Low voltage AC drives
ABB micro drives
ACS150
0.37 to 4 kW/0.5 to 5 hp
Catalog
Introduction to ACS150
ABB micro drives
ABB micro drives are designed to be incorporated into a wide
variety of machines such as mixers, conveyors, fans or pumps
or anywhere where a fixed speed motor needs to go variable
speed motor.
The ABB micro drives meet the requirements of OEMs,
machinery builders and panel builders. These drives are
widely available through the ABB distribution network. The
drives are easy to select and provide a range of built-in
features as standard including PID control, brake chopper,
fixed keypad and speed control potentiometer.
Highlights
– Worldwide availability through logistical distributors
– User-friendly LCD control panel and integrated
potentiometer
– Flexible mounting alternatives
– PID control
– Integrated EMC filter
– Built-in brake chopper
– FlashDrop tool for fast drive commissioning
Feature
Advantage
Benefit
Worldwide availability and service
Drives are available worldwide and permanently stocked in four
Fast and reliable delivery with dedicated
regions.
support to any country in the world.
Dedicated global service and support network that is one of the
widest in the industry.
User-friendly LCD control panel and
Clear alphanumeric display. Easy setup and use.
integrated potentiometer
Flexible mounting alternatives
Time savings due to quick setup and simple
configuration.
Screw or DIN rail mounting, sideways or side-by-side.
One drive type can be used in various
designs, saving installation costs and time.
Integrated EMC filter
High electromagnetic compatibility.
Low EMC emissions in selected environments.
Built-in brake chopper as standard
No need for an external brake chopper.
Space savings, reduced installation cost.
FlashDrop tool
Faster and easier drive setup and commissioning for volume
Fast, safe and trouble-free parameter setting
manufacturing and maintenance. The FlashDrop tool enables
without the need to power-up the drive.
both downloading and uploading drive parameters.
Patented.
Varies the drive’s performance according to the need of the
Enhances production output, stability and
application.
accuracy.
Board coating protects the electronics from hazards including
Reduces maintenance due to good protection
static discharge and airborne contaminates, including moisture.
of electronics components.
PID control
Coated boards
2 ABB micro drives ACS150 | Catalog
Easily integrated drives for a wide range of applications
ABB micro drives bring speed control benefits to a wide
variety of applications.
In mixing applications the drive provides high starting torque
which benefits the start of the mixing operation. The silent
operation mode adjusts the switching frequency of the drive
to a higher level after the high-torque start, resulting in lower
audible noise. The FlashDrop tool provides a quick and safe
way to configure multiple drives for identical mixer applications.
In conveyors the belt speed can be controlled using a drive
and a motor. Production lines often have multiple stages,
including conveyors, which need to be efficiently linked with
each other to provide high production output. A drive provides
smooth start and stop of the conveyor, thereby reducing
mechanical stress and lowering maintenance costs.
A heat pump system consists of an indoor unit with fan and
an outdoor unit with a compressor and a blower. The heat
pump cools indoor environment by gathering heat from the air,
and transferring the heat outside. The outdoor unit uses the
compressor and the blower to dissipate the heat. The cooled
air is blown indoors by fans located in the indoor unit. Drive
allows the user to variably control the cooling power based
on customer request. AC drives optimizes systems’ energy
efficiency and smoothens system operation.
Fans are used for process cooling and ventilation in industrial,
commercial and domestic environments. Using a drive to
control air flow enables energy savings compared to mechanical
flow control methods. An ABB drive has integrated PID control
which provides optimal air flow by adjusting the fan speed
based on a given reference value. Compact size and various
mounting methods enable flexible system design.
Catalog | ABB micro drives ACS150 3
Ratings, types and dimensions
Type designation
In column 4 on the right is the unique reference number that
clearly indentifies your drive by power rating and frame size.
Once you have selected the type designation, the frame size
(column 5) can be used to determine the drives dimensions,
shown below.
Voltages
ACS150 is available in two voltage ranges:
Ratings
Type designation
PN
PN
I2N
kW
hp
A
Frame
size
1-phase AC supply, 200 to 240 V
0.37
0.5
2.4
ACS150-01X-02A4-2
R0
0.75
1
4.7
ACS150-01X-04A7-2
R1
1.1
1.5
6.7
ACS150-01X-06A7-2
R1
1.5
2
7.5
ACS150-01X-07A5-2
R2
2.2
3
9.8
ACS150-01X-09A8-2
R2
3-phase AC supply, 200 to 240 V
2 = 200 to 240 V
4 = 380 to 480 V
Insert either “2” or “4”, depending on your chosen voltage,
into the type designation shown on the right.
0.37
0.5
2.4
ACS150-03X-02A4-2
R0
0.55
0.75
3.5
ACS150-03X-03A5-2
R0
0.75
1
4.7
ACS150-03X-04A7-2
R1
1.1
1.5
6.7
ACS150-03X-06A7-2
R1
1.5
2
7.5
ACS150-03X-07A5-2
R1
2.2
3
9.8
ACS150-03X-09A8-2
R2
3-phase AC supply, 380 to 480 V
Construction
“01X” and “03X” within the type designation varies depending
on the drive phase and EMC filtering. Choose below the one
you need.
01
03
E
U
=
=
=
=
1-phase
3-phase
EMC filter connected, 50 Hz frequency
EMC filter disconnected, 60 Hz frequency
(In case the filter is required it can easily be connected.)
0.37
0.5
1.2
ACS150-03X-01A2-4
R0
0.55
0.75
1.9
ACS150-03X-01A9-4
R0
0.75
1
2.4
ACS150-03X-02A4-4
R1
1.1
1.5
3.3
ACS150-03X-03A3-4
R1
1.5
2
4.1
ACS150-03X-04A1-4
R1
2.2
3
5.6
ACS150-03X-05A6-4
R1
3
4
7.3
ACS150-03X-07A3-4
R1
4
5
8.8
ACS150-03X-08A8-4
R1
X within the type code stands for E or U.
Cabinet-mounted drives (UL open)
Frame
IP20 UL open
size
H1
H2
H3
W
D
Weight
R0
mm
169
mm
202
mm
239
mm
70
mm
142
kg
1.1
R1
169
202
239
70
142
1.3
R2
169
202
239
105
142
1.5
H1
H2
H3
W
D
=
=
=
=
=
H1 H2 H3
Height without fastenings and clamping plate.
Height with fastenings but without clamping plate.
Height with fastenings and clamping plate.
Width
Depth
D
W
Wall-mounted drives (NEMA 1)
Frame
NEMA 1
size
H4
H5
W
D
Weight
R0
mm
257
mm
280
mm
70
mm
142
kg
1.5
R1
257
280
70
142
1.7
R2
257
282
105
142
1.9
H4
H5
W
D
=
=
=
=
Height with fastenings and NEMA 1 connection box.
Height with fastenings, NEMA 1 connection box and hood.
Width
Depth
4 ABB micro drives ACS150 | Catalog
H4 H5
D
W
Technical data
Mains connection
Voltage and power range
Frequency
Programmable control connections
1-phase, 200 to 240 V ± 10%
0.37 to 2.2 kW (0.5 to 3 hp)
3-phase, 200 to 240 V ± 10%
0.37 to 2.2 kW (0.5 to 3 hp)
3-phase, 380 to 480 V ± 10%
0.37 to 4 kW (0.5 to 5 hp)
One analog input
Voltage signal
Current signal
Potentiometer reference value
Resolution
Accuracy
0 (2) to 10 V, R in > 312 kΩ
0 (4) to 20 mA, Rin = 100 Ω
10 V ± 1% max. 10 mA, R < 10 kΩ
0.1%
± 2%
48 to 63 Hz
Auxiliary voltage
24 V DC ± 10%, max. 200 mA
Five digital inputs
12 to 24 V DC with internal or external
supply, PNP and NPN, pulse train
0 to 16 kHz
Input impedance
2.4 kΩ
One relay output
Type
Maximum switching voltage
Maximum switching current
Maximum continuous current
NO + NC
250 V AC/30 V DC
0.5 A/30 V DC; 5 A/230 V AC
2 A rms
Motor connection
Voltage
3-phase, from 0 to U supply
Frequency
0 to 500 Hz
Continuous loading
Rated output current I 2N
capability
(constant torque at a max.
ambient temperature of 40 ºC)
Overload capability
(at a max. ambient
temperature of 40 ºC)
At heavy duty use 1.5 x I2N for 1 minute
every 10 minutes
At start 1.8 x I2N for 2 s
Switching frequency
Default
Selectable
4 kHz
4 to 16 kHz with 4 kHz steps
Acceleration time
0.1 to 1800 s
Deceleration time
0.1 to 1800 s
Braking
Built-in brake chopper as standard
Motor control method
Scalar U/f
Product compliance
Low voltage Directive 2006/95/EC with supplements
Machinery Directive 2006/42/EC
EMC Directive 2004/108/EC with supplements
Quality assurance system ISO 9001
Environmental system ISO 14001
UL, cUL, CE, C-Tick and GOST R approvals
RoHS compliant
Environmental limits
Ambient temperature
Altitude
Output current
-10 to 40 ºC (14 to 104 ºF), no frost
allowed, 50 ºC (122 ºF) with 10%
derating
Rated current available at 0 to 1000 m
(0 to 3281 ft) reduced by 1% per 100 m
(328 ft) over 1000 to 2000 m (3281 to
6562 ft)
Relative humidity
Lower than 95% (without condensation)
Degree of protection
IP20/Optional NEMA 1 enclosure
Enclosure colour
NCS 1502-Y, RAL 9002, PMS 420 C
Contamination levels
IEC 721-3-3
No conductive dust allowed
Class 1C2 (chemical gases)
Class 1S2 (solid particles)
Class 2C2 (chemical gases)
Class 2S2 (solid particles)
Class 3C2 (chemical gases)
Class 3S2 (solid particles)
Transportation
Storage
Operation
Chokes
AC input chokes
External option.
For reducing THD in partial loads and to
comply with EN 61000-3-2.
AC output chokes
External option.
To achieve longer motor cables.
Catalog | ABB micro drives ACS150 5
Control connections and interfaces
Application macros
Application macros are preprogrammed parameter sets.
When starting up the drive, the user typically selects one of
the macros that is best suited for the application. The diagram
below gives an overview of ACS150 control connections
and shows the default I/O connections for the ABB standard
macro.
Removable clip for
brand labeling
Integrated interface
ABB micro drives have six standard macros:
–
–
–
–
–
–
FlashDrop
connection
EMC filter
grounding
screw (EMC)
ABB standard macro
3-wire macro
Alternate macro
Motor potentiometer macro
Hand/auto macro
PID control macro
Integrated
potentiometer
Varistor
grounding
screw (VAR)
In addition to the standard macros the user can create three
user macros. The user macro allows the user to save the
parameter settings for later use.
I/O connections
Input, brake
resistor
and motor
connections
Analog input signal
selector (U/I)
Typical I/O connections
ACS150
Screen
Analog input
0 to 10 V
Reference voltage
+10 V DC, max. 10 mA
Aux. voltage output
+24 V DC, max. 200 mA
Potentiometer
SCR
SI
AI
I
GND U AI
+10 V
COM
+24 V
NC
GND
NO
COM
0 - 20 mA
Ground the cable
screen on the
sourcing end
+24 V
start/
stop
const.
speed
1
Relay output
250 V AC / 30 V DC / 6 A
DI configuration PNP
connected (source)
with external power
supply
DI2
DI3
DI4
DI5 can also be used
as a frequency input
EMC
VAR
DI5
EMC filter grounding screw
Varistor grounding screw
6
3-phase
power
supply,
200 to
480 V AC
R < 10 kΩ
PE
U1
V1
W1
PE
L1
L2
L3
Input
choke
EMC
filter
U
ROCOM
RONC
RONO
ACS150
FlashDrop
I
0V
DI1
PROGRAMMABLE
DIGITAL INPUTS
fwd/
rev
SCR
AI
GND
+10 V
+24 V
GND
DCOM
DI1
DI2
DI3
DI4
DI5
Brake
chopper
BRK+ BRK-
M
3~
Output
choke
AC motor
ramp
pair
sel.
start/
const. fwd/ stop
speed rev
1
DI configuration
NPN connected (sink)
t°
6 ABB micro drives ACS150 | Catalog
U2
V2
W2
Brake resistor
SCR
AI
GND
+10 V
+24 V
GND
DCOM
DI1
DI2
DI3
DI4
DI5
ROCOM
RONC
RONO
I
U
Cooling and fuses
Cooling
ACS150 is fitted with cooling fans as standard. The cooling
air must be free from corrosive substances and must not be
above the maximum ambient temperature of 40 °C (50 °C with
derating). For more specific limits see the Technical data Environmental limits in this catalog.
Fuses
Standard fuses can be used with ABB micro drives.
For input fuse connections see table below.
Cooling air flow
Selection table
Type designation
Frame
Heat dissipation
Type designation
Air flow
Frame
IEC fuses
size
size
[W]
BTU/hr
3
m /h
3
ft /min
1-phase AC supply, 200 to 240 V
[A]
1-phase AC supply, 200 to 240 V
UL fuses
Fuse
)
type*
[A]
Fuse
)
type *
ACS150-01X-02A4-2
R0
25
85
-*
)
-*
)
ACS150-01X-02A4-2
R0
10
gG
10
UL class T
ACS150-01X-04A7-2
R1
46
157
24
14
ACS150-01X-04A7-2
R1
16
gG
20
UL class T
ACS150-01X-06A7-2
R1
71
242
24
14
ACS150-01X-06A7-2
R1
20
gG
25
UL class T
ACS150-01X-07A5-2
R2
73
249
21
12
ACS150-01X-07A5-2
R2
25
gG
30
UL class T
ACS150-01X-09A8-2
R2
96
328
21
12
ACS150-01X-09A8-2
R2
35
gG
35
UL class T
3-phase AC supply, 200 to 240 V
3-phase AC supply, 200 to 240 V
)
)
-*
)
-*
ACS150-03X-02A4-2
R0
10
gG
10
UL class T
106
-*
)
-*
ACS150-03X-03A5-2
R0
10
gG
10
UL class T
38
130
24
14
ACS150-03X-04A7-2
R1
10
gG
15
UL class T
R1
60
205
24
14
ACS150-03X-06A7-2
R1
16
gG
15
UL class T
ACS150-03X-07A5-2
R1
62
212
21
12
ACS150-03X-07A5-2
R1
16
gG
15
UL class T
ACS150-03X-09A8-2
R2
83
283
21
12
ACS150-03X-09A8-2
R2
16
gG
20
UL class T
ACS150-03X-02A4-2
R0
19
65
ACS150-03X-03A5-2
R0
31
ACS150-03X-04A7-2
R1
ACS150-03X-06A7-2
3-phase AC supply, 380 to 480 V
3-phase AC supply, 380 to 480 V
)
ACS150-03X-01A2-4
R0
11
38
ACS150-03X-01A9-4
R0
16
55
-*
)
-*
ACS150-03X-02A4-4
R1
21
72
13
ACS150-03X-03A3-4
R1
31
106
ACS150-03X-04A1-4
R1
40
ACS150-03X-05A6-4
R1
ACS150-03X-07A3-4
ACS150-03X-08A8-4
)
-*
)
-*
ACS150-03X-01A2-4
R0
10
gG
10
UL class T
ACS150-03X-01A9-4
R0
10
gG
10
UL class T
8
ACS150-03X-02A4-4
R1
10
gG
10
UL class T
13
8
ACS150-03X-03A3-4
R1
10
gG
10
UL class T
137
13
8
ACS150-03X-04A1-4
R1
16
gG
15
UL class T
61
208
19
11
ACS150-03X-05A6-4
R1
16
gG
15
UL class T
R1
74
253
24
14
ACS150-03X-07A3-4
R1
16
gG
20
UL class T
R1
94
321
24
14
ACS150-03X-08A8-4
R1
20
gG
25
UL class T
X within the type code stands for E or U.
X within the type code stands for E or U.
*) Frame size R0 with free convection cooling.
*) According to IEC-60269 standard.
Free space requirements
Enclosure type
Space above Space below
Space on left/right
All frame sizes
mm
75
mm
0
mm
75
Catalog | ABB micro drives ACS150 7
Options
FlashDrop tool
FlashDrop is a powerful palm sized tool for fast and easy
parameter selecting and setting. It gives the possibility to
hide selected parameters to protect the machine. Only the
parameters needed in the application are shown. The tool can
copy parameters between two drives or between a PC and a
drive. All the above can be done without a power connection
to the drive – in fact, it is not even necessary to unpack the
drive.
DrivePM
DrivePM (Drive parameter manager) is a tool to create, edit
and copy parameter sets for FlashDrop. For each parameter/
group the user has a possibility to hide it, which means that
the drive user does not see the parameter/group at all.
Protection class NEMA 1
The NEMA 1 kit includes a connection box for finger
protection, conduit tube installation, and a hood for protection
against dirt and dust.
Brake resistors
ACS150 is delivered with an integrated brake chopper as
standard. Therefore no additional space or installation time is
needed, The brake resistor is selected using the table below.
For more information about the selection of brake resistors,
see the ACS150 user’s manual.
Brake chopper limits and resistor selection table
Type
R min
PBRmax
Selection table by resistor type
designation
DrivePM requirements
– Windows 2000/XP/Vista/Windows 7
– Free serial port from a PC
FlashDrop package includes
– FlashDrop tool
– DrivePM software on a CD-rom
– User’s manual in pdf-format on the previous CD-rom
– Cable for connection between the PC and FlashDrop
– Battery charger
160
ACS150[ohm] [kW]
CBR-V
210
Braking
460
[hp]
time 1)
[s]
1-phase AC supply, 200 to 240 V
01X-02A4-2
70
0.37
0.5
90
01X-04A7-2
40
0.75
1
45
01X-06A7-2
40
1.1
1.5
28
01X-07A5-2
30
1.5
2
19
01X-09A8-2
30
2.2
3
14
3-phase AC supply, 200 to 240 V
03X-02A4-2
70
0.37
0.5
90
03X-03A5-2
70
0.55
0.75
60
03X-04A7-2
40
0.75
1
42
03X-06A7-2
40
1.1
1.5
29
03X-07A5-2
30
1.5
2
19
03X-09A8-2
30
2.2
3
14
3-phase AC supply, 380 to 480 V
03X-01A2-4
200
0.37
0.5
90
03X-01A9-4
175
0.55
0.75
90
03X-02A4-4
165
0.75
1
60
03X-03A3-4
150
1.1
1.5
37
03X-04A1-4
130
1.5
2
27
03X-05A6-4
100
2.2
3
17
03X-07A3-4
70
3
4
29
03X-08A8-4
70
4
5
20
X within the type code stands for E or U.
1)
Braking time = Maximum allowed braking time in seconds at PBRmax
every 120 seconds, at 40 °C ambient temperature
8 ABB micro drives ACS150 | Catalog
Ratings by resistor type
CBR-V 160 CBR-V 210 CBR-V 460
Nominal power [W]
280
360
790
Resistance [ohm]
70
200
80
Options
External
A separate order line and type designation is required for
any of these external options.
Input chokes
Input choke smooths the wave shape of the mains current
and reduces total harmonic distortion (THD). Together
with the input choke, the ACS150 is designed to fulfill the
requirements of the harmonics standard EN/IEC 61000-3-12.
In addition, the input choke provides improved protection
against mains voltage transients.
Type
Frame Input
I 1N
I 1N
designation
size
without
choke
[A]
[A]
[A]
[mH]
choke
ACS150-
Output chokes
Output choke decreases du/dt on the output and filters
current spikes caused by voltage spikes. With an output
choke it is possible to increase the motor cable length
which could be otherwise limited due to a temperature
increase resulting from current spikes and electromagnetic
performance.
Type
Frame
with
designation
size
choke
ACS150-
I TH
L
1-phase AC supply, 200 to 240 V
Output choke
Cable length
[m]
1-phase AC supply, 200 to 240 V
01X-02A4-2
R0
CHK-A1 6.1
4.5
5
8.0
01X-02A4-2
R0
ACS-CHK-B3
01X-04A7-2
R1
CHK-B1 11.4
8.1
10
2.8
01X-04A7-2
R1
ACS-CHK-B3
100
01X-06A7-2
R1
CHK-C1 16.1
11
16
1.2
01X-06A7-2
R1
ACS-CHK-C3
100
01X-07A5-2
R2
CHK-C1 16.8
12
16
1.2
01X-07A5-2
R2
ACS-CHK-C3
100
01X-09A8-2
R2
CHK-D1 21
15
25
1.0
01X-09A8-2
R2
ACS-CHK-C3
100
3-phase AC supply, 200 to 240
60
3-phase AC supply, 200 to 240 V
03X-02A4-2
R0
CHK-01
4.3
2.2
4.2
6.4
03X-02A4-2
R0
ACS-CHK-B3
60
03X-03A5-2
R0
CHK-02
6.1
3.6
7.6
4.6
03X-03A5-2
R0
ACS-CHK-B3
60
03X-04A7-2
R1
CHK-03
7.6
4.8
13
2.7
03X-04A7-2
R1
ACS-CHK-B3
100
03X-06A7-2
R1
CHK-03
11.8
7.2
13
2.7
03X-06A7-2
R1
ACS-CHK-C3
100
03X-07A5-2
R1
CHK-04
12
8.2
22
1.5
03X-07A5-2
R1
ACS-CHK-C3
100
03X-09A8-2
R2
CHK-04
14.3
11
22
1.5
03X-09A8-2
R2
ACS-CHK-C3
100
3-phase AC supply, 380 to 480 V
3-phase AC supply, 380 to 480 V
03X-01A2-4
R0
CHK-01
2.2
1.1
4.2
6.4
03X-01A2-4
R0
ACS-CHK-B3
60
03X-01A9-4
R0
CHK-01
3.6
1.8
4.2
6.4
03X-01A9-4
R0
ACS-CHK-B3
60
03X-02A4-4
R1
CHK-01
4.1
2.3
4.2
6.4
03X-02A4-4
R1
ACS-CHK-B3
100
03X-03A3-4
R1
CHK-01
6
3.1
4.2
6.4
03X-03A3-4
R1
ACS-CHK-B3
100
03X-04A1-4
R1
CHK-02
6.9
3.5
7.6
4.6
03X-04A1-4
R1
ACS-CHK-C3
100
03X-05A6-4
R1
CHK-02
9.6
4.8
7.6
4.6
03X-05A6-4
R1
ACS-CHK-C3
100
03X-07A3-4
R1
CHK-02
11.6
6.1
7.6
4.6
03X-07A3-4
R1
NOCH-0016-6x
100
03X-08A8-4
R1
CHK-03
13.6
7.7
13
2.7
03X-08A8-4
R1
NOCH-0016-6x
100
I1N = Nominal input current
ITH = Nominal choke thermal current
L = Choke inductance
Catalog | ABB micro drives ACS150 9
Options
External
A separate order line and type designation is required for
any of these external options.
EMC filters
The ACS150’s internal EMC filter is designed to meet category
C3 requirements of EN/IEC 61800-3 standard. External
EMC filters are used to enhance the drives electromagnetic
performance in conjunction with its internal filtering. Maximum
motor cable length depends on required electromagnetic
performance, according to the table below.
Type
Frame
designation size
Low leakage current filters
Low leakage current filters are ideal for installations where
residual current devices (RCD) are required and leakage
current needs to be below 30 mA.
Filter
Cable length1) with Cable length1)
Type
Frame
type
external EMC filter without external
designation
size
ACS150-
EMC filter
Filter type
Cable length1)
with LRFI filter
C2
ACS150-
[m]
C1
C2
C3
C3
C4
[m]
[m]
[m]
[m]
[m]
Low leakage current filters, 3-phase AC supply, 400 V
R0
R0
R1
LRFI-31
LRFI-31
LRFI-31
10
10
10
01X-02A4-2
R0
RFI-11
10
30
-
30
30
01X-04A7-2
R1
RFI-12
10
30
50
30
50
03X-01A2-4
03X-01A9-4
03X-02A4-4
01X-06A7-2
R1
RFI-12
10
30
50
30
50
03X-03A3-4
R1
LRFI-31
10
50
03X-04A1-4
R1
LRFI-31
10
50
03X-05A6-4
R1
LRFI-31
10
03X-07A3-4
R1
LRFI-32
10
03X-08A8-4
R1
LRFI-32
10
1-phase AC supply, 200 to 240 V
01X-07A5-2
01X-09A8-2
R2
R2
RFI-13
RFI-13
10
10
30
30
50
50
30
30
3-phase AC supply, 200 to 240 V
03X-02A4-2
R0
RFI-32
10
30
-
30
30
03X-03A5-2
R0
RFI-32
10
30
-
30
30
03X-04A7-2
R1
RFI-32
10
30
50
30
50
03X-06A7-2
R1
RFI-32
10
30
50
30
50
03X-07A5-2
R1
RFI-32
10
30
50
30
50
03X-09A8-2
R2
RFI-32
10
30
50
30
50
1)
Internal EMC filter must be disconnected by removing the EMC screw from
the drive.
EMC standards in general
EN 61800-3
EN 55011, product family EN 61800-3/A11 (2000),
03X-01A2-4
R0
RFI-32
30
30
-
30
30
(2004),
standard for industrial,
03X-01A9-4
R0
RFI-32
30
30
-
30
30
product
scientific and medical
03X-02A4-4
R1
RFI-32
50
50
50
30
50
standard
(ISM) equipment
03X-03A3-4
R1
RFI-32
50
50
50
30
50
Category C1
Group 1
1 st environment,
03X-04A1-4
R1
RFI-32
50
50
50
30
50
03X-05A6-4
R1
RFI-32
50
50
50
30
50
Class B
unrestricted distribution
03X-07A3-4
R1
RFI-32
50
50
50
30
50
Category C2
Group 1
1 st environment,
03X-08A8-4
R1
RFI-32
50
50
50
30
50
Category C3
Class A
Group 2
restricted distribution
2 nd environment,
Category C4
Class A
Not applicable
unrestricted distribution
2nd environment,
3-phase AC supply, 380 to 480 V
1)
Internal EMC filter must be connected with the EMC screw in the drive.
When the filter is not connected the C4 maximum cable lengths are allowed
to be used.
10 ABB micro drives ACS150 | Catalog
product standard
restricted distribution
Expertise at every stage of the value chain
Prepurchase
Order
and
delivery
Installation
and
commissioning
Operation
and
maintenance
Upgrade
and
retrofit
Replacement
and
recycling
Training and learning
Technical support
Contracts
Whether you operate in industry, commerce or a utility your
aims remain the same: to keep your motor-driven applications
running consistently and efficiently. The life cycle services for
ABB drives can help you achieve these aims by maximizing the
uptime of your process while ensuring the optimum lifetime of
ABB drives in a predictable, safe and low-cost manner.
The life cycle services for ABB drives span the entire value
chain, from the moment you make the first enquiry about a
drive through to its disposal and recycling. Throughout the
value chain, ABB provides training and learning, technical
support and contracts. All of this is supported by one of the
most extensive global drive sales and service networks.
Secure uptime throughout the drive life cycle
ABB follows a four-phase model for the life cycle management
of its drives. The life cycle phases are active, classic, limited
and obsolete. Within each phase, every drive series has a
defined set of services.
The four-phase drive life cycle management model provides
you with a transparent method for managing your investment
in drives. In each phase, you clearly see what life cycle services
are available, and more importantly, what services are not
available. Decisions on upgrading, retrofitting or replacing
drives can be made with confidence.
ABB drive life cycle management model
Active
The drive, with complete life cycle
services, is available for purchase.
Classic
The drive, with complete life cycle
services, is available for plant
extensions.
Limited
Spare parts, maintenance and repair
services are available as long as
materials can be obtained.
Obsolete
ABB cannot guarantee availability of life
cycle services for technical reasons or
within reasonable cost.
Complete life cycle services
Limited life cycle services
To ensure the availability of complete life cycle services, a drive must be in the
active or classic phase. A drive can be kept in the active or classic phase by
upgrading, retrofitting or replacing.
Caution! A drive entering the limited or obsolete phase has limited repair options.
This may result in unpredictable process downtime. To avoid this possibility, the
drive should be kept in the active or classic phase.
Catalog | ABB micro drives ACS150 11
For more information please contact your local ABB
representative or visit:
www.abb.com/drives
www.abb.com/drivespartners
© Copyright 2012 ABB. All rights reserved.
Specifications subject to change without notice.
3AFE68596114 REV F EN 24.10.2012
Contact us