PRODUCT-DETAILS
AFS96-30-22-11
AFS96-30-22-11 24-60V50/60HZ 20-60VDC
Contactor
General Information
Extended Product Type
Product ID
EAN
Catalog Description
Long Description
AFS96-30-22-11
1SBL407082R1122
3471523158016
AFS96-30-22-11 24-60V50/60HZ 20-60VDC Contactor
AFS40 ... AFS96 contactors are designed for machine safety applications. They are
delivered with fixed front-mounted auxiliary contact blocks making them ideal for
monitoring and controlling circuits. Mechanically linked and mirror contacts make your
system safer. - control circuit with electronic coil interface: - 24...60 V AC, 20...60 V DC
and 100...250 V AC / DC operated accepting a wide control voltage range - reduced
panel energy consumption - mirror and mechanically linked contacts, with front
marked symbol acc. to IEC60947-5-1, always guaranteeing the right contactor status front-mounted auxiliary contact block: - permanently fixed - protective cover to
prevent manual operation - yellow housing for easy identification - minimum switching
capacity 12 V / 3 mA, with a failure rate 10-7 acc. to IEC 60947-5-4 - built-in surge
suppression
Classifications
Object Classification
Code
Q
ETIM 4
EC000066 - Magnet contactor, AC-switching
ETIM 5
EC000066 - Magnet contactor, AC-switching
ETIM 6
EC000066 - Power contactor, AC switching
ETIM 7
EC000066 - Power contactor, AC switching
E-Number (Sweden)
3210675
AFS96-30-22-11
2
Container Information
Package Level 1 Units
box 1 piece
Package Level 1 Width
167 mm
Package Level 1 Depth /
Length
180 mm
Package Level 1 Height
97 mm
Package Level 1 Gross
Weight
1.41 kg
Package Level 1 EAN
3471523158016
Package Level 2 Units
box 6 piece
Package Level 2 Width
250 mm
Package Level 2 Depth /
Length
300 mm
Package Level 2 Height
300 mm
Package Level 2 Gross
Weight
8.46 kg
Package Level 3 Units
144 piece
Certificates and Declarations (Document Number)
CB Certificate
cUL Certificate
CB_SE_77417M2
UL_20170607-E312527-14-1
Declaration of
Conformity - CE
1SBD250022U1000
DNV Certificate
DNV-GL_TAE00001AF-3
DNV GL Certificate
EAC Certificate
GL Certificate
Instructions and
Manuals
DNV-GL_TAE00001AF-3
EAC_RUC-FRME77B03199
DNV-GL_TAE00001AF-3
1SBC101052M6801
RMRS Certificate
RMRS_1802705280
RoHS Information
1SBD250022U1000
UL Listing Card
E312527
Technical UL/CSA
General Use Rating
UL/CSA
(600 V AC) 115 A
Horsepower Rating
UL/CSA
(220 ... 240 V AC) Three Phase 30 hp
(440 ... 480 V AC) Three Phase 60 hp
(550 ... 600 V AC) Three Phase 75 hp
(120 V AC) Single Phase 7-1/2 hp
(200 ... 208 V AC) Three Phase 30 hp
(240 V AC) Single Phase 20 hp
Tightening Torque
UL/CSA
Auxiliary Circuit 11 IA
Control Circuit 11 IA
Main Circuit 53 IA
Environmental
Ambient Air
Temperature
Climatic Withstand
Maximum Operating
Altitude Permissible
Close to Contactor for Storage -60 ... +80 °C
Close to Contactor without Thermal O/L Relay -40 ... +70 °C
Close to Contactor Fitted with Thermal O/L Relay -25 ... +60 °C
Category B according to IEC 60947-1 Annex Q
3000 m
Resistance to Vibrations
acc. to IEC 60068-2-6
5 ... 300 Hz 3 g closed position / 3 g open position
Resistance to Shock acc.
Closed, Shock Direction: A 25 K40
AFS96-30-22-11
3
to IEC 60068-2-27
Closed, Shock Direction: B1 25 K40
Closed, Shock Direction: B2 15 K40
Closed, Shock Direction: C1 25 K40
Closed, Shock Direction: C2 25 K40
RoHS Status
Following EU Directive 2011/65/EU
Technical
Number of Main
Contacts NO
3
Number of Main
Contacts NC
0
Number of Auxiliary
Contacts NO
2
Number of Auxiliary
Contacts NC
2
Rated Operational
Voltage
Rated Frequency (f)
Conventional Free-air
Thermal Current (I th )
Auxiliary Circuit 690 V
Main Circuit 1000 V
Auxiliary Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
acc. to IEC 60947-5-1, q = 40 °C 16 A
acc. to IEC 60947-4-1, Open Contactors q = 40 °C 130 A
Rated Operational
Current AC-1 (I e )
(690 V) 40 °C 130 A
(690 V) 60 °C 105 A
(690 V) 70 °C 90 A
Rated Operational
Current AC-3 (I e )
(220 / 230 / 240 V) 60 °C 96 A
(380 / 400 V) 60 °C 96 A
(415 V) 60 °C 96 A
(440 V) 60 °C 96 A
(500 V) 60 °C 80 A
(690 V) 60 °C 57 A
(1000 V) 60 °C 30 A
Rated Operational Power
AC-3 (P e )
Rated Operational
Current AC-15 (I e )
Rated Short-time
Withstand Current (I cw )
Maximum Breaking
Capacity
Maximum Electrical
Switching Frequency
(220 / 230 / 240 V) 25 KWT
(380 / 400 V) 45 KWT
(415 V) 55 KWT
(440 V) 55 KWT
(500 V) 55 KWT
(690 V) 55 KWT
(400 V) 45 KWT
(220 / 240 V) 4 A
(24 / 127 V) 6 A
(500 V) 2 A
(690 V) 2 A
(400 / 440 V) 3 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 780 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 140 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 300 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1200 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 450 A
for 0.1 s 140 A
for 1 s 100 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1150 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 750 A
AC-1 600 cycles per hour
AC-2 / AC-4 150 cycles per hour
AC-3 1200 cycles per hour
AC-15 1200 cycles per hour
DC-13 900 cycles per hour
Rated Operational
Current DC-13 (I e )
(125 V) 0.55 A / 69 W
(24 V) 6 A / 144 W
(250 V) 0.27 A / 68 W
(48 V) 2.8 A / 134 W
(72 V) 1 A / 72 W
(110 V) 0.55 A / 60 W
(220 V) 0.27 A / 60 W
(400 V) 0.15 A / 60 W
(500 V) 0.13 A / 65 W
(600 V) 0.1 A / 60 W
Rated Insulation Voltage
acc. to UL/CSA 600 V
AFS96-30-22-11
(U i )
4
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
Rated Impulse
Withstand Voltage (U imp
)
8 kV
Maximum Mechanical
Switching Frequency
3600 cycles per hour
Rated Control Circuit
Voltage (U c )
50 Hz 24 ... 60 V
50 Hz / 60 Hz 24 ... 60 V
60 Hz 24 ... 60 V
DC Operation 20 ... 60 V
Operate Time
Between Coil De-energization and NC Contact Closing 19 ... 105 ms
Between Coil De-energization and NO Contact Opening 17 ... 100 ms
Between Coil Energization and NC Contact Opening 38 ... 95 ms
Between Coil Energization and NO Contact Closing 42 ... 100 ms
Connecting Capacity
Main Circuit
Rigid 1x 6 ... 70 m²
Rigid 2x 6 ... 50 m²
Flexible with Ferrule 1/2x 6 ... 50 m²
Flexible with Insulated Ferrule 1/2x 6 ... 50 m²
Connecting Capacity
Auxiliary Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5
Flexible with Insulated Ferrule 2x 0.75 ... 1.5
Flexible with Insulated Ferrule 1x 0.75 ... 2.5
Rigid 1/2x 1 ... 2.5 m²
Connecting Capacity
Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 m²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 m²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 m²
Rigid 1/2x 1 ... 2.5 m²
Wire Stripping Length
Degree of Protection
Auxiliary Circuit 10 mm
Control Circuit 10 mm
Main Circuit 17 mm
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Terminal Type
Screw Terminals
Dimensions
Product Net Width
Product Net Depth /
Length
70 mm
149 mm
Product Net Height
125.5 mm
Product Net Weight
1.27 kg
Popular Downloads
Instructions and
Manuals
1SBC101052M6801
Ordering
Minimum Order Quantity
Customs Tariff Number
Categories
Low Voltage Products and Systems → Control Products → Contactors → Block Contactors
1 piece
85364900
AFS96-30-22-11
5