AF38-40-00-13
General Information
Extended Product Type:
Product ID:
EAN:
Catalog Description:
Long Description:
AF38-40-00-13
1SBL297201R1300
3471523115330
AF38-40-00-13 100-250V50/60HZ-DC Contactor
AF38 4-pole contactors are used for controlling power circuits up to 690 V AC and 440 V
DC. They are mainly used for controlling non-inductive or slightly inductive loads (i.e.
resistance furnaces...). AF... contactors include an electronic coil interface accepting a wide
control voltage Uc min. ... Uc max. Only four coils cover control voltages between 24...500 V
50/60 Hz or 20...500 V DC. AF contactors can manage large control voltage variations. One
coil can be used for different control voltages used worldwide without any coil change. AF
contactors have built-in surge protection and do not require additional surge suppressors.
The AF... series 4-pole contactors are of the block type design. - Main poles and auxiliary
contact blocks: 4 N.O. main poles, front and side-mounted add-on auxiliary contact blocks
(mechanically-linked auxiliary contacts compliant with Annex L of IEC 60947-5-1. N.C.
mirror contacts compliant with Annex F of IEC 60947-4-1) - Control circuit: AC or DC
operated - Accessories: a wide range of accessories is available.
Categories
Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors
Ordering
Minimum Order Quantity:
Customs Tariff Number:
EAN:
1 piece
85369085
3471523115330
Dimensions
Product Net Depth:
Product Net Height:
Product Net Weight:
Product Net Width:
101 mm
86 mm
0.360 kg
45 mm
Container Information
Package Level 1 Width:
Package Level 1 Length:
Package Level 1 Height:
Package Level 1 Gross Weight:
Package Level 1 EAN:
Package Level 2 Units:
Package Level 2 Width:
Package Level 2 Length:
Package Level 2 Height:
Package Level 3 Units:
Package Level 1 Units:
87 mm
103 mm
47 mm
0.36 kg
3471523115330
36 piece
250 mm
300 mm
315 mm
864 piece
1 piece
Technical
Number of Main Contacts NC:
Number of Auxiliary Contacts NO:
Number of Auxiliary Contacts NC:
Standards:
Rated Operational Voltage:
Rated Frequency (f):
Conventional Free-air Thermal
Current (Ith):
Rated Operational Current AC-1 (Ie):
0
0
0
IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1, UL 508, CSA C22.2 N°14
Main Circuit 690 V
Main Circuit 50 / 60 Hz
acc. to IEC 60947-4-1, Open Contactors q = 40 °C 55 A
(690 V) 40 °C 55 A
(690 V) 60 °C 45 A
(690 V) 70 °C 37 A
Rated Operational Current AC-3 (Ie): (220 / 230 / 240 V) 60 °C 23.2 A
(380 / 400 V) 60 °C 22 A
(415 V) 60 °C 21.2 A
(440 V) 60 °C 20 A
(500 V) 60 °C 17.6 A
(690 V) 60 °C 10.5 A
Rated Operational Power AC-3 (Pe): (220 / 230 / 240 V) 5.5 kW
(400 V) 11 kW
(415 V) 11 kW
(440 V) 11 kW
(500 V) 11 kW
(690 V) 9 kW
Rated Short-time Withstand Current at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 300 A
(Icw):
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 55 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 150 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 450 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 225 A
Maximum Electrical Switching
AC-1 600 cycles per hour
Frequency:
Rated Insulation Voltage (Ui):
acc. to UL/CSA 600 V
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
Rated Impulse Withstand Voltage 6 kV
(Uimp):
Maximum Mechanical Switching
3600 cycles per hour
Frequency:
Rated Control Circuit Voltage (Uc): 50 Hz 100 ... 250 V
60 Hz 100 ... 250 V
DC Operation 100 ... 250 V
Operate Time:
Between Coil De-energization and NC Contact Closing 13...98 ms
Between Coil De-energization and NO Contact Opening 11...95 ms
Between Coil Energization and NC Contact Opening 38...90 ms
Between Coil Energization and NO Contact Closing 40...95 ms
Connecting Capacity Main Circuit: Flexible with Insulated Ferrule 1x 1.5...16 mm²
Flexible with Insulated Ferrule 2x 1.5...16 mm²
Flexible with Ferrule 1/2x 1.5...16 mm²
Rigid 1/2x 1.5...16 mm²
Connecting Capacity Control Circuit: Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid 1/2x 1 ... 2.5 mm²
Wire Stripping Length:
Control Circuit 10 mm
Main Circuit 12 mm
Degree of Protection:
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Terminal Type:
Screw Terminals
Number of Main Contacts NO:
4
Environmental
Climatic Withstand:
Maximum Operating Altitude
Permissible:
Resistance to Vibrations acc. to IEC
60068-2-6:
Resistance to Shock acc. to IEC
60068-2-27:
RoHS Status:
Ambient Air Temperature:
Category B according to IEC 60947-1 Annex Q
3000 m
5 ... 300 Hz 4 g closed position / 2 g open position
Closed, Shock Direction: B1 25 g
Open, Shock Direction: B1 5 g
Shock Direction: A 30 g
Shock Direction: B2 15 g
Shock Direction: C1 25 g
Shock Direction: C2 25 g
Planned to follow EU Directive 2002/95/EC August 18, 2005 and amendment after 2008 Q1
Close to Contactor for Storage -60...+80 °C
Near Contactor for Operation in Free Air -40 ... +70 °C
Technical UL/CSA
General Use Rating UL/CSA:
Tightening Torque UL/CSA:
(600 V AC) 55 A
Control Circuit 11 in·lb
Main Circuit 22 in·lb
Certificates and Declarations (Document Number)
Instructions and Manuals:
ABS Certificate:
CB Certificate:
CCC Certificate:
Data Sheet, Technical Information:
Declaration of Conformity - CE:
DNV Certificate:
EAC Certificate:
GL Certificate:
GOST Certificate:
1SBC101027M6801
ABS_15-GE1349500-PDA_90682247
CB_SE_70858M1
CCC_2010010304445623
1SBC101424D0201
1SBD250001U1000
DNV-GL_E13871
EAC_RU C-FR ME77 B01010
DNV-GL_E13871
GOST_POCCFR.ME77.B07175.pdf
LR Certificate:
RINA Certificate:
RMRS Certificate:
RoHS Information:
UL Certificate:
UL Listing Card:
LRS_1300087E1
RINA_ELE084013XG
RMRS_1400682124
1SBD251015E1000
UL_20120918-E319322-3-1
UL_E319322
Classifications
E-nummer:
ETIM 4:
ETIM 5:
ETIM 6:
UNSPSC:
Object Classification Code:
3211520
EC000066 - Magnet contactor, AC-switching
EC000066 - Magnet contactor, AC-switching
EC000066 - Power contactor, AC switching
39121529
Q
很抱歉,暂时无法提供与“AF38-40-00-13”相匹配的价格&库存,您可以联系我们找货