AF09Z-30-01-20
General Information
Extended Product Type:
Product ID:
EAN:
Catalog Description:
Long Description:
AF09Z-30-01-20
1SBL136001R2001
3471523113305
AF09Z-30-01-20 12-20VDC Contactor
AF09Z contactors are used for controlling power circuits up to 690 V AC and 220 V DC.
They are mainly used for controlling 3-phase motors, non-inductive or slightly inductive
loads. AF..Z contactors include an electronic coil interface accepting a wide control voltage
Uc min. ... Uc max. Only four coils cover control voltages between 24...250 V 50/60 Hz or
12...250 V DC. AF..Z contactors can manage large control voltage variations. One coil can
be used for different control voltages used worldwide without any coil change. AF..Z
contactors allow direct control by PLC-output ≥ 24 V DC 500 mA and obtain a reduced
holding coil consumption. AF..Z contactors withstand short voltage dips and voltage sags
(SEMI F47-0706 compliance) between 24...250 V 50/60 Hz AF..Z contactors have built-in
surge protection and do not require additional surge suppressors The AF... series 1-stack 3pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 3
main poles, 1 built-in auxiliary contact, front and side-mounted add-on auxiliary contact
blocks. (mechanically-linked auxiliary contacts compliant with Annex L of IEC 60947-5-1.
N.C. mirror contacts compliant with Annex F of IEC 60947-4-1) - Control circuit: DC operated
for AF..Z-30-..-20 contactors. Only AF..Z-30-..-20 contactors need to respect the polarity on
the coil terminals (A1+ and A2-). - Accessories: a wide range of accessories is available.
Categories
Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors
Ordering
Minimum Order Quantity:
Customs Tariff Number:
EAN:
1 piece
85369085
3471523113305
Dimensions
Product Net Depth:
Product Net Height:
Product Net Weight:
Product Net Width:
77 mm
86 mm
0.310 kg
45 mm
Container Information
Package Level 1 Width:
Package Level 1 Length:
Package Level 1 Height:
Package Level 1 Gross Weight:
Package Level 1 EAN:
Package Level 2 Units:
Package Level 2 Width:
Package Level 2 Length:
Package Level 2 Height:
Package Level 3 Units:
Package Level 1 Units:
87 mm
79 mm
47 mm
0.31 kg
3471523113305
54 piece
250 mm
300 mm
315 mm
1296 piece
1 piece
Technical
Number of Main Contacts NC:
Number of Auxiliary Contacts NO:
Number of Auxiliary Contacts NC:
Standards:
Rated Operational Voltage:
0
0
1
IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1, UL 508, CSA C22.2 N°14
Auxiliary Circuit 690 V
Main Circuit 690 V
Rated Frequency (f):
Auxiliary Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal
acc. to IEC 60947-4-1, Open Contactors q = 40 °C 35 A
Current (Ith):
acc. to IEC 60947-5-1, q = 40 °C 16 A
Rated Operational Current AC-1 (Ie): (690 V) 40 °C 25 A
(690 V) 60 °C 25 A
(690 V) 70 °C 22 A
Rated Operational Current AC-3 (Ie): (220 / 230 / 240 V) 60 °C 9 A
(380 / 400 V) 60 °C 9 A
(415 V) 60 °C 9 A
(440 V) 60 °C 9 A
(500 V) 60 °C 9.5 A
(690 V) 60 °C 7 A
Rated Operational Power AC-3 (Pe): (220 / 230 / 240 V) 2.2 kW
(380 / 400 V) 4 kW
(400 V) 4 kW
(415 V) 4 kW
(440 V) 4 kW
(500 V) 5.5 kW
(690 V) 5.5 kW
Rated Operational Current AC-15
(220 / 240 V) 4 A
(Ie):
(24 / 127 V) 6 A
(400 / 440 V) 3 A
(500 V) 2 A
(690 V) 2 A
Rated Short-time Withstand Current at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A
(Icw):
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A
for 0.1 s 140 A
for 1 s 100 A
Maximum Breaking Capacity:
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
Maximum Electrical Switching
AC-1 600 cycles per hour
Frequency:
AC-15 1200 cycles per hour
AC-2 / AC-4 300 cycles per hour
AC-3 1200 cycles per hour
DC-13 900 cycles per hour
Rated Operational Current DC-13
(110 V) 0.55 A / 60 W
(Ie):
(125 V) 0.55 A / 69 W
(220 V) 0.27 A / 60 W
(24 V) 6 A / 144 W
(250 V) 0.27 A / 68 W
(400 V) 0.15 A / 60 W
(48 V) 2.8 A / 134 W
(500 V) 0.13 A / 65 W
(600 V) 0.1 A / 60 W
(72 V) 1 A / 72 W
Rated Insulation Voltage (Ui):
acc. to UL/CSA 600 V
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
Rated Impulse Withstand Voltage 6 kV
(Uimp):
Maximum Mechanical Switching
3600 cycles per hour
Frequency:
Rated Control Circuit Voltage (Uc): DC Operation 12 ... 20 V
Operate Time:
Between Coil De-energization and NC Contact Closing 13...98 ms
Between Coil De-energization and NO Contact Opening 11...95 ms
Between Coil Energization and NC Contact Opening 38...90 ms
Between Coil Energization and NO Contact Closing 40...95 ms
Connecting Capacity Main Circuit: Flexible with Insulated Ferrule 1x 0.75...4 mm²
Flexible with Insulated Ferrule 2x 0.75...2.5 mm²
Flexible with Ferrule 1/2x 0.75...6 mm²
Rigid 1/2x 1...6 mm²
Connecting Capacity Auxiliary
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Circuit:
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid 1/2x 1...2.5 mm²
Connecting Capacity Control Circuit: Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid 1/2x 1 ... 2.5 mm²
Wire Stripping Length:
Auxiliary Circuit 10 mm
Control Circuit 10 mm
Main Circuit 10 mm
Degree of Protection:
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Terminal Type:
Screw Terminals
Number of Main Contacts NO:
3
Environmental
Climatic Withstand:
Maximum Operating Altitude
Permissible:
Category B according to IEC 60947-1 Annex Q
3000 m
Resistance to Vibrations acc. to IEC 5 ... 300 Hz 4 g closed position / 2 g open position
60068-2-6:
Resistance to Shock acc. to IEC
Closed, Shock Direction: B1 25 g
60068-2-27:
Open, Shock Direction: B1 5 g
Shock Direction: A 30 g
Shock Direction: B2 15 g
Shock Direction: C1 25 g
Shock Direction: C2 25 g
RoHS Status:
Planned to follow EU Directive 2002/95/EC August 18, 2005 and amendment after 2008 Q1
Ambient Air Temperature:
Close to Contactor for Storage -60...+80 °C
Close to Contactor Fitted with Thermal O/L Relay -25 ... +60 °C
Close to Contactor without Thermal O/L Relay -40 ... +70 °C
Technical UL/CSA
General Use Rating UL/CSA:
Horsepower Rating UL/CSA:
Tightening Torque UL/CSA:
(600 V AC) 25 A
(120 V AC) Single Phase 3/4 Hp
(240 V AC) Single Phase 1-1/2 Hp
(200 ... 208 V AC) Three Phase 2 Hp
(220 ... 240 V AC) Three Phase 2 Hp
(440 ... 480 V AC) Three Phase 5 Hp
(550 ... 600 V AC) Three Phase 7-1/2 Hp
Auxiliary Circuit 11 in·lb
Control Circuit 11 in·lb
Main Circuit 13 in·lb
Certificates and Declarations (Document Number)
Instructions and Manuals:
ABS Certificate:
CB Certificate:
CCC Certificate:
Data Sheet, Technical Information:
Declaration of Conformity - CE:
DNV Certificate:
EAC Certificate:
GL Certificate:
GOST Certificate:
LR Certificate:
RINA Certificate:
RMRS Certificate:
RoHS Information:
UL Certificate:
UL Listing Card:
1SBC101027M6801
ABS_15-GE1349500-PDA_90682247
CB_SE_70855M1
CCC_2010010304445624
1SBC101402D0201
1SBD250000U1000
DNV-GL_E13871
EAC_RU C-FR ME77 B01010
DNV-GL_E13871
GOST_POCCFR.ME77.B07175.pdf
LRS_1300087E1
RINA_ELE084013XG
RMRS_1400682124
1SBD251013E1000
UL_20140305-E312527_7_1
UL_E312527
Classifications
ETIM 4:
ETIM 5:
ETIM 6:
UNSPSC:
Object Classification Code:
EC000066 - Magnet contactor, AC-switching
EC000066 - Magnet contactor, AC-switching
EC000066 - Power contactor, AC switching
39121529
Q
很抱歉,暂时无法提供与“AF09Z-30-01-20”相匹配的价格&库存,您可以联系我们找货
免费人工找货