Technical Data Sheet
201712
Page 1
Non-Metallic Systems
PAS Standard Weight Conduit
Technical Characteristics
Conforms to
BSI Kitemark KM-35161
CE Mark to the Low voltage directive 2014/35/EU
Deutsche Bahn S4, SR2, ST2
NFR 16-10 1 I3,F3
UL Recognised to UL1696 File number E173968
Approvals and Standards
Degree of mechanical protection
High flexibility & fatigue life
Degree of protection
IP40 - Adaptaring & Jumbo
IP65 - Jumbo + SK Seal
IP66 - Adaptalok, ATS or Adaptaseal
IP67 - Adaptalok + ALS Seal or ATS, Adaptaseal
IP68 - Adaptalok + ALS Seal or ATS, Adaptaseal
IP69k - Adaptalok + ALS Seal or ATS
UV protection
Very High
Finish
Black (BL), Grey (GR)
Application
Indoors / Outdoors - light industrial, buildings & machinery
Normal operating temperature range
Application Min Temp
For use with - Fitting range
Fire performance
Max Temp
Static
- 40°C
+120°C
Dynamic
- 5°C
+120 °C
Adaptalok & ATS, Adaptaseal, Adaptaring and Jumbo fittings
Test Standard
Performance Rating
BS EN 61386
Pass
NFF16-101
I3 F3
DIN5510-2
S4 SR2 ST2
UL94
V2
Testing data
Click or See pages 3 & 4
Type of material
Polyamide (Nylon) 6 - flame retardant - heat stabilised
Self Extinguishing
& Halogen Free
Image
Cable Management Products Ltd.
CMG House - Station Road - Coleshill - B46 1HT - United Kingdom
Tel: +44(0)1675 468 222 - Fax: +44(0)1675 464 930
Technical Support e-mail: cmg.conduitsystems@tnb.com - www.adaptaflex.com
The Company’s policy is one of continuous improvement and reserves the right to change specifications at any time without prior notice.
Technical Data Sheet
201712
Page 2
Non-Metallic Systems
PAS Standard Weight Conduit
Technical & Dimensional Data
Conduit Size
Dimensions
NW
Conduit
Conduit Size Pitch
(A) Outside (B) Inside
Diameter
Diameter
Average
(C) Min. Bend Reel
Weight
Radius
Length (m) (Kg/100m)
**PAFS10 10mm
7.5
Fine
10.0mm
6.5mm
15mm
50
1.9
**PAFS13 13mm
10
Fine
13.0mm
9.6mm
25mm
50
2.8
PAFS16
16mm
13
Fine
15.8mm
11.8mm
35mm
50
3.9
PAFS18
18mm
15
Fine
18.4mm
14.0mm
40mm
50
4.9
PAFS21
21mm
17
Fine
21.2mm
16.5mm
45mm
50
6.1
PACS25
25mm
22
Coarse
25.0mm
19.8mm
50mm
50
8.0
PAFS28
28mm
23
Fine
28.5mm
22.6mm
50mm
50
10.2
PACS28
28mm
23
Coarse
28.5mm
21.7mm
50mm
50
10.0
PAFS34
34mm
29
Fine
34.5mm
28.8mm
60mm
50
13.5
PACS34
34mm
29
Coarse
34.5mm
27.7mm
60mm
50
13.5
PACS42
42mm
36
Coarse
42.5mm
35.2mm
65mm
25
16.8
PACS48
48mm
42
Coarse
48.2mm
40.9mm
70mm
25
18.8
PACS54
54mm
48
Coarse
54.5mm
46.5mm
75mm
25
24.1
PACS80
80mm
70
Coarse
79.3mm
67.0mm
160mm
10
48.0
95
Coarse
106mm
91.5mm
210mm
10
85.0
Part No.
Nominal
Conduit Size
PACS106 106mm
To order quote part number, colour & reel length, e.g PAFS21/BL/50M
**UR mark not applicable to sizes 10 and 13.
Cable Management Products Ltd.
CMG House - Station Road - Coleshill - B46 1HT - United Kingdom
Tel: +44(0)1675 468 222 - Fax: +44(0)1675 464 930
Technical Support e-mail: cmg.conduitsystems@tnb.com - www.adaptaflex.com
The Company’s policy is one of continuous improvement and reserves the right to change specifications at any time without prior notice.
Technical Data Sheet
201712
Page 3
Non-Metallic Systems
PAS Standard Weight Conduit
BS EN 61386 Classification
PA S
Fitting
Compression
Impact
Min
temp
Max
temp
bending
electrical
IP
solids
IP
water
ATS
2
4
2
4
4
0
6
7
Corrosion Tensile
-
1
Non-flame
Propogating
Suspended
load
1
0
Mechanical Properties
Test Type
Methods / Standards Requirements
Value
Crush Strength
BS EN 61386
90% recovery
>320N
Impact Strength @ 23 °C
BS EN 61386-1
No Cracks 20J
Impact Strength @-5 °C
BS EN 61386-1
No Cracks. 6.0J
Tensile Strength
BS EN 61386-1
Pull off of fitting minimum value
>100N
Dynamic Bend radius @-5 °C
BS EN 61386-23
5000 cycles minimum
4xOD
Test Type
Methods / Standards
Requirements
Value
Minimum Temp
Dynamic BS EN 61386 Dynamic 5000 cycles
-5°C
Maximum Short Term Temp
BS EN 61386
Static & Dynamic 3000 hours, 5000 cycles
150°C
Minimum Static Temp
Permanent Use (30,000) Hours
-40°C
Maximum Static Temp
Permanent Use (30,000) Hours
120°C
2xOD
Pass
Thermal Properties
Cold Bend @ - 40°C
NFR13-903
Chemical Resistance Chart
Key:
Suitable :
Limited Suitability :
Unsuitable :
Not Tested :
The information above is given as a guide only and is based on published technical data and experience. The chemical resistance of the above
products is dependant on factors such as chemical exposure, concentration of the chemical and temperature. The above chemicals are valid for a
temperature of 23°C. Use of the above table is at the users own discretion and risk. Those using it must satisfy themselves that their application
presents no health and safety risks. The end user should assess compatibility with their application and contact Thomas & Betts for further information.
ADHERENCE TO THE CURRENT WIRING REGULATIONS BS7671 OR NEC WIRING REGULATIONS (FOR USA) IS STRONGLY
ADVISED.
MINIMUM BEND RADIUS FOR FLEXING IS DEPENDANT UPON MINIMUM TEMPERATURE, BENDING FREQUENCY AND CHEMICAL
ENVIRONMENT.
Cable Management Products Ltd.
CMG House - Station Road - Coleshill - B46 1HT - United Kingdom
Tel: +44(0)1675 468 222 - Fax: +44(0)1675 464 930
Technical Support e-mail: cmg.conduitsystems@tnb.com - www.adaptaflex.com
The Company’s policy is one of continuous improvement and reserves the right to change specifications at any time without prior notice.
Technical Data Sheet
201712
Page 4
Non-Metallic Systems
PAS Standard Weight Conduit
Flammability
Test Type
Method / Standard
Requirement
Result
Unit
Oxygen Index
ISO 4589-2
% Oxygen to support combustion
28.9
%
Glow Wire Rating
IEC 60695
No Ignition to Extinguish with 30s
850
°C
Flammability
UL94
Vertical (V0) or Horizontal (HB)
V2
HB-V0
Flammability
BS EN 61386-1
1Kw Burner @ 45° Vertical burn
Pass
Pass/Fail
NF F16-101
Glow Wire & oxygen index
I3
-
Ignition Rating
Smoke
Test Type
Method / Standard
Fume Rating
Requirement
Result
Unit
NF F16-101
Smoke & Toxicity
F3
-
Smoke Density
BS6853
A