PRO D U C T OV ERV I E W
Protecta Plus
MCB distribution board 250A Edition 1
2
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
—
Our electrical distribution
solutions upgrade power in
buildings to create safer, more
energy efficient and more
productive environments, enabling
our customers and their customers
to do more with less.
TA B L E O F C O N T E N T S
3
—
Table of contents
004 – 009 Introduction to Protecta Plus
010 – 021 Key modular components
022 – 047 Ordering codes
048 – 073 Technical information
074 – 075 Glossary
4
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
—
Protecta Plus
General features of the series
With the new Protecta Plus system, ABB has developed a new and personalised
series of MCB distribution boards which can be expanded over time. The wide
internal accessibility ensures a quick and easy approach to the electrical components
assembly. The neutral and earth bars positioned on the inner sides of the
distribution board are completely isolated to ensure better safety for users.
Main construction features
• Structure in epoxy coated metal sheets, 1 mm,
textured finish
• Wall installation for indoor environments
• Degree of protection - IP43 with door, IP30
without door
• Mechanical resistance: IK07
• Busbar rating: 250A
• Number of ways: 4, 8, 12, 16, 20, 24
• Maximum ambient temperature +35 °C
• Compliance with IEC BS EN 61439 1-2
• Simple wiring of all cabinets, both horizontally
and vertically
• Easy internal accessibility that facilitates all the
wiring operations and maintenance
• Prepackaged standardized kits for specific
applications (e.g. surge protection, metering)
A comprehensive range
The range consists of distribution boards for wall
mounting in six heights from 590 mm to 1360
mm, 450 mm width and depth starting from
125 mm, ensuring the development of multiple
solutions. Protecta Plus system is easy to design,
quick to assemble and reliable to apply.
Ease of wiring
With the new mounting concept, Protecta Plus
offers great levels of flexibility and accessibility
for installation and wiring. The internal module
can be easily removed allowing the wiring of
different equipment outside the distribution board.
This solution allows for an easier installation with
more rapid production times.
Maximum accessibility
Thanks to the particularly large opening angle of
the door, Protecta Plus offers the possibility to
have optimal access to the distribution board,
especially in case of maintenance. The perfectly
reversible doors can be installed with right
or left opening.
P R OT E C TA P LU S – G E N E R A L F E AT U R E S O F T H E S E R I E S
5
—
A series of rational solutions developed to achieve a complete
range of capabilities and functions with a single type of
distribution board to meet different installation requirements,
whilst simplifying the work of the installer.
Simplified series
connection
The distribution
boards can be
combined side-byside through pre-cut
cable conduit holes
large enough for the
passage of wiring
harnesses.
Range
depth: 125 mm;
width: 450 mm;
6 heights: 590, 730,
870, 1050, 1220,
1360 mm.
Ergonomics
and design
The design of
this series is
characterized by
special features,
such as rounded
edges for a
more efficient
ergonomic look.
High output
capacity
Primary branch
capacity up to 100A.
Complete
protection
Designed to ensure
maximum
protection and
efficiency, through
the prevision for the
installation of surge
protection devices
and counters.
Flexible mounting
The PAN assembly
system can easily be
removed from the
bottom distribution
board of the
framework, ensuring
quick and simple
installation.
6
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
—
Protecta Plus
The details make the difference
Board width
Protecta Plus has been designed with a width of 450 mm,
this combined with the reduced RCBO height of 115 mm
gives the installer ample cable room either side of the
board.
One Solution
All Protecta Plus boards come as standard with 250A main
bars. This gives the user a full range from 125A 3P through
to 250A 4P incoming options.
Incoming shroud
The shroud comes ready to accept a 125A 3P incoming
devices. The easy break technology and clear indication on
the rear allows the user to modify the shroud dependant
upon requirements up to 250A 4P.
100A Outgoing ways
The first two 3P outgoing ways are fitted with 3 mm branch
copper to allow for 100A MCBs to be fitted. This allows for a
maximum of 2 x 100A 3P or 6 x 100A 1P MCBs per board
removing the need to move up to high performance boards
or panel boards.
P R OT E C TA P LU S – T H E D E TA I L S M A K E T H E D I F F E R E N C E
7
Full MCB blank
To aid installation and safety a custom MCB blank has been
developed specifically for Protecta Plus.
Clean earth
Earth bars are fitted with removable links allowing the
boards to be configured for 50/100% clean earth.
Padlocking facilities
All outgoing devices on Protecta Plus can be padlocked in
on/off position for increased safety.
Metering and surge protection
Available in kit form to fit all Protecta Plus TPN boards.
The boards have been designed to house these integrally.
8
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
—
P R OT EC TA P L U S
The wide internal accessibility ensures
a quick and easy approach to the
electrical components assembly.
—
CMS
Circuit monitoring systems (CMS)
is a unique ultra-compact and
high-performance multichannel
measurement system for branch
monitoring power
9
—
P R OT EC TA P L U S
The wide internal accessibility ensures
a quick and easy approach to the
electrical components assembly.
10
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
—
Key modular components - MCB S 200
State-of-the-art safety
Twin terminal
for separate
feeding of busbar
and conductor.
Easy identification
of the product and
highly resistant
laser marking.
IP20
finger safety.
Save your time
all important data
available right
away.
Easy product name,
easy identification.
Quick identification
thanks to laser printed
EAN marking.
Contact position
indication
Captive screws
don’t loose what’s
important to you.
K E Y M O D U L A R C O M P O N E N T S - M C B S 2 0 0 – S TAT E - O F -T H E - A R T S A F E T Y
11
Contact position indication
All System pro M compact® MCBs are equipped with a contact position indication (CPI) on the toggle. You can easily
identify, if the MCB is in the ON or OFF position – easy and
safe maintenance work is possible.
Approvals printed on the dome
S 200 MCBs comply with IEC/EN 60898-1 and IEC/EN
60947-2 , as well as carrying the relevant approval marks for
the markets they are designed for. Certification markings
are printed on the dome of the MCB, making it possible to
see the markings when mounted.
Locking device for MCBs and RCBOs
Preventing unauthorised or dangerous operation of the
operating lever. An adaptor makes it possible to block the
operating lever whether switched ON or OFF. The lever is
blocked with a padlock having a cross bar section of 3 mm
or, as the case may be, 6 mm max. For multi-pole devices,
one lock may be fitted per pole.
IP 20 - finger safe terminals
The System pro M compact® MCBs are equiped with
35 mm² + 10 mm² cylinder lift twin terminals, a well proven
and reliable technology - designed for sopisticated
industrial use.
12
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
—
Key modular components - DSE201 M
Compact design, enhanced protection
Space for insulated screwdrivers
Equipped with cage type
terminals (16 mm² load side),
with tightening torque of 1.2 Nm.
In control
A test button allows the
regular check of the
functionality of the
device: to be pushed
every six months.
Earth fault indicator
Blue window in the
front of the device to
detect any earth fault
trip: the cause of trip
of the device can be
identified in a short
time, reducing the
downtime for
maintenance.
Combination with
auxiliary elements
New platform suitable
for quick installation in
combination with the
standard auxiliary
elements that can be
mounted with RCDs
and MCBs.
Easy to install
Fast installation is
supported by the two
flying leads for neutral
cable and functional
earth, each integrated in
the device, which can be
directly connected to
the main neutral and
earth bars.
Anti-counterfeiting
Equipped with an RFID
tag containing a unique
serial number assigned
by ABB in accordance to
ISO/IEC FCD 15693-3
standard in order to
authenticate the
product.
Real contact position
indicator below the toggle
Directly linked to the
moving contact of the
device, the green/red
window in the front of the
device can identify the
current position of the
contacts (open/closed)
independently on the
toggle position.
Reduced height
Thanks to its reduced
height, only 115 mm,
DSE201 M makes for
easier wiring operation
inside the consumer unit
or the distribution.
K E Y M O D U L A R C O M P O N E N T S - D S E 2 0 1 M - C O M PA C T D E S I G N , E N H A N C E D P R OT E C T I O N
13
—
With its breaking capacity of 10/15kA in only one module width
and 115 mm height, DSE201 M series is the perfect solution for a
complete protection in commercial and industrial applications,
where space optimization is required.
Device status at a glance
Earth fault indicator: blue window above the toggle to
immediately detect and identify any earth fault trip,
reducing downtime for maintenance. Contact position
indicator (CPI): green/red window below the toggle to
identify the real position of the contacts independently on
the toggle position.
Double slot terminal
Easy to install, , fail-safe line side, terminal to avoid
improper connection. Two slots of different dimensions
(35 mm2 and 10 mm2) available to allow the connection both
with cables and busbars.
Load side
The load side terminal accepts cables, both rigid and flexible
up to 16 mm2. Flying leads are straight instead of pigtail
ones to reduce the space required for wiring operations.
Easy and flexible
Double and bistable clips with a new design for a secure
fixing in any type of consumer unit or distribution board.
Easy removal from a cluster of RCBOs/MCBs supplied
with busbars.
14
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
—
Key modular components
A complete range for your surge protection
Standard pro M terminals
Designed for a better
coordination with the complete
ABB System pro M compact®
modular range.
Auxiliary Contact
Possibility to add an
auxiliary contact on the
OVR Plus range with the
standard ABB option.
Clear information
On the front of the
product indicating
the technical
characteristics of
the OVR product.
End-of-life indicator
The end-of-life indicator of the SPD
signals the status of the device.
Turning from green to red when the SPD
reaches the end of its life.
The optional safety reserve system has a
partial-release mechanism, which
provides a pre-failure warning.
K E Y M O D U L A R C O M P O N E N T S - O V R P LU S - A C O M P L E T E R A N G E F O R YO U R S U R G E P R OT E C T I O N
Complete coordination
The bi-directional cylindrical terminal block of the OVR Plus
range allows a complete coordination with the ABB
range with considerable time savings in wiring operations.
All the devices allow connection through busbars, both from
above and from below.
15
Pluggable feature
The pluggable feature of ABB OVR T1-T2, T2 and T2-T3 surge
protective devices (SPDs) facilitates maintenance. Should
one or more worn cartridges need to be replaced, the
electrical circuit does not have to be isolated nor do the
wires have to be removed.
PLE A S E
S U PPLY
I M AG E
Furse option for critical installations
The Furse ESP 415 CD40 provides continuous operation of
sensitive electronic systems in lightning intense
environments, offering market-leading levels of protection,
making it ideal for high-end applications, such as hospitals,
data centres and automated process control systems.
Active status indication
The Furse ESP 415 CD40 offers three way LED status
indication, showing full, reduced and no protection. It also
notifies the user of loss of phase, loss of power and warning
of excessive volts between N-E.
16
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
—
Key modular components Energy metering
Advanced energy performance analysis
—
01 Modern
sub-metering increases
energy efficiency
and saves money
by fair and accurate
cost distribution.
Requirements for a deliberate strategy to manage
and control energy consumption are having an
increasing impact on commercial buildings such
as shopping centers, offices, hotels and airports.
Electricity meters in commercial buildings are
usually acquired by the property owner and read
automatically via a facility or building
management system. Just like for private
property, modern sub-metering solutions can
increase energy efficiency in commercial
buildings and make considerable savings.
MID approval facilitates problem-free
cost distribution
Meters that are MID approved have the advantage
of a certified and verified metering accuracy. This
is important if discussions on the fairness of the
cost distribution arise.
EQ meters can easily help distribute consumption
costs between different tenants, e.g. stores and
boutiques in shopping malls, businesses in office
blocks, or different airlines and functions
(baggage handling, for example) at airports.
The fact that many commercial properties are not
designed from the beginning for sub-metering
presents no problem. EQ meters fit neatly
wherever they are needed.
—
01
Mandatory energy declarations
Commercial properties must have an energy declaration that describes the building’s energy performance. Its aim is to reduce the climate effect
and increase the efficient use of energy, i.e. benefits for both society and the building owner.
Energy declarations require that the electrical
consumption for lighting, elevators, heating and
ventilation, etc., be accounted for separately.
Data collected from individually-located meters
(sub-metering) are extremely valuable in this
respect. As well as being a legal requirement, it
highlights ways to increase efficiency by locating
unnecessary energy consumption.
ISO 50001, L2 building regulations, BREEAM
and others
Whichever you aim for, analyzing energy
consumption is an important early step and in the
end also the best way to maintain an achieved
level. EQ meters will provide accurate information
regarding the electrical energy consumption.
Max demand also cuts energy consumption*
Measuring the highest average power during a
set time interval results in the max demand value.
Measuring max demand helps dimension a
building’s electrical installations to its use.
17
KE Y MODUL AR COMPONENTS - ENERGY METERING
—
The EQ series are meters for single
phase and three phase metering. The
EQ series meters are mounted on a
DIN rail and are suitable for installation
in distribution boards and small
enclosures such as consumer units.
—
02
—
02 EQ series meters
The EQ series are suitable in applications where
there is a need for reliable energy measurements
and where space is limited.
General features
The EQ series meters are versatile meters for
many applications and installations. Navigating
the meter is easily done via the push-buttons
below the display. To configure the meter
settings, the set button must be accessed and
this button is protected against unauthorized use
when the transparent lid on the front of the meter
is closed and sealed. The power consumption of
the meter is very low, less than 0.8 VA.
Communication*
Data from the EQ series meters can be collected
via pulse output or serial communication. The
pulse output is a solid state relay that generates
pulses proportionally to the measured energy.
The meters can also be equipped with built-in
serial communication interfaces for M-Bus or
Modbus (RS-485).
Inputs and outputs*
The EQ series support two inputs and two
outputs in a fixed configuration. Inputs can be
used for counting pulses from e.g. a water meter,
or reading status from external devices. Outputs
can be used as pulse outputs or controlling
external apparatus like a contactor or an alarm
(connected via an external relay).
Approvals*
The EQ series meters are type approved
according to IEC and they are both type approved
and verified according to MID. MID is the
Measuring Instruments Directive 2004/22/EC
from the European Commission. MID type
approval and verification is mandatory for meters
in billing applications within EU and EEA. The
type approval is according to standards that
covers all relevant technical aspects of the meter.
These include climate conditions, electromagnetic
compatibility (EMC), electrical requirements,
mechanical requirements and accuracy.
* Dependant upon EQ Series metal selected
Instrumentation*
The EQ series meters support reading of
instrument values. A large number of electrical
properties can be read. Depending on version of
the meter the following data is available:
• Active power
• Apparent power
• Reactive power
• Current
• Voltage
• Frequency
• Power factor
18
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
—
Key modular components - CMS
Circuit monitoring systems
—
01 CMS-600
—
02 Connection
technology
CMS bus interface
A bus interface allows up to 96
sensors to be connected to the
Control Unit.
—
03 Double slot terminal
—
04 CMS sensors
Control Units
The Control Unit is a kind of
computing and
communication center that,
depending on the equipment
connected to it, evaluates the
different data picked up by
the sensors and makes it
available via the built-in
interfaces.
Serial interfaces
Depending on the unit,
numerous interfaces and
protocols are available to
ensure smooth network
implementation: RS485
(Modbus RTU), LAN (TCP/IP and
Modbus TCP).
Thanks to the built-in web
server, an internet browser or a
free Android or iOS app can be
used to visualize the values
measured. What’s more, the
measured values can also be
exported to CSV files.
19
K E Y M O D U L A R C O M P O N E N T S - C M S - C I R C U I T M O N I TO R I N G S Y S T E M S
—
The quality of a Circuit Monitoring System is dependent on the
strengths of the individual components and how well they
interact. ABB’s CMS sets the bar particularly high. Regardless of
whether we’re talking compactness, technology, measurement
results, user friendliness or flexibility, every component and
every feature of this CMS has been fully optimized in terms of
practicality and functionality.
Connection technology
Connecting the sensors to the
Control Unit is extremely
simple and requires no special
tools. All sensors are
connected to the Control Unit
by means of a flexible flat
cable and insulation
displacement connectors. The
positioning of sensors is fully
customizable so that they sit
exactly where a measurement
is required.
Sensors
The CMS sensors form the heart of the
system and they can be mounted
anywhere without any problem.
Initializing the sensors is also child’s
play, with the desired identifier being
assigned to each individual sensor via
the control unit in just a few simple
steps. The entire configuration and
commissioning procedure takes just a
matter of minutes. All measurement
functions are available immediately
following initialization.
—
01
—
02
—
03
—
04
20
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
—
Key modular components - ABB i-bus® KNX
Intelligent building solutions
—
01 The conventional
solution: Many
separate cables,
separate functionality,
little flexibility
—
02 The intelligent
solution: KNX – a
system, a standard,
with many interoperable
functions for
maximum flexibility
In many areas of our private and working lives,
the increasing level of automation is a trend that
confronts us on a daily basis without actually
being noticed.
—
Automation in buildings aims to
combine individual room
functions with one another and
to simplify the implementation of
individual customer preferences.
KNX is the logical development for implementing
traditional and new requirements in electrical
building installations, replacing conventional
installation techniques.
The intelligent installation bus system efficiently
performs the conventional functions and offers
an additional broad range of expanded features,
which could not be realized without a bus system.
—
01
ABB offers consultants, system integrators and
electrical installers a comprehensive product
range with ABB i-bus® KNX, in order to meet the
challenges posed to electrical building
installations both today and in the future.
Further information:
http://www.abb.com/knx
Intelligent Building Solutions with
ABB i-bus® KNX ensure:
• The right light in every situation by switching,
dimming and controlling lights
• Visual protection and protection against
sunlight by drive control of rolling shutters and
blinds
• The right room temperature in every room by
heating and cooling control
• The right air quality by controlling ventilation
and climatization
• Automatic functions controlled by timer,
movement, presence or meteorological data
• Security by monitoring operating conditions,
signaling technical faults, recognizing hazards
and triggering alarms
• Everything under control by visualization and
manual operation
—
02
Actuators
(command recipients)
230 V
KNX
bus
Sensors
(issue commands)
22
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
—
Protecta Plus
Order process
Protecta Plus DB
Vertical split-load board
Horizintal split-load board
Incoming kit
2 x Distribution boards
Meter/surge kits (optional)
Surge kits (optional)
MCB/RCBO/Blanks
Accessories
Surge kits (optional)
23
—
—
—
In many
Protecta
Plusareas of our private and
Protecta
Plus gives UK installers
Order
Codes lives, the increasing level
working
and designers the flexibility to
of automation is a trend that
cover all applications through
confronts us on a daily basis
standard and customised
without actually being noticed.
kit packages.
ABB I-BUS® KNX
P R OT EC TA P L U S
24
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
—
Protecta Plus
Order Codes
Pack contents: Standard distribution board
• 250A distribution bar
• RAL7035 textured finish
• Door closing latch
—
MCB distribution board - Type B
Description
Order codes
Protecta Plus DB 4 Way 250A
EPP-W304
Protecta Plus DB 8 Way 250A
EPP-W308
Protecta Plus DB 12 Way 250A
EPP-W312
Protecta Plus DB 16 Way 250A
EPP-W316
Protecta Plus DB 20 Way 250A
EPP-W320
Protecta Plus DB 24 Way 250A
EPP-W324
Pack contents: Horizontal split load kit
• 2 x MID, Modbus ( RS485 ) & Pulse Meters
• Associated CTs
• Incoming isolators
• Internal cables
• Requires 2 x MCB distribution board - Type B
Please note as these kits allow for 4 to 24way
boards cutting and crimping of cables is required.
—
Horizontal split load kit
Description
Order codes
125A 3P Horizontal split load kit - 2 x Meters
EPP-HSL-1253P
125A 4P Horizontal split load kit - 2 x Meters
EPP-HSL-1254P
160A 3P Horizontal split load kit - 2 x Meters
EPP-HSL-1603P
160A 4P Horizontal split load kit - 2 x Meters
EPP-HSL-1604P
250A 3P Horizontal split load kit - 2 x Meters
EPP-HSL-2503P
250A 4P Horizontal split load kit - 2 x Meters
EPP-HSL-2504P
P R OT E C TA P LU S – O R D E R C O D E S
25
—
Protecta Plus
Order Codes
Pack contents: Vertical Split Load Boards
• 2/3 MID, Modbus ( RS485 ) & Pulse Meters
• Associated CTs
• Incoming terminals
• Internal cables
Please note, no additional assembly is required.
Units will be delivered with meters
pre-configured to internal C.T sizing.
—
Vertical Split Load Boards - 42 variations are available
Order codes
EPP-VSL84
No. of outgoing
Incomer rating (A)
8+4 TPN
EPP-VSL88
8+8 TPN
EPP-VSL128
12+8 TPN
EPP-VSL1212
12+12 TPN
EPP-VSL168
16+8 TPN
EPP-VSL844
8+4+4 TPN
EPP-VSL1284
12+8+4 TPN
Example order codes
EPP-VSL1212-1253P 12+12 Way 125A 3P
EPP-VSL168-2503P 16+8 Way 250A 3P
Vertical DB CT ratios
Dual 125 125+100
Dual 160 160+125
Dual 250 250+160
Tri 125 125+100+100
Tri 160 160+125+100
Tri 250 250+160+125
Boards are supplied fully assembled and metering devices configured to C.T. ratio's
-125
-160
-250
No. of poles
3P
4P
26
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
—
Protecta Plus
Order Codes
Pack contents: Incoming kit
• Copper connection kit and fittings
• Incoming device
• Cover plate
• Instruction leaflet
—
Incoming connection kit
Description
Order codes
125A 3P Switch incoming connection kit
EPP-1253P
125A 4P Switch incoming connection kit
EPP-1254P
100A 4P RCD incoming connection kit 30mA Type AC - Left side neutral
EPP-1004R
160A 3P Switch incoming connection kit
EPP-1603P
160A 4P Switch incoming connection kit
EPP-1604P
250A 3P Switch incoming connection kit
EPP-2503P
250A 4P Switch incoming connection kit
EPP-2504P
Pack contents: Incoming metering
• 1 x Meter
• 1 x C.T Block
• 1 x Wiring Loom & DIN support
• Instruction leaflet
Please note as these kits allow for 4 to 24way
boards cutting and crimping of cables is required.
—
Incoming metering
Description
125A MID Approved c/w pulse output
Order codes
EPP-METMOD125A
125A MID Approved c/w pulse output & Modbus ( RS485 )
EPP-METMOD125B
125A MID Approved c/w pulse output, Modbus ( RS485 ) Imp / Exp
EPP-METMOD125C
160A MID Approved c/w pulse output
EPP-METMOD160A
160A MID Approved c/w pulse output & Modbus ( RS485 )
EPP-METMOD160B
160A MID Approved c/w pulse output, Modbus ( RS485 ) Imp / Exp
EPP-METMOD160C
250A MID Approved c/w pulse output
EPP-METMOD250A
250A MID Approved c/w pulse output & Modbus ( RS485 )
EPP-METMOD250B
250A MID Approved c/w pulse output, Modbus ( RS485 ) Imp / Exp
EPP-METMOD250C
P R OT E C TA P LU S – O R D E R C O D E S
27
—
Protecta Plus
Order Codes
Pack contents: Surge protection
• 1 x Surge unit
• 1 x MCB 3P
• 1 x Wiring Loom & DIN support
• Instruction leaflet
Please note as these kits allow for 4 to 24way
boards cutting and crimping of cables is required.
—
Surge protection
Description
Order codes
Type 2 surge protection - including 63A 3P MCB
EPP-SOULE
Type 2/3 surge protection - including 63A 3P MCB
EPP-FURSE
Pack contents: Contactor control
• 3P contactor
• Control circuit & fuse protection
• Instruction leaflet
—
Contactor Control
Description
Order codes
125A AC1 rated 3P Contactor
EPP-CON125
160A AC1 rated 3P Contactor
EPP-CON160
250A AC1 rated 3P Contactor
EPP-CON250
28
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
—
Protecta Plus
Order Codes
Pack contents: Top extension boxes
• Fixings
• DIN rail / mounting plate
• RAL7035 textured finish
—
Extension boxes
Dimensions (mm)
Type
No. of
modules
Height
(W x D)
Hinged door with 1 DIN rail
16
200
450 x 130
Order codes
EPP-R1016
Hinged door with 2 DIN rail
32
400
450 x 130
EPP-R2032
Plain extension box 200mm
200
450 x 130
EPP-EB20
Plain extension box 400mm
400
450 x 130
EPP-EB40
Pack contents: Type A distribution
• Supplied factory fitted with 100A switch
disconnector
• RAL7035 textured finish
—
MCB Distribution board - Type A
Description
Order codes
Protecta Plus DB 4way 100A
HSMS4C
Protecta Plus DB 7way 100A
HSMS7C
Protecta Plus DB 11way 100A
HSMS11C
Protecta Plus DB 16way 100A
HSMS16C
Protecta Plus DB 20way 100A
HSMS20C
P R OT E C TA P LU S – O R D E R C O D E S
29
—
Protecta Plus
Order Codes
Pack contents: Row type boards
• Fixings
• DIN rail / mounting plate
• RAL7035 textured finish
—
Row type extension boxes
Dimension
No. of modules
No. of
rows
Sided
width
Height
Order codes
36
2
4way DB
590
EPP-R2036
54
3
8way DB
730
EPP-R3054
72
4
12way DB
870
EPP-R4072
90
5
16way DB
1050
EPP-R5090
108
6
20way DB
1220
EPP-R6108
126
7
24way DB
1360
EPP-R7126
—
Additional N/PE for side extension boxes
Description
Order codes
Protecta Plus - Row Type N-Bar 9
EPP-N-09
Protecta Plus - Row Type N-Bar 13
EPP-N-13
Protecta Plus - Row Type N-Bar 17
EPP-N-17
Protecta Plus - Row Type N-Bar 21
EPP-N-21
Protecta Plus - Row Type E-Bar 9
EPP-PE-09
Protecta Plus - Row Type E-Bar 13
EPP-PE-13
Protecta Plus - Row Type E-Bar 17
EPP-PE-17
Protecta Plus - Row Type E-Bar 21
EPP-PE-21
—
Terminal cover
Description
Protecta Plus - Top Shroud
Order codes
EPP-TC
Protecta Plus Mains TS - 4 Way
EPP-MTCO4
Protecta Plus Mains TS - 8 Way
EPP-MTCO8
Protecta Plus Mains TS - 12 Way
EPP-MTC12
Protecta Plus Mains TS - 16 Way
EPP-MTC16
Protecta Plus Mains TS - 20 Way
EPP-MTC20
Protecta Plus Mains TS - 20 Way
EPP-MTC24
30
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
—
Protecta Plus
Order Codes
—
Labels for outgoing circuits
No. of ways
Order codes
4
EPP KIT-LAB04W
8
EPP KIT-LAB08W
12
EPP KIT-LAB12W
16
EPP KIT-LAB16W
20
EPP KIT-LAB20W
24
EPP KIT-LAB24W
—
Replacement doors
Description
Order codes
Protecta Plus Trans Door - 4 ways / 2 rows
EPP-TD-04
Protecta Plus Trans Door - 8 ways / 3 rows
EPP-TD-08
Protecta Plus Trans Door - 12 ways / 4 rows
EPP-TD-12
Protecta Plus Trans Door - 16 ways / 4 rows
EPP-TD-16
Protecta Plus Trans Door - 20 ways / 5 rows
EPP-TD-20
Protecta Plus Trans Door - 24 ways / 6 rows
EPP-TD-24
Protecta Plus Solid Door - 4 ways / 2 rows
EPP-ST-04
Protecta Plus Solid Door - 8 ways / 3 rows
EPP-ST-08
Protecta Plus Solid Door - 12 ways / 4 rows
EPP-ST-12
Protecta Plus Solid Door - 16 ways / 4 rows
EPP-ST-16
Protecta Plus Solid Door - 20 ways / 5 rows
EPP-ST-20
Protecta Plus Solid Door - 24 ways / 6 rows
EPP-ST-24
—
Accessories
Description
MCB Blank RAL7035 Grey
MCB Blank RAL9004 Black
Lock And Key
Side By Side Connection Kit
Padlock Adaptor
EPP-BP1
EPP-BP1B
EPP-LK KEY
EPP-KIT JOIN
SA 1
Padlock C/W 2 X Keys
SA 2
125A Single Phase Kit
EPP-KIT-1251P*
250A Single Phase Kit
EPP-KIT-2501P**
Trunking adaptor plate
* Requires kit EPP-1254P
Order codes
EPP-TRADT
Protecta Plus - Glandplate Plain
EPP-GP-B
Protecta Plus - Glandplate K Os
EPP-GP KO
19 Modules 30 mm Busbar
PS1/19/30
** Required kit EPP-2504P
MBC S – ORDER CODES
31
—
P R OT EC TA P L U S
ABB has developed a new and
personalised series of MCB
distribution boards which can be
expanded over time.
32
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
—
MCB - S 200 M series
Order codes
—
S 200 series M B
Rated
current
in A
6
Rated current in kA
Order codes
IEC/EN 60898-1
IEC/EN 60947-2
1 Pole
3 Pole
10kA/15kA
S201M-B6
S203M-B6
S203M-B10
10
10kA/15kA
S201M-B10
13
10kA/15kA
S201M-B13
S203M-B13
16
10kA/15kA
S201M-B16
S203M-B16
20
10kA/15kA
S201M-B20
S203M-B20
25
10kA/15kA
S201M-B25
S203M-B25
32
10kA/15kA
S201M-B32
S203M-B32
40
10kA/15kA
S201M-B40
S203M-B40
50
10kA/15kA
S201M-B50
S203M-B50
63
10kA/15kA
S201M-B63
S202M-B63
80A
6kA
S201-B80
S203-B80
100A
6kA
S201-B100
S203-B100
—
S 200 series M C
Rated
current
in A
Rated current in kA
Order codes
IEC/EN 60898-1
IEC/EN 60947-2
1 Pole
3 Pole
6
10kA/15kA
S201M-C6
S203M-C6
10
10kA/15kA
S201M-C10
S203M-C10
13
10kA/15kA
S201M-C13
S203M-C13
16
10kA/15kA
S201M-C16
S203M-C16
20
10kA/15kA
S201M-C20
S203M-C20
25
10kA/15kA
S201M-C25
S203M-C25
32
10kA/15kA
S201M-C32
S203M-C32
40
10kA/15kA
S201M-C40
S203M-C40
50
10kA/15kA
S201M-C50
S203M-C50
63
10kA/15kA
S201M-C63
S202M-C63
80A
6kA
S201-C80
S203-C80
100A
6kA
S201-C100
S203-C100
—
S 200 series M D
Rated
current
in A
Rated current in kA
IEC/EN 60898-1
IEC/EN 60947-2
Order codes
1 Pole
3 Pole
6
10kA/15kA
S201M-D6
S203M-D6
10
10kA/15kA
S201M-D10
S203M-D10
13
10kA/15kA
S201M-D13
S203M-D13
16
10kA/15kA
S201M-D16
S203M-D16
20
10kA/15kA
S201M-D20
S203M-D20
25
10kA/15kA
S201M-D25
S203M-D25
32
10kA/15kA
S201M-D32
S203M-D32
40
10kA/15kA
S201M-D40
S203M-D40
50
10kA/15kA
S201M-D50
S203M-D50
63
10kA/15kA
S201M-D63
S202M-D63
Please see glossary for complete MCB offering.
MCB - S 20 0 SERIES - ORDER CODES
33
—
MCB - S 200 P series
Order codes
—
S 200 series P B
Rated
current
in A
Rated current in kA
Order codes
IEC/EN 60898-1
1 Pole
3 Pole
6
25kA
S201P-B6
S203P-B6
10
25kA
S201P-B10
S203P-B10
13
25kA
S201P-B13
S203P-B13
16
25kA
S201P-B16
S203P-B16
20
25kA
S201P-B20
S203P-B20
25
25kA
S201P-B25
S203P-B25
32
15kA
S201P-B32
S203P-B32
40
15kA
S201P-B40
S203P-B40
50
15kA
S201P-B50
S203P-B50
63
15kA
S201P-B63
S203P-B63
—
S 200 series P C
Rated
current
in A
Rated current in kA
Order codes
IEC/EN 60898-1
1 Pole
3 Pole
6
25kA
S201P-C6
S203P-C6
10
25kA
S201P-C10
S203P-C10
13
25kA
S201P-C13
S203P-C13
16
25kA
S201P-C16
S203P-C16
20
25kA
S201P-C20
S203P-C20
25
25kA
S201P-C25
S203P-C25
32
15kA
S201P-C32
S203P-C32
40
15kA
S201P-C40
S203P-C40
50
15kA
S201P-C50
S203P-C50
63
15kA
S201P-C63
S203P-C63
—
S 200 series P D
Rated
current
in A
Rated current in kA
IEC/EN 60898-1
Order codes
1 Pole
3 Pole
6
25kA
S201P-D6
S203P-D6
10
25kA
S201P-D10
S203P-D10
13
25kA
S201P-D13
S203P-D13
16
25kA
S201P-D16
S203P-D16
20
25kA
S201P-D20
S203P-D20
25
25kA
S201P-D25
S203P-D25
32
15kA
S201P-D32
S203P-D32
40
15kA
S201P-D40
S203P-D40
50
15kA
S201P-D50
S203P-D50
63
15kA
S201P-D63
S203P-D63
Please see glossary for complete MCB offering.
34
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
—
RCBO DSE201 M - Type A
Order codes
—
DSE201 M - Type A
Rated
residual
current IΔn [mA]
Rated
current
in A
10
6
30
100
300
Rated current in kA
Order codes
B Characteristic
C Characteristic
10kA/15kA
DSE201 M B6 A10
DSE201 M C6 A10
10
10kA/15kA
DSE201 M B10 A10
DSE201 M C10 A10
16
10kA/15kA
DSE201 M B16 A10
DSE201 M C16 A10
20
10kA/15kA
DSE201 M B20 A10
DSE201 M C20 A10
DSE201 M C25 A10
25
10kA/15kA
DSE201 M B25 A10
32
10kA/15kA
DSE201 M B32 A10
DSE201 M C32 A10
40
10kA/15kA
DSE201 M B40 A10
DSE201 M C40 A10
50
10kA
DSE201 M B50 A10
DSE201 M C50 A10
6
10kA/15kA
DSE201 M B6 A30
DSE201 M C6 A30
10
10kA/15kA
DSE201 M B10 A30
DSE201 M C10 A30
16
10kA/15kA
DSE201 M B16 A30
DSE201 M C16 A30
20
10kA/15kA
DSE201 M B20 A30
DSE201 M C20 A30
25
10kA/15kA
DSE201 M B25 A30
DSE201 M C25 A30
32
10kA/15kA
DSE201 M B32 A30
DSE201 M C32 A30
40
10kA/15kA
DSE201 M B40 A30
DSE201 M C40 A30
50
10kA
DSE201 M B50 A30
DSE201 M C50 A30
6
10kA/15kA
DSE201 M C6 A100
10
10kA/15kA
DSE201 M C10 A100
16
10kA/15kA
DSE201 M C16 A100
20
10kA/15kA
DSE201 M C20 A100
25
10kA/15kA
DSE201 M C25 A100
32
10kA/15kA
DSE201 M C32 A100
40
10kA/15kA
DSE201 M C40 A100
50
10kA
DSE201 M C50 A100
6
10kA/15kA
DSE201 M C6 A300
10
10kA/15kA
DSE201 M C10 A300
16
10kA/15kA
DSE201 M C16 A300
20
10kA/15kA
DSE201 M C20 A300
DSE201 M C25 A300
25
10kA/15kA
32
10kA/15kA
DSE201 M C32 A300
40
10kA/15kA
DSE201 M C40 A300
50
10kA
DSE201 M C50 A300
35
RCBO DSE201 M - T YPE AC – ORDER CODES
—
RCBO DSE201 M - Type AC
Order codes
—
DSE201 M - Type AC
Rated current in kA
Order codes
Rated
residual
current IΔn [mA]
Rated
current
in A
B Characteristic
C Characteristic
10
6
10kA/15kA
DSE201 M B6 AC10
DSE201 M C6 AC10
10
10kA/15kA
DSE201 M B10 AC10
DSE201 M C10 AC10
16
10kA/15kA
DSE201 M B16 AC10
DSE201 M C16 AC10
20
10kA/15kA
DSE201 M B20 AC10
DSE201 M C20 AC10
DSE201 M C25 AC10
30
100
300
25
10kA/15kA
DSE201 M B25 AC10
32
10kA/15kA
DSE201 M B32 AC10
DSE201 M C32 AC10
40
10kA/15kA
DSE201 M B40 AC10
DSE201 M C40 AC10
50
10kA
DSE201 M B50 AC10
DSE201 M C50 AC10
6
10kA/15kA
DSE201 M B6 AC30
DSE201 M C6 AC30
10
10kA/15kA
DSE201 M B10 AC30
DSE201 M C10 AC30
16
10kA/15kA
DSE201 M B16 AC30
DSE201 M C16 AC30
20
10kA/15kA
DSE201 M B20 AC30
DSE201 M C20 AC30
25
10kA/15kA
DSE201 M B25 AC30
DSE201 M C25 AC30
32
10kA/15kA
DSE201 M B32 AC30
DSE201 M C32 AC30
40
10kA/15kA
DSE201 M B40 AC30
DSE201 M C40 AC30
50
10kA
DSE201 M B50 AC30
DSE201 M C50 AC30
6
10kA/15kA
DSE201 M C6 AC100
10
10kA/15kA
DSE201 M C10 AC100
16
10kA/15kA
DSE201 M C16 AC100
20
10kA/15kA
DSE201 M C20 AC100
25
10kA/15kA
DSE201 M C25 AC100
32
10kA/15kA
DSE201 M C32 AC100
40
10kA/15kA
DSE201 M C40 AC100
50
10kA
DSE201 M C50 AC100
6
10kA/15kA
DSE201 M C6 AC300
10
10kA/15kA
DSE201 M C10 AC300
16
10kA/15kA
DSE201 M C16 AC300
20
10kA/15kA
DSE201 M C20 AC300
DSE201 M C25 AC300
25
10kA/15kA
32
10kA/15kA
DSE201 M C32 AC300
40
10kA/15kA
DSE201 M C40 AC300
50
10kA
DSE201 M C50 AC300
36
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
—
RCCB F 200 series AC type
Order Codes
—
F 200 AC type - F202
Number
of poles
Rated
residual
current IΔn [mA]
Rated
current
in A
Order codes
2
10
16
F202 AC-16/0.01
30
100
300
500
25
F202 AC-25/0.01
25
F202 AC-25/0.03
40
F202 AC-40/0.03
63
F202 AC-63/0.03
80
F202 AC-80/0.03
100
F202 AC-100/0.03
25
F202 AC-25/0.1
40
F202 AC-40/0.1
63
F202 AC-63/0.1
80
F202 AC-80/0.1
100
F202 AC-100/0.1
25
F202 AC-25/0.3
40
F202 AC-40/0.3
63
F202 AC-63/0.3
80
F202 AC-80/0.3
100
F202 AC-100/0.3
25
F202 AC-25/0.5
40
F202 AC-40/0.5
63
F202 AC-63/0.5
80
F202 AC-80/0.5
100
F202 AC-100/0.5
RCCB F 20 0 SERIES – ORDER CODES
37
—
RCCB F 200 series AC type
Order Codes
—
F 200 AC type - F204
Number
of poles
Rated
residual
current IΔn [mA]
Rated
current
in A
Order codes
4
30
25
F204 AC-25/0.03
40
F204 AC-40/0.03
100
300
500
63
F204 AC-63/0.03
80
F204 AC-80/0.03
100
F204 AC-100/0.03
25
F204 AC-25/0.1
40
F204 AC-40/0.1
63
F204 AC-63/0.1
80
F204 AC-80/0.1
100
F204 AC-100/0.1
25
F204 AC-25/0.3
40
F204 AC-40/0.3
63
F204 AC-63/0.3
80
F204 AC-80/0.3
100
F204 AC-100/0.3
25
F204 AC-25/0.5
40
F204 AC-40/0.5
63
F204 AC-63/0.5
80
F204 AC-80/0.5
100
F204 AC-100/0.5
38
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
—
Metering EQ series
Order codes
—
A series - A41
80A SPN 4mod
Description
Order codes
Pulse output
A41 111 - 100
Pulse output, RS-485
A41 112 - 100
Pulse output, M-Bus
A41 113 - 100
2 output, 2 input, RS-485
A41 312 - 100
2 output, 2 input. M-Bus
A41 313 - 100
—
A series - A43
80A TPN 7mod
Description
Order codes
Pulse output
A43 111 - 100
Pulse output, RS-485
A43 112 - 100
Pulse output, M-Bus
A43 113 - 100
2 output, 2 input, RS-485
A43 312 - 100
2 output, 2 input, M-Bus
A43 313 - 100
—
B series - B21
65A SPN 2mod
Description
Order codes
Pulse output
B21 111 - 100
Pulse output, RS-485
B21 112 - 100
Pulse output, M-Bus
B21 113 - 100
2 output, 2 input, RS-485
B21 312 - 100
2 output, 2 input, M-Bus
B21 313 - 100
—
B series - B23
65A TPN 4mod
Description
Order codes
Pulse output
B23 111 - 100
Pulse output, RS-485
B23 112 - 100
Pulse output, M-Bus
B23 113 - 100
2 output, 2 input, RS-485
B23 312 - 100
2 output, 2 input, M-Bus
B23 313 - 100
C I R C U I T M O N I TO R I N G S T Y S T E M - C M S - O R D E R C O D E S
39
—
Circuit Monitoring System - CMS
Order Codes
ABB's circuit monitoring system (CMS) is a unique
ultra-compact and high-performance multi-channel
measurement system for branch monitoring.
The system consists of a control unit and sensors
with different measurement ranges and mounting
possibilities.
—
Open core sensors Open-core sensors 18 mm for Pro M & SMISSLINE installation devices with twin terminals
Description
80 A
0rder codes
CMS-120PS
40 A
CMS-121PS
20 A
CMS-122PS
—
Open core sensors Open-core sensors 18 mm for DIN rail mounting (universally usable)
Description
0rder codes
80 A
CMS-120DR
40 A
CMS-121DR
20 A
CMS-122DR
—
Control Units
Description
0rder codes
Control Unit CMS-600
CMS-600
Control Unit CMS-700
CMS-700
For more detailed information see p66.
—
Accessories
Description
0rder Codes
Cable 5m
CMS-802
Sensor connectors ( 35pcs )
CMS-820
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
40
—
ESB installation contactors
Order Codes
These devices are specifically made for
commanding loads and signalling electrical
conditions in any low-voltage distribution board.
The functions of these devices are particularly
switching, pushing and signalling electrical
conditions in any installations (low-voltage area)
—
ESB 24
Main
poles
2 N.O.
A1
A2
40-50 Hz
DC
Order codes
2
24 V
24 V
ESB 24-20*
230...240 V
230...240 V
ESB 24-20*
12 V
12 V
ESB 24-40*
24 V
24 V
ESB 24-40*
3
1
4
2
4 N.O.
2
A1
1
3
5
7
A2
2
4
6
8
4 N.C.
2
A1
R1
R3
R5
R7
A2
R2
R4
R6
R8
2 N.O. 2 N.C.
2
A1
1
R3
R5
7
A2
2
R4
R6
8
2
3 N.O. 1 N.C.
A1
1
R3
5
7
A2
2
R4
6
8
2
4 N.O. 3 N.C.
A1
A2
Control coil voltage
Number
of
modules
R1
3
R5
R7
R2
4
R6
R8
* Ensure voltage is selected
110...120 V
110...120 V
ESB 24-40*
230...240 V
230...240 V
ESB 24-40*
12 V
12 V
ESB 24-04*
24 V
24 V
ESB 24-04*
110...120 V
110...120 V
ESB 24-04*
230...240 V
230...240 V
ESB 24-04*
12 V
12 V
ESB 24-22*
24 V
24 V
ESB 24-22*
110...120 V
110...120 V
ESB 24-22*
230...240 V
230...240 V
ESB 24-22*
12 V
12 V
ESB 24-31*
24 V
24 V
ESB 24-31*
110...120 V
110...120 V
ESB 24-31*
230...240 V
230...240 V
ESB 24-31*
12 V
12 V
ESB 24-13*
24 V
24 V
ESB 24-13*
110...120 V
110...120 V
ESB 24-13*
230...240 V
230...240 V
ESB 24-13*
41
E S B I N S TA L L AT I O N C O N TA C TO R S – O R D E R C O D E S
—
ESB installation contactors
Order Codes
—
ESB 40
Control coil voltage
Main
poles
Number
of modules
40-50 Hz
DC
Order codes
4 N.O.
3
12 V
12 V
ESB 40-40*
24 V
24 V
ESB 40-40*
110...120 V
110...120 V
ESB 40-40*
230...240 V
230...240 V
ESB 40-40*
24 V
24 V
ESB 40-22*
230 V
230 V
ESB 40-22*
A2
5
3
1
A1
6
4
2
7
8
2 N.C.
3
A1
1
R3
R5
7
A2
2
R4
R6
8
1
R3
5
7
2
R4
6
8
1 N.C.
3
A1
A2
3 N.O.
3
A1
1
3
5
A2
2
4
6
2 N.O.
3
A1
1
3
A2
2
4
24 V
24 V
ESB 40-31*
230 V
230 V
ESB 40-31*
24 V
24 V
ESB 40-30*
230 V
230 V
ESB 40-30*
24 V
24 V
ESB 40-20*
230 V
230 V
ESB 40-20*
* Ensure voltage is selected
—
ESB 63
Control coil voltage
Main
poles
Number
of modules
40-50 Hz
DC
Order codes
4 N.O.
3
12 V
12 V
ESB 63-40*
24 V
24 V
ESB 63-40*
110...120 V
110...120 V
ESB 63-40*
230...240 V
230...240 V
ESB 63-40*
110 V
110 V
ESB 63-31*
230 V
230 V
ESB 63-31*
230 V
230 V
ESB 63-30*
400 V
400 V
ESB 63-30*
A2
5
3
1
A1
6
4
2
7
8
1 N.C.
3
A1
1
R3
5
7
A2
2
R4
6
8
3 N.O.
3
A1
1
3
5
A2
2
4
6
2 N.O.
3
A1
1
3
A2
2
4
1 N.O. 1 N.C.
3
A1
1
R3
A2
2
R4
* Ensure voltage is selected
24 V
24 V
ESB 63-20*
230 V
230 V
ESB 63-20*
230 V
230 V
ESB 63-11*
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
42
—
D Line digital time switches
Order Codes
D Line weekly digital time switches
The unique design, with white backlit LCD display,
and extreme ease of use with two lines of text
menu and only four buttons, make D Line ideal to
automate the installation functions.
Thanks to the innovative management of time
vacation, the D Line digital time switches allow
the exclusion of the normal weekly program in
one or more periods of several years or between
two different years.
The range includes 1 and 2 channel versions,
equipped with large capacity internal battery to
maintain operation without power supply and
permanent memory EEPROM, to avoid the risk of
program loss and to maintain the date and time
settings in the event of power failure, irrespective
of its duration.
The “Plus” version can transfer different types of
program by using a D KEY to be quickly copied in
using no digital time switches, avoiding the
errors due to future modification. The
“SYNCHRO” version can be coupled to the D
DCF77 antenna, that allows an automatic
synchronization of the digital time switch with
the Frankfurt DCF77 time signal, or can be
coupled to the D GPS antenna to allows
synchronization received from the Global
Positioning System.
The D Line is particularly useful in environments
and situations where user management is
required with a time schedule flexible enough to
predict or exclude activities according to time
and day of week or month.
—
D Line switches
Channels no.
D1
Type
Order codes
D1
2CSM258763R0621
1
D1 PLUS
2CSM257583R0621
1
D1 SYNCHRO
2CSM257493R0621
2
D2
2CSM256313R0621
1
D1 Plus
2
D2 PLUS
2CSM277583R0621
2
D2 SYNCHRO
2CSM277363R0621
—
Accessories
Versions
Programming key
Programming software
DCF77 antenna
GPS antenna
Please see page 70 for explanation of types
Type
Order codes
D KEY
2CSM277143R0621
D SW
2CSM299973R0621
D DCF77
2CSM299983R0621
D GPS
2CSM299993R0621
43
D/ T L I N E D I G I TA L T I M E S W I TC H E S – O R D E R C O D E S
—
T Line modular twilight switches
Order Codes
—
01 T1
—
02 T1 PLUS
—
03 LS-D
T Line modular twilight switches
These twilight switches allow to switch ON and
switch OFF lighting devices according to a
scheduled level of the ambient light. They are
used in combination with an external sensor to
detect if the ambient light is higher or lower than
the set level.
A switching delay prevents them from operating
unnecessarily when the light intensity suddenly
changes (e.g. lightning, moving vehicles, etc.). The
T1 twilight switch in 1 channel is preset at 10 lux.
from factory and is equipped with 2 signalling
LEDs that indicate the setpoint value and display
the status of the contact . The operating
instructions are printed on the side of the
product. T1 PLUS switches feature a setpoint that
can be adjusted for 4 different scale values (2:40,
20:200, 200:2000, 2000:15000).This makes them
ideal for daytime applications where the lux
values are very high. With a 10 lux preset factory
setting, they are equipped with 2 signalling LEDs
that indicate the setpoint value and display the
status of the contact.
—
T Line modular twilight switches
Brightness range
lux
2:200
2:15000
Accessories for T Line modular twilight switches
The external sensor is supplied in the same
package of the switch, but it’s also available
separately as spare part. The upper part of the
external case (with screw locking), is made up of
Type
Order codes
T1
2CSM295563R1341
T1 PLUS
2CSM295793R1341
thermoplastic materials and bears up against
ultraviolet rays to guarantee a homogeneous
diffusion of the daylight internally. LS-D is also
equipped with a cable gland.
—
Accessories
—
01
Brightness range
lux
Type
Order codes
External sensor
LS-D
2CSM295723R1341
—
02
—
03
44
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
—
Modular sockets
Order Codes
—
British standard modular sockets
Colour
M1363
Modules
Order codes
Grey
3
M1363
Grey with light
3
M1363-L
—
E 90 fuse switch disconnectors
Order Codes
E 90 series fuse switch disconnectors are
designed for switching circuits under load,
providing protection against short circuits and
overloads. The case is made of self-extinguishing
thermoplastic material resistant to high
temperatures (all materials are UL listed) while
the contact clips are in silver plated copper.
E 90 fuse switch disconnectors can be sealed or
padlocked to ensure operator safety during
maintenance. Versions with blown fuse indicator
allow to check whether the fuse is still working
correctly or not. For easy and quick installation E
90 range is totally compatible with connecting
bars, terminals and caps of S 200 MCBs.
Thanks to cURus approval, they can be installed in
UL certified machines.
—
E 90 fuse switch disconnectors for 10.3 x 38 mm fuses (AC-22B)
Rated
current
In
Modules
1
32
1
E 91/32
1
32
1
E 91/32s
3
32
3
E 93/32
3
32
3
E 93/32s
Number
of poles
E92
E94
E94
Fuses not included
Order codes
45
—
CMS
The CMS system allows users
to measure AC and DC
currents for up to 64
individual lines. Data can be
remotely monitored via
desktop or mobile device app.
46
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
—
Protecta Plus
Technical specifications
—
Technical features
Description
Standards/requirements
IEC BS EN 61439-1&2, ed.2 (2011-08)
Rated current
Maximum load
250A at ambient temperature +35°
Rated operational voltage (Ue)
415 V AC
Rated frequency
50/60 Hz
Rated insulation voltage (Ui)
690 V
Rated conditional short circuit current (Icc)
35 kA
Neutral size
2 Brass bar each size (7*10) mm
Earth size
2 Brass bars each size (7*10) mm
Degree of protection
Mechanical impact strength
With Door
IP 43
Pan Assembly
IP 20
Cabinet enclosures
IK 07
Housing and door material
Material Type
Cold rolled sheet steel 1 mm
Color
RAL 7035
Coating Type (Powder or)
Electrostatic powder coating, textured finish
Door opening angle
180°
Position of knockouts
Top and bottom
Type of Door Closure
Latch (Optional Lock)
Incoming cable connections*
125A >50 mm
160A >70 mm
250A >95 mm
*For requirements above stated figures seek advise from technical services
P R OT E C TA P LU S – D I M E N S I O N S
47
—
Protecta Plus
Dimensions
—
01 Type B
Distribution
boards
—
Type B Distribution boards
—
02 Extension
boxes
Height
mm
Width
mm
Depth
mm
M1
mm
M2
mm
EPP-W304
590
450
125
358
500
EPP-R2036
590
450
125
358
500
EPP-W308
730
450
125
358
640
EPP-R3054
730
450
125
358
640
EPP-W312
870
450
125
358
780
EPP-R4072
870
450
125
358
780
EPP-W316
1,050
450
125
358
960
EPP-R5090
1,050
450
125
358
960
EPP-W320
1,220
450
125
358
1,130
EPP-R6108
1,220
450
125
358
1,130
EPP-W324
1,360
450
125
358
1,270
EPP-R7126
1,360
450
125
358
1,270
Height
mm
Width
mm
Depth
mm
M1
mm
M2
mm
—
Extension boxes
—
01
EPP-EB20
200
450
125
358
110
EPP-EB40
400
450
125
358
310
EPP-RW1016
200
450
125
358
110
EPP-RW2032
400
450
125
358
310
EPP-CON
500
450
125
358
410
—
02
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
48
—
Protecta Plus
Dimensions
—
01 Horizontal
split-load boards
—
01 / 02 Horizontal split-load boards
—
02 Connection
philosophy
—
03 Type A
distribution board
Height
mm
125/160A
Height
mm
250A
Width
mm
Depth
mm
EPP-HSL 2x4way
990
1,190
900
125
EPP-HSL 2x8way
1,130
1,330
900
125
EPP-HSL 2x12way
1,270
1,470
900
125
EPP-HSL 2x16way
1,450
1,650
900
125
EPP-HSL 2x20way
1,620
1,820
900
125
EPP-HSL 2x24way
1,760
1,960
900
125
EPP-HSL kits are aligned from the base of the DB. SLP-HSL assemblies are aligned from the top od the DB. SLP-HSL are complete
assemblies designed for projects.
EPP-HSL
SLP-HSL
SLP-HSL
Consumer Units
125A
Dimensional
details160A
(continued)
250A
125A
160A
250A
Isolator
Direct Connection kit
Comby steel flap consumer unit flush mounted
—
01
Meter & C.T
—
02
Type Code
250
Number
of modules
ECS 107 DF
ECS 110 DF
ECS 116 DF
ECS 120 DF
C
—
03 Housemaster compact sheet steal consumer unit (surface mounted)
276
110
A
mm
B
mm
256
C
mm
142
HSMS 04C
4way
152
155
77
HSMS 07C
7way
207
210
133
HSMS 11C
11way
257
263
187
HSMS 16C
16way
265
368
292
HSMS 20C
20way
437
440
360
Housemaster compact sheet steal consumer unit surface mounted
11
0
Type Code
C
256
110
88
256
—
03
Housemaster compact plastic consumer unit surface mounted
142
HSMS 04C
HSRC 04C
HSMS 07C
HSRC 07C
HSMS 11C
HSRC 11C
HSSL 4+4C
HSMS 16C
HSRC 16C
HSSL 6+6C
HSMS 20C
HSRC 20C
HSSL 8+8C
P R OT E C TA P LU S – D I M E N S I O N S
49
—
Protecta Plus
Dimensions
—
01 Vertical
split-load board
—
Vertical split-load boards
—
02 Metering layout
Height
mm
Width
mm
Depth
mm
M1
mm
M2
mm
EPP-VSL 8+4
1,090
450
125
358
1,000
EPP-VSL 8+8
1,270
450
125
358
1,180
EPP-VSL 12+8
1,440
450
125
358
1,350
125/160/250A
EPP-VSL 12+12*
1,580
450
125
358
1,490
EPP-VSL 16+8*
1,580
450
125
358
1,490
EPP-VSL 8+4+4*
1,380
450
125
358
1,290
EPP-VSL 12+4+4*
1,690
450
125
358
1,600
* Please ensure RCBO lead lengths are considered.
125A
160A
250A
—
01
—
02
Isolator
Meter & C.T
50
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
—
MCBs technical details
Definitions according to standards for
miniature circuit breakers
Rated insulation voltage (Ui) according
IEC/EN 60664-1:
Root mean square (R.M.S.) withstand voltage
value assigned by the manufacturer to the
equipment or to a part of it, characterizing the
specified (long-term) withstand capability of its
insulation.
—
The rated insulation voltage is not
necessarily equal to the rated
voltage of the equipment which is
primarily related to functional
performance.
IEC/EN 60898-1
Miniature Circuit Breakers according IEC/EN
60898-1 are intended for the protection against
over-currents of wiring installations in buildings
and similar applications; they are designed for
use by uninstructed people and for not
being maintained.
This part of IEC/EN 60898 applies for a.c. airbreak circuit-breakers for operation at 50 Hz or
60 Hz, having a rated voltage not exceeding 440 V
(between phases), a rated current not exceeding
125 A and a rated short-circuit capacity not
exceeding 25,000 A. As far as possible, it is in line
with the requirements contained in
IEC/EN 60947-2.
Rated short-circuit capacity (Icn)
The rated short-circuit capacity of a circuitbreaker is the value of the ultimate short-circuit
breaking capacity assigned to that circuitbreaker by the manufacturer.
The sequence of operations shall be: O – t – CO
Service short-circuit capacity (Ics)
A circuit-breaker having a given rated shortcircuit capacity has a corresponding fixed service
short-circuit capacity (Ics).
This is therefore generally not indicated.
Rated operational voltage (Un)
The rated voltage of a circuit-breaker is the value
of voltage, assigned by the manufacturer, to
which its performance (particularly the shortcircuit performance) is referred.
The same circuit-breaker may be assigned a
number of rated voltages and associated rated
short-circuit capacities.
The voltage which appears across the terminals
of a pole of a circuit-breaker after the breaking
of the current.
The value of the power frequency recovery
voltage shall be equal to 110% of the rated
voltage of the circuit-breaker under test.
IEC/EN 60947-2
This part of the IEC/EN 60947 applies to circuitbreakers, the main contacts of which are intended
to be connected to circuits, the rated voltage of
which does not exceed 1,000 V AC or 1,500 V DC
It applies whatever the rated currents, the
method of construction or the proposed
applications of the circuit-breakers may be.
The circuit-breakers are designed for use by
instructed people.
Rated ultimate short-circuit breaking capacity Icu
The rated ultimate short-circuit breaking capacity
of a circuit-breaker is the value of ultimate shortcircuit breaking capacity assigned to that circuitbreaker by the manufacturer for the
corresponding rated operational voltage.
It is expressed as the value of the prospective
breaking current, in kA (r.m.s. value of the AC
component in the case of AC).
The sequence of operations shall be: O – t – CO
Rated service short-circuit breaking capacity Ics
The rated service short-circuit breaking capacity
of a circuitbreaker is the value of service shortcircuit breaking capacity assigned to that circuitbreaker by the manufacturer for the
corresponding rated operational voltage. It is
expressed as a value of prospective breaking
current, in kA, corresponding to one of the
specified percentages of the rated ultimate
ART I CL E OR CH AP T ER T I TL E
—
01 The rated insulation
voltage is not
necessarily equal to
the rated voltage of
the equipment which
is primarily related to
functional performance
shortcircuit breaking capacity and rounded up to
the nearest whole number. It may be expressed as
a percentage of Icu (for example Ics = 25% Icu).
The sequence of operations shall be:
O – t – CO – t – CO
The following symbols are used for defining the
sequence of operatons:
O
represents an opening operation.
CO
represents a closing operation followed
by an automatic opening.
t
represents the time interval between
two short-circuit operations.
51
Rated operational voltage (Ue)
The rated operational voltage of an equipment is
a value of voltage which, combined with a rated
operational current, determines the application
of the equipment and to which the relevant tests
and the utilization categories are referred.
For single-pole equipment it is generally stated
as the voltage across the pole. For multi pole
equipment it is generally stated as the voltage
between phases.
Equipment may be assigned a number of
combinations of rated operational voltage and
associated making and breaking capacities for
different duties and utilization categories.
52
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
—
MCBs technical details
Definitions according to standards for miniature circuit breakers
—
Characteristic C IEC-EN60898
Multiples of rated current
Tripping curve
from cold state
Tripping curve
from cold state
Tripping curve
from cold state
Minutes Minutes
Tripping curve
from cold state
Multiples of rated current
2CSC400400F0202
2CSC400400F0202
Multiples of rated current
Multiples of rated current
Multiples of rated current
2CSC400400F0202
2CSC400400F0202
Seconds Seconds
Minutes Minutes
—
Characteristic Z IEC-EN60947-2
Seconds Seconds
Seconds Seconds
2CSC400401F0202
2CSC400401F0202
Multiples of rated current
—
Characteristic K IEC-EN60947-2
—
Characteristic D IEC-EN60898
2CSC400400F0202
2CSC400400F0202
2CSC400400F0202
2CSC400400F0202
—
Characteristic B IEC-EN60898
53
—
ABB
ABB continually develops smart
solutions for controlling and
monitoring the flow of electricity,
as well as improving energy
efficiency in buildings and critical
power applications.
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
54
—
MCB
S 200 Series technical features
—
Technical features
General data
Specifications
Standards
Poles
UL 1077, CSA 22.2
No. 235
UL 1077, CSA 22.2 No. 235
–
1P, 2P, 3P, 4P, 1P+N, 3P+N
Tripping characteristics
–
B, C, D, K, Z
A
0.5...63A
–
Hz
50/60Hz
50/60Hz
Rated insulation voltage Ui acc.
to IEC/EN 60664-1
–
440V AC (phase to phase)
250 V AC (phase to ground),
500 V AC (phase to phase)
Overvoltage category
–
III
–
Pollution degree
–
3
2
Rated operational voltage Un
V
1P: 230/400V AC; 1P+N:
230V AC ;
2... 4P: 400V AC; 3P+N: 400V
1P: 230V AC, 220V DC
2P: 400V AC, 440V DC
3...4P: 400V AC*
Max. power frequency recovery voltage (Umax)
V 1P: 253V AC; 1P+N: 253V AC;
2P: 440V AC; 3...4P: 440V
AC; 3P+N: 440V AC
1P: 230V AC, 220V DC
2P: 400V AC, 440V DC
3...4P: 400V AC*
Min. operating voltage
Rated short-circuit capacity Icn
B, C, D, K, Z
V
12V AC - 12V DC
–
kA
10kA
≤ 25A: 25kA
> 25A: 15kA
3
–
3
Rated impulse withstand voltage Uimp. (1.2/50μs)
kV
–
–
Dielectric test voltage
kV
2kV (50/60Hz, 1 min.)
2kV (50/60Hz, 1 min.)
oC
B, C, D: 30°C
30°C
ops.
In < 32A: 20,000 ops (AC),
In ≥ 32A: 10,000 ops. (AC);
1,000 ops. (DC);
–
Energy limiting class (B, C up to 40 A)
Reference temperature for tripping characteristics
Electrical endurance
Data acc. to
IEC/EN 60947-2
S 200P
IEC/EN 60898-1,
IEC/EN 60947-2
Rated current In
Rated current f
Data acc. to
IEC/EN 60898-1
(except S200M UC
data acc. to
IEC/EN60898-2)
S 200 M
IEC/EN 60898-1,
IEC/EN 60947-2
Rated operational voltage Ue
V
1P: 230V AC;
1P+N: 230V AC;
2...4P: 400V AC;
3P+N: 400V AC
Max. power frequency recovery voltage (Umax)
V
1P: 253V AC;
1P+N: 253V AC;
2P...4P: 440V AC;
3P+N: 440V AC;
1P: 72V DC;
2P: 125V DC
V
12V AC - 12V DC
12 V AC - 12V DC
Rated ultimate short-circuit breaking capacity Icu
Min. operating voltage
kA
15kA
≤ 25A: 25kA
≥ 32A: 15kA
Rated service short-circuit breaking capacity Ics
kA
≤ 40A: 11.2kA
50, 63A: 7.5kA
≤ 25A: 12.5kA
≤ 32…40A: 11.2kA
50, 63A: 7.5kA
Rated impulse withstand voltage Uimp. (1.2/50μs)
kV
4kV (test voltage 6.2kV at
sea level, 5kV at 2,000m)
–
Dielectric test voltage
kV
2kV (50/60Hz, 1 min.)
–
B, C, D: 55°C; K, Z: 20°C
B, C: 55°C; K, Z: 20°C
Reference temperature for tripping characteristics
Electrical endurance
Note: * Only acc. to IEC/EN 60898-1 r switching
°C
ops.
In < 32A: 20,000 ops (AC), In < 32A: 20,000 ops (AC), In ≥
In ≥ 32A: 10,000 ops. (AC); 32A: 10,000 ops. (AC); 1,000
1,000 ops. (DC);
ops. (DC);
(1 cycle 2s - ON, 13s - OFF, In ≤
(1 cycle 2s - ON,
32A),
13s - OFF, In ≤ 32A),
(1 cyle 2s - ON, 28s - OFF, In >
(1 cyle 2s - ON,
32A)
28s - OFF, In ≥ 32A)
M C B - T E C H N I C A L F E AT U R E S
55
—
MCB
S 200 80A-100A series technical features
—
Technical features
General Data
S 200 80A-100A
Standards
IEC/EN 60898-1, IEC/EN 60947-2
Poles
1P, 2P, 3P, 4P, 1P+N, 3P+N
Tripping characteristics
B, C
Rated current I n
80 A, 100 A
Rated frequency f
50/60 Hz
Rated insulation voltage Ui acc. to IEC/EN 60664-1 (VDE 0110-1) 440 V AC
Overvoltage category
III
Pollution degree
2
IEC/EN 60898-1 (VDE 0641-11)
Rated operational voltage U n
1P: 230/400 V AC; 1P+N: 230 V AC; 2P, 3P, 4P, 3P+N: 400 V AC
Max. power frequency recovery voltage U max
1P: 253/440 V AC; 1P+N: 253 V AC; 2P, 3P, 4P, 3P+N: 440 V AC
Min. operating voltage
12 V AC
Rated short-circuit capacity I cn
6 kA
Rated impulse withstand voltage Uimp (1.2/50µs)
4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m)
Dielectrical test voltage
2 kV (50/60 Hz, 1 min.)
Reference temperature for tripping characteristics
B, C: 30 °C
Electrical endurance
10,000 ops. (AC); one cycle 2 s - ON, 28 s - OFF
IEC/EN 60947-2 (VDE 0660-101)
Rated operational voltage U e
1P, 1P+N: 230 V AC; 2P, 3P, 4P, 3P+N: 400 V AC
Max. power frequency recovery voltage U max
1P, 1P+N: 253 V AC; 2P, 3P, 4P, 3P+N: 440 V AC
Min. operating voltage
12 V AC
Rated ultimate short-circuit breaking capacity I cu
6 kA
Rated service short-circuit breaking capacity I cs
6 kA
Rated impulse withstand voltage Uimp (1.2/50 µs)
4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m)
Dielectrical test voltage
2 kV (50/60 Hz, 1 min.)
Reference temperature for tripping characteristics
B, C: 55 °C
Electrical endurance
10,000 ops. (AC); one cycle 2 s - ON, 28 s - OFF
Mechanical data
Housing
Insulation group I, RAL 7035
Toggle
Insulation group II, black, sealable
Contact position indication
Real CPI (red ON/green OFF)
Protection degree acc. to DIN EN 60529
IP20 (1), IP40 in enclosure with cover
Mechanical endurance
20,000 ops.
Shock resistance acc. to DIN EN 60068-2-27
25 g, 2 shocks, 13 ms
Vibration resistance acc. to DIN EN 60068-2-6
5 g, 20 cycles at 5…150…5 Hz at 0.8 I n
Environmental conditions (Damp heat cyclic) acc. to DIN EN
28 cycles with 55 °C/90-96 % and 25 °C/95-100 %
60068-2-30
Ambient temperature
-25 ... +55 °C
Storage temperature
-40 ... +70 °C
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
56
—
MCB
S200 80A-100A series technical features and tripping characteristics
—
Installation features
Installation
S 200 80A-100A
Terminal
Failsafe bi-directional cache clamp
Cross-section of conductors (top/bottom)
solid, stranded: 50 mm 2 / 50 mm 2
flexible: 50 mm 2 / 50 mm 2
Cross-section of busbars (top/bottom)
16 mm 2 / 16 mm 2
Torque
3.0 Nm
Screwdriver
Nr. 2 Pozidriv
Mounting
On DIN rail 35 mm acc. to EN 60715 by fast clip
Mounting position
any
Supply
any
Dimensions and weight
Mounting dimensions acc. to DIN 43880
Mounting dimension 1
Pole dimensions (H x T x B) mm
88.8 x 69 x 17.5
Pole weight
approx. 126 g
Combination with auxiliary elements
Auxiliary contact
Yes
Signal/auxiliary contact
Yes
Shunt trip
Yes
Unervoltage release
Yes
Motor Operating Device
Yes
—
Tripping characteristics
Thermal release (¹)
Tripping
characteristics
Rated
current In
Currents:
conventional
non-tripping
current
I1
DIN EN 60898-1
B
80 up to
100 A
1.13 · In
1.45 · In
>2h
2h
63A) ( 2 )
Terminal size top/bottom for cable
Terminal size top/bottom for busbar
°C/RH
mm2 25/25 (35/35 single slot terminal for In > 63A)
UL/CSA
AWG
18-4 (up to 63A)
IEC
mm2
10/10 (not for In = 80-100A)
UL/CSA
AWG
18-8 (up to 63A)
Nm
2.8 (3 for In = 125A)
Tightening torque
in-lbs.
25 (up to 63A)
Tool
UL/CSA
–
Nr. 2 Pozidriv
Mounting
On DIN rail EN 60715 (35mm) by means
–
of fast clip device
Connection
–
Withdrawal from busbar
It is possible without using any tools only
–
from the bottom (not for 125A)
Dimensions
and weight
Dimensions (H x D x W)
Combination
with auxiliary
elements
Combinable with:
mm
Weight
g
Auxiliary contact
Signal contact/auxiliary switch
From top and bottom
85 x 69 x 35
200
Yes (no for 125A)
Yes
Shunt trip
Yes (no for 125A)
undervoltage release
Yes (no for 125A)
60
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
—
EQ Meter - A series
Technical features
—
Technical features
A41
Voltage/current inputs
Nominal voltage
Voltage range
Power dissipation voltage circuits
Power dissipation current circuits
Base current Ib
Rated current In
Reference current Iref
Transitional current Itr
Maximum current Imax
Minimum current Imin
Starting current Ist
Terminal wire area
Recommended tightening torque
Communication
Terminal wire area
Recommended tightening torque
Transformer ratios
Configurable voltage ratio (VT)
Configurable current ratio (CT)
Pulse indicator (LED)
Pulse frequency
Pulse length
General data
Frequency
Accuracy Class
Active energy
Display of energy
Environmental
Operating temperature
Storage temperature
Humidity
Resistance to fire and heat
Resistance to water and dust
Mechanical environment
Electromagnetic environment
Outputs
Current
Voltage
Pulse output frequency
Pulse length
Terminal wire area
Recommended tightening torque
Inputs
Voltage
OFF
ON
Min. pulse length
Terminal wire area
Recommended tightening torque
EMC compatibility
Impulse voltage test
Surge voltage test
Fast transient burst test
Immunity to electromagnetic HF-fields
Immunity to conducted disturbance
Immunity to disturbance with
harmonics
Radio frequency emission
Electrostatic discharge
Standards
Mechanical
Material
Dimensions
Width
Height
Depth
DIN modules
*) Only A44 552 - 110 and A44 553 - 110
230 V AC
57.7 - 288 V AC (-20% - +15%)
0.8 VA (0.8 W) total
0.007 VA (0.007 W) at 230 V AC and Ib
5A
5A
0.5 A
80 A
0.25 A
< 20 mA
1 - 25 mm2
3 Nm
A43
3x230/400 V AC
3x57.7/100 ... 288/500 V AC (-20% - +15%)
0.007 VA (0.007 W) per phase at 230 V AC and Ib
5A
5A
0.5 A
80 A
0.25 A
< 20 mA
1 - 25 mm2
3 Nm
0.5 - 1 mm2
0.25 Nm
0.5 - 1 mm2
-
-
1000 imp/kWh
40 ms
1000 imp/kWh
40 ms
50 or 60 Hz ± 5%
B (Cl.1) or Reactive Cl. 2
1%
Pixel oriented
A (Cl.2), B (Cl.1) or Reactive Cl. 2
1%, 2%
-40°C - +70°C
-40°C - +85°C
75% yearly average, 95% on 30 days/year
Terminal 960°C, cover 650°C (IEC 60695-2-1)
IP20 on terminal block without protective enclosure and IP51 in protective enclosure, according to IEC
60529.
Class M2 in accordance with the Measuring Instrument Directive (MID). (2004/22/EC).
Class E2 in accordance with the Measuring Instrument Directive (MID), (2004/22/EC).
2 - 100 mA
5 - 240 V AC/DC. For meters with only 1 output, 5 - 40 V DC.
Programmable: 1 - 999999 imp/kWh
Programmable: 10 - 990 ms
0.5 - 1 mm2
0.25 Nm
0 - 240 V AC/DC
0 - 12 V AC/DC
57-240 V AC/24 - 240 V DC
30 ms
0.5 - 1 mm2
0.25 Nm
6 kV 1.2/50 µs (IEC 60060-1)
4 kV 1.2/50 µs (IEC 61000-4-5)
4 kV (IEC 61000-4-4)
80 MHz - 2 GHz at 10 V/m (IEC 61000-4-3)
150 kHz - 80 MHz, (IEC 61000-4-6)
2kHz - 150kHz
EN 55022, class B (CISPR22)
15 kV (IEC 61000-4-2)
IEC 62052-11, IEC 62053-21 class 1 & 2, IEC 62053-22 class 0,5 S, IEC 62053-23 class 2, IEC 62054-21, GB/T
17215.211-2006,
GB/T 17215.321-2008 class 1 & 2, GB/T 17215.322-2008 class 0,5 S, GB 4208-2008, EN
50470-1, EN 50470-3 category A, B & C
Polycarbonate in transparent front glass, bottom case, upper case and terminal cover, Glass reinforced polycarbonate in
terminal block.
70 mm
97 mm
65 mm
4
123 mm
97 mm
65 mm
7
E Q M E T E R - A / B S E R I E S - T E C H N I C A L F E AT U R E S
61
—
EQ Meter - B series
Technical features
—
Technical features
B21
Voltage/current inputs
Nominal voltage
Voltage range
Power dissipation voltage circuits
Power dissipation current circuits
Base current Ib
Rated current In
Reference current Iref
Transitional current Itr
Maximum current Imax
Minimum current Imin
Starting current Ist
Terminal wire area
Recommended tightening torque
Communication
Terminal wire area
Recommended tightening torque
Transformer ratios
Configurable current ratio (CT)
Pulse indicator (LED)
Pulse frequency
Pulse length
General data
Frequency
Accuracy Class
Active energy
Display of energy
Environmental
Operating temperature
Storage temperature
Humidity
Resistance to fire and heat
Resistance to water and dust
Mechanical environment
Electromagnetic environment
Outputs
Current
Voltage
Pulse output frequency
Pulse length
Terminal wire area
Recommended tightening torque
Inputs
Voltage
OFF
ON
Min. pulse length
Terminal wire area
Recommended tightening torque
EMC compatibility
Impulse voltage test
Surge voltage test
Fast transient burst test
Immunity to electromagnetic
HF-fields
Immunity to conducted disturbance
Immunity to disturbance with harmonics
Radio frequency emission
Electrostatic discharge
Standards
Mechanical
Material
Dimensions
Width
Height
Depth
DIN modules
230 V AC
220-240 V AC (-20% - +15%)
0.9 VA (0,4 W) total
0.014 VA (0.014 W) at 230 V AC and I b
5A
5A
0.5 A
65 A
0.25 A
< 20 mA
1 - 25 mm2
3 Nm
B23
B24
3 x 230/400 V AC
3 x 220-240 V AC (-20% - +15%)
1.6 VA (0.7 W) total
0.007 VA (0.007 W) per phase at 230 V AC and Ib
1A
0.05 A
6A
0.02 A
< 1 mA
0.5 - 10 mm2
1.5 Nm
0.5 - 1 mm2
0.25 Nm
1000 imp/kWh
40 ms
1/9 - 9999/1
1000 imp/kWh
40 ms
50 or 60 Hz ± 5%
B (Cl. 1) and Reactive Cl. 2
1%
6 digit LCD
B (Cl. 1) and Reactive Cl. 2
1%
7 digit LCD
5000 imp/kWh
40 ms
B (Cl. 1) or C (Cl. 0,5 S) and Reactive
Cl. 2
0.5%, 1%
-40°C - +70°C
-40°C - +85°C
75% yearly average, 95% on 30 days/year
Terminal 960 °C, cover 650°C (IEC 60695-2-1)
IP20 on terminal block without protective enclosure and IP51 in protective enclosure, according to IEC 60529.
Class M2 in accordance with the Measuring Instrument Directive (MID), (2004/22/EC).
Class E2 in accordance with the Measuring Instrument Directive (MID), (2004/22/EC).
2 - 100 mA
5 - 240 V AC/DC. For meters with only 1 output 5 - 40 V DC.
Programmable: 1 - 999999 imp/kWh
Programmable: 10 - 990 ms
0.5 - 1 mm 2
0.25 Nm
0 - 240 V AC/DC
0 - 12 V AC/DC
57 - 240 V AC/24 - 240 V DC
30 ms
0.5 - 1 mm2
0.25 Nm
6 kV 1.2/50μs (IEC 60060-1)
4 kV 1.2/50μs (IEC 61000-4-5)
4kV (IEC 61000-4-4)
80 MHz - 2 GHz (IEC 61000-4-6)
150kHz - 80MHz (IEC 61000-4-6)
2kHz - 150kHz
EN 55022, class B (CISPR22)
15 kV (IEC 61000-4-2)
IEC 62052-11, IEC 62053-21 class 1 & 2, IEC 62053-22 class 0,5 S, IEC 62053-23 class 2, IEC 62054-21, GB/T 17215.211-2006, GB/T
17215.312-2008 class 1 & 2, GB/T 17215.322-2008 class 0,5 S, GB 4208-2008, EN 50470-1, EN 50470-3 category A, B & C
Polycarbonate in transparent front glass. Glass reinforced polycarbonate in bottom case and upper case. Polycarbonate in
terminal cover.
35 mm
97 mm
65 mm
2
70 mm
97 mm
65 mm
4
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
62
—
EQ Meter - A series
Wiring diagram
—
Terminal block A41 (A)
—
01 Terminal block A41
—
02 Terminal block A43
1
—
03 Terminal block A44
3 4
6
L
N
—
Terminal block A43 (A)
4 wire connection, 3 elements
3 wire connection, 2 elements
1
3 4
6 7
9 10
3 4
6 7
9 10
L1
L2
L3
N
L1
L2
L3
(C)
1
12
(C)
(B)
(B)
(C)
(B)
SET
OK
(A)
—
01
(A)
—
02
(A)
—
03
12
EQ METER - A /B SERIES - WIRING DIAGR AM
63
—
EQ Meter - B series
Wiring diagram
—
01 Terminal block B21
—
Terminal block B21
—
02 Terminal block B23
—
03 Terminal block B24
3
1
5
L
N
—
Terminal block B23
3 wire connection, 2 elements
3 4
1
4 wire connection, 3 elements
6 7
9
1
11
3 4
6 7
9
11
L1
L2
L3
N
L1
L2
L3
—
Terminal block B24
4 wire connection, 3 elements
3 wire connection, 2 elements
1 2 3
L1
L2
L3
5
7 8 9
11
P1
P1
S1
S2
P1
P2
1 2 3 4 5 6 7 8 9
L1
L2
L3
N
P1
P1
P1
11
1
Phase in
1 4 7 Phase in
1 4 7 Current in
3
Phase out
3 6 9 Phase out
2 5 8 Voltage
5
Neutral
11
3 6 9 Current out
Neutral
11
Neutral
11 1 2 4 5 7 8
5
11
1
1
4
7
(A & B )
(A & B )
—
01
3
(A & B )
3
—
02
6
9
—
03
3
6
9
S1
S2
P1
P2
64
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
—
EQ Meter - A/B series
Inputs/ouputs and communication
—
Inputs / outputs (B)
2 outputs, 2 inputs
C
13
4 Configurable inputs/outputs
Out1
Out2
Inp3
Inp4
C
I/O 1
I/O 2
I/O 3
I/O 4
15
16
17
18
13
15
16
17
18
External power supply needed 5-240 VAC/VDC...
1 output
C
Out1
13
15
NC
NC
NC
External power supply needed 5-40VDC...
—
Communication (C)
RS-485
M-Bus
A
B
C
37
36
35
37
36
ARTICLE OR CHAPTER TITLE
65
—
ABB
With a broad range of marketleading products and solutions, a
global sales network and
customised support, ABB provides
flexibility that improves energy
performance, whatever the
requirements.
66
P R O T E C TA P L U S M C B D I S T R I B U T I O N B O A R D 2 5 0 A
—
Circuit Monitoring System - CMS
Technical features
—
Control unit CMS 600
Control Unit CMS-600 – «Modbus RTU»Unit 600
Supply voltage
Power input
[V DC]
24 (± 10 %)
[W]
4 – 24 (dep. on number of sensors)
Interface
RS485 2-wire
Protocol
Data rate
Modbus RTU
[Baud]
Refresh time
Insulation strength
≤1 sec with max. 64 sensors
[V AC]
400
0.5 ... 2.5 mm2, max. 0.6 Nm
Screw-type terminals
Mounting method
Dimensions
2400 ... 115200
35 mm DIN rail (DIN 50022) or SMISSLINE TP plug base
[mm]
71.8 x 87.0 x 64.9 (4 WM)
Operating temperature
[°C]
− 25 ... +70
Bearing temperature
[°C]
− 40 ... +85
Standards
IEC 61010-1 UL 508/ CSA C22.2 No. 14
—
Control unit CMS 700
Control Unit CMS-700
Supply voltage
[V AC]
80 – 277 (L1-N, +5%)
Frequency
[Hz]
50 / 60
Power input (L1-N)
[W]
5 ... 40 (dep. on number of sensors)
Power input, current transformer,
secondary side
Voltage measurement range
Measurement range, current transformer,
Harmonic component
Data rate of Modbus RTU
[VA]
Current circuit