voltage versions
–– Precise adjustment by front-face operating controls
–– Screw connection technology or
Easy Connect Technology available
–– Housing material for highest fire protection classification
UL 94 V-0
–– Tool-free mounting on DIN rail as well as demounting
–– 2 c/o (SPDT) contacts
–– 22.5 mm (0.89 in) width
–– 3 LEDs for status indication
2CDC 251 245 F0005
All devices are available with two different terminal
versions. You can choose between the proven
screw connection technology (double-chamber
cage connecting terminals) and the completely
tool-free Easy Connect Technology (push-in
terminals).
Approvals / Marks
A C R E L
/ ab
Classifcations:
EN 50155, IEC 60571, NF F 16-101/102, EN 45545-2
EN 50155, IEC 60571
Temp.
class
T3
Voltage supply
S1
S2
n
n
Vibration and shock
acc to IEC/EN 61373
Coated pcb.
Cat 1, Class B
no
C1 C2
n
-
NF F 16-101/102
Flammability
Opticity and toxicity of
index
smoke index
EN 45545-2
Risk level achieved
I2
HL3
F2
Order data
Current monitoring relays
Type
Rated control supply voltage
Connection technology
Measuring ranges
Order code
CM-SRS.21P
24-240 V AC/DC
Push-in terminals
3-30 mA, 10-100 mA, 0.1-1 A
1SVR740840R0400
110-130 V AC
1SVR740841R0400
220-240 V AC
CM-SRS.21S
24-240 V AC/DC
1SVR740841R1400
Screw type terminals
3-30 mA, 10-100 mA, 0.1-1 A
110-130 V AC
1SVR730841R0400
220-240 V AC
CM-SRS.22S
24-240 V AC/DC
1SVR730840R0400
1SVR730841R1400
Screw type terminals
0.3-1.5 A, 1-5 A, 3-15 A
1SVR730840R0500
110-130 V AC
1SVR730841R0500
220-240 V AC
1SVR730841R1500
Accessories
Type
Description
Order code
ADP.01
Adapter for screw mounting
1SVR430029R0100
MAR.12
Marker label for devices with DIP switches
1SVR730006R0000
COV.11
Sealable transparent cover
1SVR730005R0100
2 - Current monitoring relays CM-SRS.2 | Data sheet
Connection technology
Type designation CM-xxS.yyP
Type designation CM-xxS.yyS
2CDC 253 025 F0011
Approved screw connection technology with
double-chamber cage connecting terminals
2CDC 253 026 F0011
Maintenance free Easy Connect Technology with
push-in terminals
Push-in terminals
Double-chamber cage connecting terminals
–– Tool-free connection of rigid and flexible wires with
wire end ferrule
–– Easy connection of flexible wires without wire end
ferrule by opening the terminals
–– No retightening necessary
–– One operation lever for opening both connecting
terminals
–– For triggering the lever and disconnecting of wires
you can use the same tool (Screwdriver according to
DIN ISO 2380-1 Form A 0.8 x 4 mm (0.0315 x 0.157
in), DIN ISO 8764-1 PZ1 ø 4.5 mm (0.177 in))
–– Constant spring force on terminal point independent
of the applied wire type, wire size or ambient
conditions (e. g. vibrations or temperature changes)
–– Opening for testing the electrical contacting
–– Gas-tight
–– Terminal spaces for different wire sizes
–– One screw for opening and closing of both cages
–– Pozidrive screws for pan- or crosshead screwdrivers
according to DIN ISO 2380-1 Form A 0.8 x 4 mm
(0.0315 x 0.157 in), DIN ISO 8764-1 PZ1 ø 4.5 mm
(0.177 in)
Both the Easy Connect Technology with push-in terminals and screw connection technology with double-chamber cage
connecting terminals have the same connection geometry as well as terminal position.
Data sheet | Current monitoring relays CM-SRS.2 - 3
Functions
Operating controls
1 Adjustment of the hysteresis (MIN = Default)
2 Adjustment of the threshold value (MIN = Default)
3 Indication of operational states
U/T: green LED – control supply voltage/timing
R: yellow LED – relay status
I: red LED – over- / undercurrent
1
2CDC 251 054 V0011
2
4 Adjustment of the tripping delay TV
5 DIP switches (see DIP switch functions)
3
4
5
Application
The current monitoring relays CM-SRS.2 are designed for use in single-phase AC and/or DC systems for over- or
undercurrent monitoring. The devices are available with different supply voltage ranges, provide an adjustable tripping delay
and work according to the open-circuit principle.
Operating mode
The CM-SRS.2 with 2 c/o (SPDT) contacts are available in 2 versions with 3 measuring ranges: 3-30 mA, 10-100 mA,
0.1-1 A (CM-SRS.21) and 0.3-1.5 A, 1-5 A, 3-15 A (CM-SRS.22). The measuring range is selected by connecting the
monitored wire to the corresponding terminal B1/B2/B3-C.
The units are adjusted with front-face operating controls. The selection of over- b or undercurrent monitoring a is made
with a DIP switch. Potentiometers, with direct reading scale, allow the adjustment of the threshold value I, the hysteresis %
and the tripping delay TV. The hysteresis % is adjustable within a range of 3 to 30 % of the threshold value and the tripping
delay TV over a range of instantaneous to a 30 s delay. Timing is displayed by a flashing green LED labelled U/T.
4 - Current monitoring relays CM-SRS.2 | Data sheet
Function diagrams
Overcurrent monitoring
b
The current to be monitored (measured value) is applied to terminals B1/B2/B3-C. The control supply voltage applied to
terminals A1-A2 is displayed by the glowing green LED.
If the measured value exceeds the adjusted threshold value, the tripping delay TV starts and the red LED (overcurrent)
glows. Timing of TV is displayed by the flashing W green LED. When TV is complete and the measured value still
exceeds the threshold value minus the adjusted hysteresis, the output relays energize and the yellow LED (relay energized)
glows.
If the measured value decreases below the threshold value minus the adjusted hysteresis, the output relays de-energize
and the red and yellow LEDs turn off.
A1-A2
Threshold
Hysteresis
Measured value
TV
< TV
11-14 (15-18)
11-12 (15-16)
2CDC 252 210 F0205
21-24 (25-28)
21-22 (25-26)
green LED
red LED
yellow LED
Undercurrent monitoring
a
The current to be monitored (measured value) is applied to terminals B1/B2/B3-C. The control supply voltage applied to
terminals A1-A2 is displayed by the glowing green LED.
If the measured value decreases below the adjusted threshold value, the tripping delay TV starts and the red LED
(undercurrent) flashes W . Timing of TV is displayed by the flashing W green LED. When TV is complete and the
measured value is still below the threshold value plus the adjusted hysteresis, the output relays energize and the yellow LED
(relay energized) glows.
If the measured value exceeds the threshold value plus the adjusted hysteresis, the output relays de-energize and the red
and yellow LEDs turn off.
A1-A2
Measured value
TV
< TV
Hysteresis
Threshold
21-24 (25-28)
21-22 (25-26)
green LED
red LED
yellow LED
2CDC 252 211 F0205
11-14 (15-18)
11-12 (15-16)
Data sheet | Current monitoring relays CM-SRS.2 - 5
Electrical connection
A1
B1
1115
B2
B1 B2 B3 1115
A1-A2
2125
B3
B1-C
Measuring range 1:
2125
1216
2226
C
A2
2CDC 252 205 F0005
1418
2428
CM-SRS.21: 3-30 mA
CM-SRS.22: 0.3-1.5 A
B2-C
Measuring range 2: CM-SRS.21: 10-100 mA
CM-SRS.22: 1-5 A
C
A1 A2 1216 1418 2226 2428
Rated control supply voltage
B3-C
Measuring range 3: CM-SRS.21: 0.1-1 A
CM-SRS.22: 3-15 A
11 15-12 16/14 18
Output contacts - open-circuit principle
21 25-22 26/2428
Connection diagram
DIP switches
1
ON Undercurrent monitoring
OFF Overcurrent monitoring
2CDC 252 272 F0005
OFF = Default
6 - Current monitoring relays CM-SRS.2 | Data sheet
Technical data
Data at Ta = 25 °C and rated values, unless otherwise indicated
Input circuits
Supply circuit
A1-A2
Rated control supply voltage Us
110-130 V AC
Rated control supply voltage Us tolerance
-15...+10 %
Rated frequency
220-240 V AC
50/60 Hz
Typical current / power consumption
24 V DC
24-240 V AC/DC
50/60 Hz or DC
-
-
30 mA / 0.75 W
115 V AC
24 mA / 2.6 VA
-
17 mA / 1.9 VA
230 V AC
-
12 mA / 2.6 VA
11 mA / 2.6 VA
Power failure buffering time
20 ms
Transient overvoltage protection
varistors
Measuring circuit
B1/B2/B3-C
Monitoring function
over- or undercurrent monitoring configurable
Measuring method
TRMS measuring principle
Measuring inputs
CM-SRS.21
terminal connection
measuring range
input resistance
pulse overload capacity t < 1 s
continuous capacity
B1-C
B2-C
CM-SRS.221)
B3-C
B1-C
B2-C
0.3-1.5 A 1-5 A
3-15 A
3.3 Ω
0.1 Ω
0.05 Ω
0.01 Ω
0.0025 Ω
10 A
15 A
50 A
100 A
2A
7A
17 A
1Ω
500 mA 1 A
50 mA
150 mA 1.5 A
Threshold value
adjustable within the indicated measuring range
Tolerance of the adjusted threshold value
10 % of the range end value
Hysteresis related to the threshold value
3-30 % adjustable
Measuring signal frequency range
DC / 15 Hz - 2 kHz
Rated measuring signal frequency range
Maximum response time
B3-C
3-30 mA 10-100 mA 0.1-1 A
DC / 50-60 Hz
AC
80 ms
DC
120 ms
Accuracy within the rated control supply voltage tolerance
ΔU ≤ 0.5 %
Accuracy within the temperature range
ΔU ≤ 0.06 % / °C
Timing circuit
Time delay TV
0 s or 0.1-30 s adjustable
Repeat accuracy (constant parameters)
±0.07 % of full scale
Tolerance of the adjusted time delay
-
Accuracy within the rated control supply voltage tolerance
Δt ≤ 0.5 %
Accuracy within temperature range
Δt ≤ 0.06 % / °C
User interface
Indication of operational states
Control supply voltage
Measured value
Relay status
U/T: green LED
I: red LED
R: yellow LED
V: control supply voltage applied
W: tripping delay TV active
V: overcurrent
W: undercurrent
V: output relay energized
For usage of the current monitoring relays according to UL, following limitations for the measuring circuits are applicable: The load on any single measuring circuit should not exceed
15 A at 51-150 V, 10 A at 151-300 V or 5 A at 301-600 V.
This limitation is only valid for application according to UL and not for IEC applications.
1)
Data sheet | Current monitoring relays CM-SRS.2 - 7
Output circuits
Kind of output
1115-1216/1418
relay, 1st c/o (SPDT) contact
2125-2226/2428
relay, 2nd c/o (SPDT) contact
Operating principle
open-circuit principle (output relay energizes if the
measured value exceeds
b / falls below a the
adjusted threshold value)
Contact material
AgNi
Rated operational voltage Ue
250 V
Minimum switching voltage / Minimum switching current
24 V / 10 mA
Maximum switching voltage / Maximum switching current
250 V AC / 4 A AC
Rated operational current Ie
AC rating (UL 508)
AC-12 (resistive) at 230 V
4A
AC-15 (inductive) at 230 V
3A
DC-12 (resistive) at 24 V
4A
DC-13 (inductive) at 24 V
2A
utilization category (Control Circuit Rating Code)
max. rated operational voltage
max. continuous thermal current at B 300
max. making/breaking
B 300
300 V AC
5A
3600/360 VA
apparent power at B 300
Mechanical lifetime
30 x 106 switching cycles
Electrical lifetime
AC-12, 230 V, 4 A
0.1 x 106 switching cycles
Maximum fuse rating to achieve
n/c contact
10 A fast-acting
short-circuit protection
n/o contact
10 A fast-acting
General data
MTBF
on request
Duty time
100 %
Dimensions (W x H x D)
product dimensions
packaging dimensions
Weight
net weight
CM-SRS.21
CM-SRS.22
gross weight
CM-SRS.21
CM-SRS.22
22.5 x 85.6 x 103.7 mm (0.89 x 3.37 x 4.08 in)
97 x 109 x 30 mm (3.82 x 4.29 x 1.18 in)
Screw connection
Easy Connect
technology
Technology (Push-in)
Version 24-240 V AC/DC
0.152 kg (0.335 lb)
0.141 kg (0.311lb)
Version 110-130 V AC
0.179 kg (0.395 lb)
0.168 kg (0.370 lb)
Version 220-240 V AC
0.179 kg (0.395 lb)
0.168 kg (0.370 lb)
Version 24-240 V AC/DC
0.144 kg (0.318 lb)
-
Version 110-130 V AC
0.181 kg (0.399 lb)
-
Version 220-240 V AC
0.181 kg (0.399 lb)
-
Version 24-240 V AC/DC
0.174 kg (0.384 lb)
0.163 kg (0.359 lb)
Version 110-130 V AC
0.201 kg (0.443 lb)
0.190 kg (0.419 lb)
Version 220-240 V AC
0.201 kg (0.443 lb)
0.190 kg (0.419 lb)
Version 24-240 V AC/DC
0.166 kg (0.366 lb)
-
Version 110-130 V AC
0.203 kg (0.448 lb)
-
Version 220-240 V AC
0.203 kg (0.448 lb)
-
Mounting
DIN rail (IEC/EN 60715),
snap-on mounting without any tool
Mounting position
any
Minimum distance to other units
10 mm (0.39 in) at measured current > 10 A
Material of housing
Degree of protection
8 - Current monitoring relays CM-SRS.2 | Data sheet
UL 94 V-0
housing
IP50
terminals
IP20
Electrical connection
Connecting capacity
Screw connection
technology
Easy Connect
Technology (Push-in)
fine‑strand with(out)
1 x 0.5-2.5 mm²
2 x 0.5-1.5 mm²
wire end ferrule
(1 x 18-14 AWG)
(2 x 18-16 AWG)
2 x 0.5-1.5 mm²
(2 x 18-16 AWG)
rigid
1 x 0.5-4 mm²
2 x 0.5-1.5 mm²
(1 x 20-12 AWG)
(2 x 20-16 AWG)
2 x 0.5-2.5 mm²
(2 x 20-14 AWG)
Stripping length
8 mm (0.32 in)
Tightening torque
0.6 - 0.8 Nm
-
(7.08 lb.in)
Environmental data
operation -25...+60 °C (-13...+140 °F)
Ambient temperature ranges
storage -40...+85 °C (-40...+185 °F)
Damp heat, cyclic (IEC/EN 60068-2-30)
55 °C, 6 cycles
Vibration, sinusoidal
Class 2
Shock
Class 2
Isolation data
Rated insulation voltage Ui
supply / measuring circuit / output
600 V
output 1 / output 2
250 V
Rated impulse withstand voltage Uimp
supply / measuring circuit / output
6 kV 1.2/50 μs
output 1 / output 2
4 kV 1.2/50 μs
Pollution degree
3
Overvoltage category
III
Standards / Directives
Standards
IEC/EN 60947-5-1, IEC/EN 60255-27, EN 50178
Low Voltage Directive
2014/35/EU
EMC Directive
2014/30/EU
RoHS Directive
2011/65/EU
Railway application standards
EN 50155, IEC 60571
“Railway applications – Electronic equipment
used on rolling stock”
temperature class
supply voltage category
IEC/EN 61373
T3
S1, S2, C1
Category 1, Class B
“Railway applications – Rolling stock equipment – Shock and vibration tests”
EN 45545-2 Railway applications – Fire protection on railway vehicles – part 2:
HL3
Requirements for fire behavior of materials
and components
ISO 4589-2
LOI 32.3 %
NF X-70-100-1
C.I.T. (T12) 0.45
EN ISO 5659-2
Ds max (T10.03) 104
NF F 16-101: Rolling stock. Fire behaviour. Materials choosing
I2 / F2
NF F 16-102: Railway rolling stock. Fire behaviour. Materials choosing, application for
electric equipment
DIN 5510-2 Preventive fire protection in railway vehicles. Part 2: Fire behaviour and fire
fullfilled
side effects of materials and parts
Data sheet | Current monitoring relays CM-SRS.2 - 9
Electromagnetic compatibility
Interference immunity to
IEC/EN 61000-6-2
electrostatic discharge
IEC/EN 61000-4-2
Level 3
radiated, radio-frequency, electromagnetic field
IEC/EN 61000-4-3
Level 3
electrical fast transient / burst
IEC/EN 61000-4-4
Level 3
surge
IEC/EN 61000-4-5
Level 3
conducted disturbances, induced by
IEC/EN 61000-4-6
Level 3
radio-frequency fields
Interference emission
IEC/EN 61000-6-3
high-frequency radiated
IEC/CISPR 22, EN 55022
Class B
high-frequency conducted
IEC/CISPR 22, EN 55022
Class B
Technical diagrams
Load limit curves
V
300
V
300
V 200
resistive load
20
20
10
0.1
0.2
0.5
1
2
I
4
6
10
A
2CDC 252 194 F0205
100
80
60
50
40
30
AC load (resistive)
0.2
Switching cycles
0.9
0.8
0.7
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
cos ϕ
1
2
I
4
6
10
A
250 V
resistive load
2CDC 252 192 F0205
0.6
0.5
0.5
DC load (resistive)
1.0
F
10
0.1
Derating factor F for inductive AC load
Switching current [A]
Contact lifetime
10 - Current monitoring relays CM-SRS.2 | Data sheet
2CDC 252 193 F0205
resistive load
100
80
60
50
40
30
2CDC 252 148 F0206
V 200
Dimensions
in mm and inches
113.4 4.47”
105.9 4.17”
2CDC 252 009 F0011
85.6 3.37”
22.5 0.89”
103.7 4.08”
Accessories
in mm and inches
8 0.32”
4.8 0.19”
68 2.68”
11.5
0.453”
ADP.01 ‑ Adapter for screw mounting
MAR.12 ‑ Marker label for devices
with DIP switches
front to back
110.5 4.31”
2CDC 252 010 F0011
19.9
0.783”
2CDC 252 020 F0011
4T22
7.85
22.2
0.874”
0.309”
60 2.362”
70 2.756”
2CDC 252 008 F0010
62.5 2.461”
10
0.394”
20
0.787”
6.5
0.256”
22.5 0.89”
COV.11 ‑ Sealable transparent cover
Further documentation
Document title
Document type
Document number
Electronic products and relays
Technical catalogue
2CDC 110 004 C02xx
CM-SRS.1, CM-SRS.2
Instruction manual
1SVC 730 610 M0000
You can find the documentation on the internet at www.abb.com/lowvoltage
-> Automation, control and protection -> Electronic relays and controls -> Measuring and monitoring relays.
CAD system files
You can find the CAD files for CAD systems at http://abb-control-products.partcommunity.com
-> Low Voltage Products & Systems -> Control Products -> Electronic Relays and Controls.
Data sheet | Current monitoring relays CM-SRS.2 - 11
Contact us
Document number 2CDC 112 168 D0201 (07.2016)
ABB STOTZ-KONTAKT GmbH
P. O. Box 10 16 80
69006 Heidelberg, Germany
Phone: +49 (0) 6221 7 01-0
Fax: +49 (0) 6221 7 01-13 25
E-mail: info.desto@de.abb.com
You can find the address of your
local sales organisation on the
ABB home page
http://www.abb.com/contacts
-> Low Voltage Products and Systems
Note:
We reserve the right to make technical changes
or modify the contents of this document without
prior notice. With regard to purchase orders, the
agreed particulars shall prevail. ABB AG does
not accept any responsibility whatsoever for
potential errors or possible lack of information in
this document.
We reserve all rights in this document and in
the subject matter and illustrations contained
therein. Any reproduction, disclosure to third
parties or utilization of its contents – in whole
or in parts – is forbidden without prior written
consent of ABB AG.
Copyright© 2016 ABB
All rights reserved