Critical Power from GE
Compact Power Line
48V DC Critical Power Solution
Overview
Rectifier Options
The Compact Power Line platform
is designed to provide highly reliable
DC power for 48V distributed power
architectures. A single shelf configuration
provides up to 14kW of 48V output
power in 1U high and mounts in 19inch or 23-inch wide frames. The CPL
product platform is easily expandable
for future growth, and is a reliable DC
power solution for mission-critical
enterprise and telecommunications
network equipment.
CPL family of rectifiers are single phase,
constant power rectifiers with rear power
entry that provide from 2000 Watts to
3500 Watts of highly reliable DC power.
The class leading density, constant
output power characteristics, extended
temperature range, universal AC input,
and compact size are key attributes that
make this rectifier the right choice for
your power needs. CPL converters share
the same form factor as CPL rectifiers
and provide wide range 40V-72V DC
input and regulated 48-54V DC output.
Airflow direction is front to rear.
Shelf Options
The CP product line provides several
shelf options with common or split DC
output configurations. There are two
families of CPL shelves; one used with
a Pulsar Edge controller, the other used
without a controller or with a customer’s
own controller using industry standard
PMBus/I2C communications. J85480S1
and J2014003 shelves have four slots
for rectifiers or converters (PEMs) and
use PMBus/I2C for communications.
J2007001 and J2014004 shelves have
four slots with an additional space for
a full-feature Pulsar Edge Controller.
The Pulsar Edge controller has secure
Ethernet connectivity to facilitate
remote network management to
monitor and control rectifiers, batteries,
and distribution. CPL is ideal for a
broad range of applications requiring
highly efficient 48V DC power.
by high reliability Molex connectors. Up
to four modules can be installed in a
single 1RU shelf. The shelves support
3kW and 3.5kW power supplies.
Advantages
• Compact 48V DC
distributed power system
• Efficiency
approaching 97%
• Maximum power in
minimal space
Pulsar Edge Controller
• Scalable to 80 kW
CPL family of products support the
Pulsar Edge controller delivering
large system intelligence in a small
system form factor. Secure Ethernet
connectivity with SNMP helps facilitate
remote network management.
• Powering enterprise and
telecommunications
networks
Shelf Options
J85480S1 and J2007001 shelves provide
1RU rack density up to 11kW and support
appliance connector (C13 or C19) AC
connection options. The shelves support
2kW, 2.5kW and 2.7kW power supplies.
Up to four modules can be installed in a
single 1RU shelf. J2014003 and J2014004
shelves provide 1RU rack density up to
14kW with AC connectivity provided
CPL Power Supplies
The CPL series of rectifiers are specifically designed to operate as an integral
part of a complete distributed power system or can be easily integrated into
an OEM design. The high-density, front-to-back airflow rectifier is designed for
minimal space utilization and is highly expandable for future growth.
The power modules are available with many features including PoE isolation, RS485
communications bus for use with GE battery plant controllers in forming an energy
reserve system and redundant I2C communications bus for use with a customer’s
embedded controller. This flexible and sophisticated feature set makes this front
end power supply an excellent choice for power in a variety of application spaces.
Applications
• Enterprise Networks
• LAN/WAN/MAN Applications
• Broadcast
• OEM Telecom Equipment
• Indoor Wireless
• Test and Measurement
• Power Over Ethernet
• Routers and Switches
• Mission Critical
• VoIP/Soft Switches
• Industrial
• High Reliability
• SAN/NAS/iSCSI Applications
• Laser
Key Features
• Compact 1RU Form Factor
• Constant Power; 52 – 58 Vdc
• CE Marked
• PMBus Compliant Dual I2C and
RS485 Serial Bus Communications
• Programmable Output Voltage;
44 – 58 Vdc
• RoHS 6 Compliant
• Front Panel LED Indicators
• Universal AC Input
• Internal Variable-Speed Fan Control
• PoE Compliant Versions Available
• Hot Pluggable
Specifications: AC-DC Power Supplies
1
2
INPUT
2000
Voltage Range
- Low-Line
- High-Line
2725
3000
120Vac Nominal (1200W)
208, 240, 277Vac Nominal
120Vac Nominal (1500W)
208, 240, 277Vac Nominal
Input Frequency
47 – 63 Hz
47 – 66 Hz
Input Current
11.9 Arms @ 110Vac
13.1 Arms @ 240Vac
15.5 Arms @ 110Vac
16 Arms @ 240Vac
Inrush Transient
25Apk Typical
25Apk Typical
Power Factor
0.98 from 50% to 100% Load
0.97 Min, 0.995 Typical
Ride through (at 1240VAC, 25C)
1/2 Cycle Min, Full Cycle Typical
2
EMI/EMC
Exceeds FCC and CISPR22 (EN55022) - Class A
High Accuracy AC Measurement
No
3500
Optional
measurement starts at zero crossing of the ac voltage, and voltage devayed to 40V
for loads below 1200W
2
Compact Power Line, CPB-CPL | www.gecriticalpower.com
Specifications: AC-DC Power Supplies (Cont.)
OUTPUT
2000
Voltage Adjust Range
- Hardware set via Margin Pin
- Set by either I2C for
2725
3000
3500
44-58Vdc
42-58Vdc
Rated Output Current
- Low Line
- High Line1
25
38.4
25
52.4
28.9
57.8
28.9
67.3
Rated Output Power
- Low Line
- High Line
1200W
2000W
1200W
2725W
1500W
3000W
1500W
3500W
Psophometric Noise
9mVrms
Ripple (5Hz to 20MHz)
- RMS
- Peak to Peak
100mVrms max
250mVp-p max
Over Voltage Protection
- Delayed
- Immediate
1
65Vdc
Three restart attempts are implemented within a 1 minute window prior to a latched shutdown.
Over Temperature
- Warning
- Shutdown
- Restart Attempt Hys-
5C
20C
10C
PoE Isolation per IEEE 802.3
Optional
No
at full power @ 52V @ 200-240Vac
Specifications: DC-DC Power Supplies
OUTPUT
2000
Voltage Range
-40 to -72 Vdc
2500
Input Current
60Adc max
75Adc max
Inrush Current
60Adc max
100Adc max
Holdup Time
6ms
EMI/EMC
Exceeds FCC and CISPR22 (EN55022) - Class A
Voltage Default
54Vdc
Voltage Adjust Range
44 - 58 Vdc
Rated Output Current
0.1 to 37A
0.1 to 46.3A
Rated Output Power
2000W
2500W
Ripple (5Hz to 20MHz)
- RMS
- Peak to Peak
250mVrms
500mVpk-pk
Over Voltage Protection
- Delayed
- Immediate
60Vdc
65Vdc
Over Temperature
- Warning
- Shutdown
5C
20C
PoE Isolation
Yes
Yes
Specifications: All AC-DC Models and All DC-DC Models
MECHANICAL
Length (in./mm)
13.85 / 351.2
Width (in./mm)
4 / 101.6
Height (in./mm)
1.63 / 41.4
Weight (lb / kg)
5 / 2.27
Compact Power Line, CPB-CPL | www.gecriticalpower.com
3
Specifications: All AC-DC Models and All DC-DC Models (Cont.)
1
ENVIRONMENTAL
2000/2725
3000/3500
Operating Temperature1
-40°C to +75°C (-40°F to 167°F)
-40°C to +55°C (-40°F to 131°F)
Storage Temperature
-40°C to +85°C (-40°F to 185°F)
Power De-Rating
> +55°C (derates @ 2% per °C)
Relative Humidity
95% max, non-condensing
Altitude
4,000m max (13,000 ft)
Altitude De-Rating
Above 1524/5000 m/ft; 3962/13000 m/ft max (derates at 2C/1000ft)
Audible Noise
55dBA, full load
designed to start at an ambient as low as -40°C but may not meet operational limits until above -5°C
GENERAL
2000/2725
Cooling
Internal variable speed fan cooled, microprocessor fan speed control
3000/3500
Air Flow Direction
Front to Rear
Efficiency (30-80% of FL, 240VAC @ 25°C)
94.5% Min
96.5% Typical
94.2% Min
96.1% Typical
Heat Dissipaation
AC-DC 2000/2725 100 W/341 BTU @ 80% load
153 W/522 BTU @ 100% load
AC-DC 3000/3500 190 W/648 BTU @ 80% load
250 W/853 BTU @ 100% Load
DC-DC 2000 -> 176W / 601 BTU
2500 -> 220W / 751 BTU
SAFETY AND STANDARDS COMPLIANCE
2000/2725
Zone 4
Per Telcordia GR-63-CORE, all floors when installed in CPL shelf
3000/3500
Safety
CE mark to Low Voltage Directive 2006/95/EC UL 609501-1 Recognized
CAN/CSA C22.2 No. 60950-1-03 Certified VDE 0805-1 Licensed to IEC60950-1
RoHS
Compliant to RoHS EU Directive 2002/95/EC
EMC
FCC and CISPR22 (EN 55022) Class A
ESD
EN/IEC 61000-4-2 Level 3
Front Panel LEDs
SYMBOL
ANALOG MODE
I2C MODE
RS485 MODE
ON: Input OK
BLINKING: Input Out of Limits
ON: Output OK
BLINKING: Overload
ON: Over-temperature Warning
ON: Over-temperature Warning
BLINKING: Service
ON: Fault
ON: Over-temperature Warning
ON: Fault
BLINKING: Not Communicating
Outline Drawings
DIMENSIONS
4
Compact Power Line, CPB-CPL | www.gecriticalpower.com
Pulsar Edge Controller (For Applications in J2007001
and J2014004 shelves)
The CPL Pulsar Edge controller delivers large system intelligence in a small system form factor. This family of
controllers functions as a network interface controller (NIC) and as a full-featured battery plant controller to the
Compact Power Line (CPL) platform. Its thin modular plug-in form factor minimizes shelf space. The Pulsar Edge
CP841A controller is utilized in bulk power applications in data centers and enterprise applications.
Ethernet connectivity with SNMP facilitates remote network management access through its
front-accessible RS232 or USB port and is aided by the EasyView2 graphical user interface.
As a battery plant controller, it provides a complete set of features to monitor and control rectifiers,
batteries, and distribution. A flexible set of configurable inputs allow the CP841A to monitor a wide
variety of system equipment and incorporate appropriate state information enabling a centralized point
of management. The controller utilizes secure network management protocols allowing for advanced network
supervision. GE Galaxy Manager* software is the centralized visibility and control component of a comprehensive
power management system designed to meet engineering, operations, and maintenance needs. The Galaxy Manager
client-server architecture enables remote access to system controllers across the power network.
Applications
• Telecommunications Networks
• Routers/Switches
• Transmission Equipment
• Data Networks
• Fiber in the Loop
• PBX
- N + X redundancy check
Key Features
Remote Access and Features
• Integrated 10/100Base-T Ethernet
Network
- TCP/IP
- SNMP V2c for management
- SMTP for email
- Telnet for command line interface
- DHCP for plug-n-play
- FTP for rapid backup and upgrades
- HTTP for standard web pages
and browsers
- Compatible with Galaxy Manager
and other management packages
- Shielded RJ-45 interface
referenced to chassis ground
• Password protected security levels:
User, Super-User, Administrator for
all access Ground-referenced RS232
system port ANSI T1.317 commandline interface
• Modem access support
- Remote via external modem
- Callback security
• EasyView2, Windows-based GUI
software for local terminal or
Modem access
• Enterprise Networks Voice, Data, PoE
• Secure Protocols:
- SNMP V3
- SSL
- SSH
- IPv6
Standard System Features
• Monitor and control of more than 40
connected devices
- Maximum of 32 rectifiers
- Maximum of 6 distribution
control cards
- Robust RS485 system bus
• Standard and user defined
system alarms
- Alarm test
- Assignable alarm severity:
Critical, Major, Minor, Warning,
and Record-only
• Rectifier management features
- Automatic rectifier restart
- Active Rectifier Management
(energy efficiency)
- Remote rectifier (on/off)
- Reserve Operation
- Automatic rectifier
sequence control
Compact Power Line, CPB-CPL | www.gecriticalpower.com
5
• Multiple Low Voltage Load and
Low Voltage Battery Disconnect
thresholds (4)
• Configuration, statistics, and history
- All stored in non-volatile memory
- Remote/local backup and restore
of configuration data
• Industry standard defaults
- Customer specific
configurations available
• Remote/ local software upgrade
• Basic, busy hour, and trend statistics
• Detailed event history
• User defined events and
derived channels
Standard Battery Management Features
• Float/boost mode control
- Manual boost
- Manual timed boost locally, T1.317,
and remotely initiated
- Auto boost terminated by time
or current
• Battery discharge testing
- Manual (local/remote)
- Periodic
6
Compact Power Line, CPB-CPL | www.gecriticalpower.com
Pulsar Edge Controller Key Features (Cont.)
Integrated Monitoring Inputs/Outputs
- Plant Battery Test (PBT)
input driven
• System plant voltage (accuracy ±0.5%,
- Configurable threshold or
resolution 0.01V)
20% algorithm
• One system shunt (accuracy ±1% full
- Graphical discharge data
scale, resolution 1A)
- Rectifiers on-line during test
- Battery or load
• Slope thermal compensation
- Mounted in the return side
- High temperature
of DC bus
- Low temperature
• Up to 15 binary inputs
- Step temperature
- Six inputs close/open to battery
- STC Enable/Disable,
- 9 input close/open to return
low temperature
(number is dependent upon
Enable/Disable
number of output alarms)
- Configurable mV/°C slopes
- User assignable
• State of charge indication
• Up to 5 user assignable Form-C
• High temperature disconnect setting
output alarms (50VDC @ .3A)
• Reserve-time prediction
• 1-Wire* bus devices
• Recharge current limit
• Emergency Power-Off input
- Up to 16 temperature
probes (QS873)
- Up to 6 mid-string monitors (ES771)
Galaxy Manager Compatible
• Centralized web server and database
with multiple user access to live or
managed data with drill down to
problem details
• Monitor and control of more than 40
connected devices
• Management information from polling
or alarms received from alarm traps
from multiple sites are available on
one screen via the inter/intranet
• Trend user selected data over time
• Automatic or manual
report generation
• Standard engineering tools like
reserve time calculators and cable
voltage drop analyzer
Specifications
CONTROLLER GENERAL
Operating Voltage
±24 Vdc, ±48 Vdc
(Range: ±18 to ±60 Vdc)
Input Power
Less than 7W
Operating Temperature Range
-40°C to +75°C (-40°F to 167°F)
Storage Temperature Range
-40°C to +85°C (-40°F to 185°F)
Operating Relative Humidity
0 - 95% (non-condensing)
Physical Specifications
1.75 in. H, 0.75 in. W, 8.00 in. D; 0.5lb
45mm H, 20mm W, 204mm D; 227g
CONTROLLER AGENCY CERTIFICATIONS
Radiated Emissions
FCC, Class B; EN 55022, Class B
Safety
UL Unlisted Component as Part of CPL or SPS Power System
RoHS
Compliant to RoHS EU Directive 2002/95/EC
EMC
FCC/EN55022 Class B, CISPR22 Level B
ESD
EN 61000-4-2 level 4
Compact Power Line, CPB-CPL | www.gecriticalpower.com
7
Ordering Information – Compact Power Line
48V DC Critical Power Solution
The Compact Power Line platform is designed to provide highly reliable DC power for 48V distributed power architectures. When embedded into
an OEM design, GE can assist with the integration into the OEM design, Otherwise an external shelf can be used to provide power. A single shelf
configuration provides up to 14kW of 48V output power in 1U high and mounts in 19-inch or can be adapted to 23-inch wide frames. The CPL product
platform is easily expandable for future growth by stacking multiple shelves. CPL is a reliable DC power solution for mission-critical enterprise and
telecommunications network equipment.
The CPL product line provides several shelf options. J85480S1 and J2014003 shelves have four slots for either rectifiers or converters (PEMs). These
shelves are primarily used without a controller or with a customer’s controller using PMBus or I2C communications. J2007001 and J2014004 shelves
have four slots with space for a full-feature Pulsar Edge Network Interface Controller (NIC). The Pulsar Edge controller has secure Ethernet connectivity
with SNMPv3 to facilitate remote network management to monitor and control rectifiers, batteries, and distribution. These shelves are used with
either shelf mounted distribution or external distribution panels for small battery plant applications.
Simplified Shelf Identification Matrix
SHELF SERIES
USAGE
COMMUNICATIONS
POWER SUPPLY INPUT CONNECTOR
J85480S1
CP2000/CP2725
PM Bus/I2C
Rear
J2007001
CP2000/CP2725
RS485
Rear
J2014004
CP3000/CP3500
RS485
Rear
J2014003
CP3000/CP3500
PM Bus/I2C
Rear
Embedded Only
CP3000AC-Fxx
PM Bus/I2C or RS485
Front
Embedded Only
CP2500DC-Fxx
2
PM Bus/I C or RS485
Front
Features – Model J85480S1 and J2014003
• Fits into a standard 19” rack
• Two DC Outputs may be common or split. Each output bus is
rated for 100A with two-hole lug landings for 2 AWG wire.
• Choose between IEC-320 C13 or C19 or other AC input connections
J2007 or J2014004
Rectifier Shelf
• Analog or dual/redundant I2C communications
• Adjustable mounting ears for near flush front or multiple set back positions
Features – Model J2007001 and J2014004
• Fits into a standard 19” rack
J2007 Converter Shelf
• Single DC output rated for 200A with two-hole
lug landings for up to 2/0 AWG cable
• Choose between IEC-320 or Molex Mini-Fit SR for AC input
Single, dual or quad input feeds
• RS485 communications
• Adjustable mounting ears with multiple set back positions
J85480 or J2014003
Rectifier Shelf
• Up to 3 shelves may be interconnected with bus
straps for DC outputs for a 600A system
• Plug-N-Play CP841A controller with front access craft
port, rear access LAN and alarm connections
• Select Shelves include distribution modules
8
J85480 Converter Shelf
Compact Power Line, CPB-CPL | www.gecriticalpower.com
Outline Drawings - J85480S1 Shelves
DIMENSIONS
J8540S1 Converter Shelf Options
LIST
14
MAX
POWER
DC INPUT
PLUG
DC OUTPUT
BUS
TERMINATION
10kW
Qty 2 (1 per
2 rectifiers)
Split
Double Hole Lugs
1/4in x 5/8in Spacing
MAX POWER
SUPPLY
FEATURES
SETPOINT
OTHER
ORDER CODE
CP2500DC
(+) 48Vdc
POE, Analog, I2C
CC109124764
J85480S1 Rectifier Shelf Options
LIST
20
MAX
POWER
AC INPUT
PLUG
DC OUTPUT
TERMINATION
MAX
RECTIFIER
SIZE
FEATURES
BUS
SETPOINT
OTHER
11kW
IEC-320, C19
Common
DH Lugs
CP2725
(+) 54Vdc
Analog, I2C
21
23
Split
8kW
IEC-320, C13
Common
ORDER CODE
CC109147344
-54Vdc
CP2000
(+) 54Vdc
CC109147328
2
POE, Analog, I C
CC109150447
Notes
• Split shelves L21 and Vout (-) is split, however Vout (+) is paralleled among the 4 rectifiers. Vout (+) should be grounded.
• All lists, up to 2 shelves can be paralleled for a single I 2C line. Up to eight shelves may be paralleled for current shared power delivery.
• All lists, shelf configured set point ensures inter-operability among all rectifiers from CP2000 to CP2725. Rectifiers will proportionately current share relative
to their output power capacity.
• All Shelves are RoHS 6 compliant. Order should reflect J85480S1LxxZ where xx is the list number and Z indicates compliance to RoHS 6.
Compact Power Line, CPB-CPL | www.gecriticalpower.com
9
Outline Drawings - J2014003 Shelves
DIMENSIONS
J2014003 Rectifier Shelf Options
LIST
1
10
MAX
POWER
AC INPUT
CONNECTOR
DC OUTPUT
BUS
TERMINATION
FEATURES
RECTIFIER SIZE
SET POINT
14kW
Molex Mini-Fit Sr
Common
Double Hole Lugs
1/4in x 5/8in Spacing
CP3000/
CP3500
54Vdc
OTHER
ORDER CODE
Analog I2C
150040608
Compact Power Line, CPB-CPL | www.gecriticalpower.com
DC Output Types: Common Output Bus for Terminal Lug Connection
Rectifier 4
Rectifier 3
Rectifier 2
Rectifier 1
SCHEMATIC
DC Output Types: Split Output Bus for Terminal Lug Connection
Compact Power Line, CPB-CPL | www.gecriticalpower.com
Rectifier 4
Rectifier 3
2 hole 1/4” studs
Rectifier 2
Multiple shelves may not be paralleled together.
Rectifier 1
SCHEMATIC
2 hole 1/4” studs
11
J1 Communication Signals – J85480S1 (J1 Connector – Pin Out)
PIN
SIGNAL
PIN
SIGNAL
1
POWER_CAP_1
16
SDA_1
2
POWER_CAP_2
17
Fault
3
POWER_CAP_3
18
Alert#_0
4
POWER_CAP_4
19
Enable side B
5
MOD_PRES_1
20
Logic_GRD
6
MOD_PRES_2
21
Enable Side A
7
MOD_PRES_3
22
Logic_GRD
8
MOD_PRES_4
23
Alert#_1
9
PFW_1
24
5VA
10
PFW_2
25
OTW
11
PFW_3
26
Reset
12
PFW_4
27
Iso. barrier n/c
13
SCL_0
28
Iso. barrier n/c
14
SCL_1
29
Shelf_Addr_B
15
SDA_0
30
Shelf_Addr_A
PHOTO
Control Interface cable (part # CC848854034)
J2 Communication J85480S1 and J2014003 Shelves (J2 Connector – Pin Out)
PIN
SIGNAL
PIN
SIGNAL
1
SCL_0
8
Alert#_1
2
SCL_0
9
Isolation n/c
3
SDA_0
10
Isolation n/c
4
SDA_1
11
Ishare - B
5
Alert#_0
12
Ishare - A
6
5VA
13
8V_INT - B
7
Logic_GRD
14
8V_INT - A
PHOTO
Shelf-to-shelf cable connection (part # CC848848952)
J1 Communication Signals – J2014003 Shelves (J1 Connector – Pin Out)
PIN
SIGNAL
PIN
SIGNAL
1
POWER_CAP_1
16
SDA_1
2
POWER_CAP_2
17
Fault
3
POWER_CAP_3
18
Alert#_0
4
POWER_CAP_4
19
Enable side B
5
MOD_PRES_1
20
Logic_GRD
6
MOD_PRES_2
21
Enable Side A
7
MOD_PRES_3
22
Logic_GRD
8
MOD_PRES_4
23
Alert#_1
9
PFW_1
24
5VA
10
PFW_2
25
OTW
11
PFW_3
26
Reset
12
PFW_4
27
Iso. barrier n/c
13
SCL_0
28
Iso. barrier n/c
14
SCL_1
29
VProg
15
SDA_0
30
Rack ID
PHOTO
Control Interface cable (part # CC848854034)
12
Compact Power Line, CPB-CPL | www.gecriticalpower.com
Outline Drawings - J2007001 Shelves
DIMENSIONS
J2007001L14 DC PEM Shelf Options
LIST
14
MAX
POWER
DC INPUT
PLUG
DC OUTPUT
BUS
TERMINATION
10kW
2 x 1/4-20 x
5/8 in DH Lug
Common
2 x 1/4-20 x 5/8 in
DH Lug
MAX POWER
SUPPLY
FEATURES
SETPOINT
OTHER
ORDER CODE
CP2500DC
Variable, set by
Edge Controller
RS485
CC109157657
J2007001 Rectifier Shelf Options
LIST
MAX RECTIFER SIZE
AC INPUT
DC OUTPUT
3
2725 Watts
Single AC feed
(terminal blocks for
6ga wire and 3/4”
conduit fitting)
4
2725 Watts
Individual feed
(Molex Mini-Fit SR)
DC output bus is
rated for 200A for
two 2ga or one
2/0 gauge
two- hole lugs
(1/4-20 studs on
5/8” centers).
6
2725 Watts
Individual feed
(IEC-320 C19 Cords)
REAR VIEW OF SHELF
DC Output Bus
AC
Signal
Notes:
1. CP841A Pulsar Edge Controller ships separately.
2. Up to 3 shelves may be interconnected.
Compact Power Line, CPB-CPL | www.gecriticalpower.com
13
Outline Drawings - J2014004 Shelves
DIMENSIONS
J2014004 Rectifier Shelf
LIST
1
MAX
POWER
AC INPUT
PLUG
DC OUTPUT
BUS
TERMINATION
14kW
Molex Mini
Fit Sr
Common
2pr x 1/4-20 x 5/8 in
DH Lug
MAX POWER
SUPPLY
FEATURES
SETPOINT
OTHER
ORDER CODE
CP3500
Variable, set by
Edge Controller
RS485
150040609
Notes: 1. CP841A Pulsar Edge Controller ships separately. 2. Up to 3 shelves may be interconnected.
14
Compact Power Line, CPB-CPL | www.gecriticalpower.com
J2007001 and J2014004 Shelves System Controller Overview
EDGE CONTROLLER
CP841A_3C3R_S
PHOTO
J1 has 3 alarm inputs with a common return
and 3 output relays; Power Major,
Power Minor, 1 Selectable
Communication Signals for J2007001 and J2014004 Shelves
J1 provides alarm outputs and inputs based on the controller installed (see
table on next page). Inputs are “Dry”, no voltage, contact Closures or Opens
to a common return on pin 6. Outputs are relay contacts. Both input and
output alarms are customer defined on the controller’s web pages.
J2 provides alarm inputs (see table on next page). Alarm inputs
are contact Closures or Opens to the non-grounded side of the dc
bus [-48V]. Pins 6, 7, 8 provide -48V for these alarm inputs.
J3 battery thermal probe (QS873A) or battery mid-string
voltage monitor (ES771) with battery thermal probe.
J4 shelf to shelf communication connection J5 LAN/Ethernet.
J7 provides distribution control for shelves with external
distribution. See table on next page.
J1 Connector – Pin Out
PIN
SIGNALS FOR SPS841A_3C3R
SIGNALS FOR SPS841A_0I5R
1
ALM1 Input
Alarm Relay 3 Rtn
2
ALM2 Input
Alarm Relay 2 Rtn
3
Alarm Relay 1 Rtn
Alarm Relay 1 Rtn
4
Power Minor Rtn
Power Minor Rtn
5
Power Major Rtn
Power Major Rtn
6
ALM1, 2, 6C RTNS
Alarm Relay 3
7
ALM6 Input
Alarm Relay 2
8
Alarm Relay 1
Alarm Relay 1
9
Power Minor
Power Minor
10
Power Major
Power Major
Compact Power Line, CPB-CPL | www.gecriticalpower.com
15
J2 Connector
ALM6 Input
ALM3 Input
ALM4 Input
ALM5 Input
J7 Connector
LVD_NO
Coil1
Coil2
Battery Monitoring
Temperature/Voltage probes are needed for battery monitoring. They are connected to each battery or battery string
to provide slope thermal compensation, temperature alarms and voltage imbalance alarms.
Refer to ordering guide for diagram and part numbers.
16
Compact Power Line, CPB-CPL | www.gecriticalpower.com
CP2000/CP2725 Shelves
J85480S1 Family Shelves Ordering Guide
MOUNTING BRACKETS
1U bracket for 23”
frame mount
CC848844803
2U bracket for 23”
frame mount
848683009
Wall mount bracket
COMMUNICATION CABLES
AC INPUT, DC OUTPUT CABLES
10’ Communication
Cable (J1)
CC848854034
C13 plug with 5-15P plug, 10’
CC848776105
C13 plug with L6-20P plug, 10’
CC848820317
Shelf to shelf
communication cable
CC848848952
C13 plug, unterminated, 10’
847861192
C19 plug, with 5-15P plug, 8’
CC848850792
C19 plug, with L6-20P plug, 8’
CC848850842
C19 plug, unterminated, 8’
CC848847368
DC output cable, 2 GA, 10’
848748987
CC848864504
AC
DC
RECTIFIER SHELF OPTIONS
RECTIFIER
List 20
CC109147344
CP2000AC54TEZ
CC109158440
RECTIFIER SLOT FILLER
List 21
CC109147328
CP2000AC54TEP
CC109167565
List 23
CC109150447
CP2725AC54TEP
CC109167532
CP2725AC54TEZ
CC109149423
Central
Office White
CC848822263
J85480S1 Converter Shelf Ordering Guide
DC INPUT CABLES
MOUNTING BRACKETS
DC OUTPUT CABLES
1U bracket for 23”
frame mount
CC848844803
DC output cable, 2 GA 10’
848748987
CC848864504
DC Bus for 1/4” Faston Connections
(2 required)
CC848886192
Wall mount bracket
CONVERTER (PEM) OPTIONS
CONVERTER SHELF OPTIONS
CP2000DC54PEZ
CC109162104
CP2500DC54PEZ
CC109170528
RECTIFIER SLOT FILLER
Compact Power Line, CPB-CPL | www.gecriticalpower.com
17
Central Office
18
Compact Power Line, CPB-CPL | www.gecriticalpower.com
CP2000/CP2725 Shelves (Cont.)
J2007001 Family Shelves Ordering Guide
ALARM AND COMMUNICATION CABLES
MOUNTING BRACKETS
1U bracket for 23”
frame mount
CC848844803
2U bracket for 23”
frame mount
848683009
Wall mount bracket
CC848864504
CONTROLLER
AC INPUT, DC OUTPUT CABLES
15’ Alarm or distribution cable (J1 or J7)
CC848865980
C19 plug, with 5-15P plug, 8’
CC848850792
50’ Alarm or distribution cable (J1 or J7)
CC848817651
C19 plug, with L6-20P plug, 8’
CC848850842
150’ Alarm or distribution cable (J1 or J7)
CC848817668
C19 plug, unterminated, 8’
CC848847368
15’ Alarm input cable (J2)
CC848853614
CC848847780
Molex Mini-Fit SR, unterminated,
8awg, 10’ (2 cables provided)
848710711
Shelf to shelf communication cable (J3, J4)
DC output cable, 2ga, 10’
848748987
DC Bus Bar Strap (2 required)
CC848844324
RECTIFIER
RECTIFIER SLOT FILLER
RECTIFIER SHELF OPTIONS
CP841A_3C3R_S
150032047
CP2000AC54TEZ
CC109158440
List 3
CC109147542
Slot Filler
CC848847871
CP2000AC54TEP
CC109167565
List 4
CC109140043
CP2725AC54TEP
CC109167532
List 6 (Shown)
CP2725AC54TEZ
CC109149423
CC109140027
(Rohs5)
150047190
(Rohs6)
J2007001L014 Converter Shelf Ordering Guide
MOUNTING BRACKETS
DC OUTPUT CABLES
1U bracket for 23”
frame mount
CC848844803
DC output cable, 2 GA 10’
848748987
DC Bus for 1/4” Faston Connections (2 required)
CC848886192
Wall mount bracket
CC848864504
CONVERTER SHELF OPTIONS
CONVERTER (PEM) OPTIONS
CONTROLLER
CP841A_3C3R_S
150032047
Slot Filler
CC848847871
RECTIFIER SLOT FILLER
CP2000DC54PEZ
CC109162104
CP2500DC54PEZ
CC109170528
RECTIFIER SLOT FILLER
Central
Office White
Compact Power Line, CPB-CPL | www.gecriticalpower.com
19
CP3000/CP3500 Shelves
J2014003 Shelf Ordering Guide
MOUNTING BRACKETS
AC INPUT, DC OUTPUT CABLES
1U bracket for 23”
frame mount
CC848844803
Molex Mini-Fit SR, unterminated, 8awg, 36” (Single Cable)
CC848763301
Molex Mini-Fit SR, unterminated, 8awg, 10’ (Single Cable)
CC848793026
2U bracket for 23”
frame mount
848683009
Molex Mini-Fit SR, unterminated, 8awg, 10’ (2 cables provided)
848710711
DC output cable, 2ga, 10’
848748987
DC Bus Bar Strap (2 required)
CC848844324
Wall mount bracket
CC848864504
RECTIFIER SLOT FILLER
RECTIFIER
RECTIFIER SHELF OPTIONS
CP3000AC54TEZ
150033916
CP3000AC54TECZ
150041904
CP3500AC54TEZ
150030396
CP3500AC54TECZ
150041901
J2014003001
List 1
150040608
J2014004 Shelf Ordering Guide
AC INPUT, DC OUTPUT CABLES
MOUNTING BRACKETS
ALARM AND COMMUNICATION CABLES
1U bracket for 23”
frame mount
CC848844803
15’ Alarm or distribution cable (J1 or J7)
CC848865980
50’ Alarm or distribution cable (J1 or J7)
CC848817651
Wall mount bracket
CC848864504
150’ Alarm or distribution cable (J1 or J7)
CC848817668
15’ Alarm input cable (J2)
CC848853614
Shelf to shelf communication cable (J3, J4)
CC848847780
SHELF OPTIONS
CONTROLLER
20
RECTIFIER
RECTIFIER SLOT FILLER
CP3000AC54TEZ
150033916
CP3000AC54TECZ
150041904
CP3500AC54TEZ
150030396
CP3500AC54TECZ
150041901
Molex Mini-Fit SR, unterminated,
8awg, 36” (Single Cable)
CC848763301
Molex Mini-Fit SR, unterminated,
8awg, 10’ (Single Cable)
CC848793026
Molex Mini-Fit SR, unterminated,
8awg, 10’ (2 cables provided)
848710711
DC output cable, 2ga, 10’
848748987
DC Bus Bar Strap (2 required)
CC848844324
RECTIFIER SHELF OPTIONS
Compact Power Line, CPB-CPL | www.gecriticalpower.com
CP841A_3C3R_S
150032047
Slot Filler
CC848847871
Compact Power Line, CPB-CPL | www.gecriticalpower.com
21
BATTERY MANAGEMENT ACCESSORIES
PHOTO
A: QS873A Thermal Probe
CC109142980
B: 10’ probe to controller wireset
CC848817024
C: 1’ probe to probe wireset
CC848822560
C: 5’ probe to probe wireset
848719803
C: 10’ probe to probe wireset
CC848822321
ES771A Voltage Monitor Card
108958422
D: 2 1/2’ ES771A to probe wireset
CC848791517
D: 6’ ES771A to probe wireset
CC848797290
D: 10’ ES771A to probe wireset
848719829
G: 4’ ES771A to ES771A or controller wireset
CC848791500
G: 10’ ES771A to ES771A or controller wireset
848652947
Specifications
Rectifiers
POWER MODULE
OUTPUT POWER/INPUT VOLTAGE
OUTPUT VOLTAGE
PROTECTION
PHYSICAL
CP2000AC54TEZ/TEP
2000W / 200-277VAC
1200W / 100-120VAC
15A breaker, 14 gauge wire
CP2500DC54PEZ
2500W / 40-72VDC
Hardware set
44 - 58Vdc
Software set
42 - 58Vdc
Length: 13.85”/351.8mm
Width: 4.00”/101.6mm
Height: 1.66”/42.2mm
Weight: 4.6lb/2.1kg
CP2725AC54TEZ/TEP
2725W / 200-277VAC
1200W / 100-120VAC
20A breaker, 12 gauge wire
CP2000DC54-PEZ
2000W / 40-72VDC
60A breaker, 8 gauge wire
CP3000AC54TEZ/TECZ
3000W / 200-277VAC
1500W / 100-120VAC
30A breaker, 10 gauge wire
CP3500AC54TEZ/TECZ
3500W / 200-277VAC
1500W / 100-120VAC
20A breaker, 12 gauge wire
70A breaker, 8 gauge wire
Notes: PE suffix denotes PoE compliance. Z suffix denotes RoHS 6 compliance. TE suffix denotes Total Efficiency* architecture.
Shelves
MECHANICAL
J85480S-1
J2014003
J2007001L014
J2007001
J2014004
Height
1.71 inches/43.4mm
1.71 inches/43.4mm
1.71 inches/43.4mm
1.71 inches/43.4mm
1.71 inches/43.4mm
Width (with mounting ears)
19 inches/483mm
19 inches/483mm
19 inches/483mm
19 inches/483mm
19 inches/483mm
Depth
16.25 inches/413mm
17.25 inches/438mm
19.5 inches/497mm
17.06 inches/433mm
16.9 inches/429mm
Weight (without rectifiers)
9.25lbs/4.2kg
9.5lbs/4.3kg
9.5lb/4.3kg
8.75lbs/4.0kg
9lbs/4.1kg
Note: dimensions of specific model numbers may vary
22
Compact Power Line, CPB-CPL | www.gecriticalpower.com
Reliability
• Proven field performance
• Advanced alarming
• N+1 modularity
Intelligence
• Industry leading controller features
Management Visibility
Galaxy Manager* software is the centralized visibility and control component
of a comprehensive power management system designed to meet engineering,
operations and maintenance needs. The Galaxy Manager client-server architecture
enables remote access to system controllers across the power network.
• Dashboard display with one-click access to
management information database
• Ethernet interface for
remote access
• Trend analysis
• Centralized network management
• Fault, configuration, asset, and performance management
• Scheduled or on demand reports
Investment Protection
• Minimal space requirements
• Versatile configurations
Training
• Efficient operation
GE offers on-site and classroom training options based on certification curriculum.
Technical training can be tailored to individual customer needs. Training enables
customers and partners to more effectively manage and support the power
infrastructure. We have built our training program on practical learning objectives
that are relevant to specific technologies or infrastructure design objectives.
On Time Delivery
• Standard building blocks
• 8-16 week availability
• 24/7 support
Service & Support
GE field service and support personnel are trusted advisors to our customers
– always available to answer questions and help with any project, large or
small. Our certified professional services team consists of experts in every
aspect of power conversion with the resources and experience to handle
large turnkey projects along with custom approaches to complex challenges.
Proven systems engineering and installation best practices are designed
to safely deliver results that exceed our customers’ expectations.
Warranty
GE is committed to providing quality products and solutions. We have
developed a comprehensive warranty that protects you and provides a
simple way to get your products repaired or replaced as soon as possible.
For full warranty terms and conditions please go to
www.gecriticalpower.com.
Critical Power from GE
601 Shiloh Road
*Registered trademark of the General Electric Company.
The GE brand, logo, and lumination are trademarks of the General Electric Company. © 2016 General Electric Company.
Plano, TX 75074
Information provided is subject to change without notice. All values are design or typical values when measured under
laboratory conditions.
+1 877 546 3243
CPB-CPL, Rev. 12/2020
www.gecriticalpower.com
Compact Power Line, CPB-CPL | www.gecriticalpower.com
23