a
Evaluation Board Documentation
AD7751/AD7755 Energy Metering IC
EVAL-AD7751/AD7755EB
FEATURES
Single +5 V Power Supply
Easy Connection of External Transducers via Screw
Terminals
Easy Modification of Signal Conditioning Components
Using PCB Sockets
Trim Pot for Analog Calibration of Meter Constant
LED Indicators on Logic Outputs for Fault (AD7751
Only), REVP and CF
Optically Isolated Output for Calibration/Test Purposes
External Reference Option Available for Reference
Evaluation
GENERAL DESCRIPTION
The AD7751 and AD7755 are high accuracy energy measurement
ICs. The part specifications surpass the accuracy requirements
as quoted in the IEC1036 standard. The AD7751 incorporates
a novel fault detection scheme that both warns of fault conditions with the logic output FAULT but allows the AD7751 to
continue accurate billing during a fault event. The AD7751
does this by continuously monitoring both the phase and neutral
(return) currents. A fault is indicated when these currents differ
by more than 12.5%. Billing is continued using the larger of the
two currents. The FAULT output is connected to an LED on
the evaluation board.
The AD7751 supplies average real power information on the
low frequency outputs F1 and F2. These logic outputs may be
used to directly drive an electromechanical counter or interface
to an MCU. The evaluation board provides screw connectors
for easy connection to an external counter. The CF logic output
gives instantaneous real power information. This output is intended to be used for calibration purposes. The evaluation
board allows this logic output to be connected to an LED or
optoisolator. The REVP logic output goes high when negative
real power is detected. This causes an LED on the evaluation
board to switch on.
The AD7751/AD7755 evaluation board can easily be converted
into an energy meter by the addition of a local power supply and
the connection of the appropriate transducers. A large amount
of prototype area is made available on the evaluation board for
this purpose.
FUNCTIONAL BLOCK DIAGRAM
DGND DVDD
AGND AVDD
V1A/NC*
V1N
V1B/V1P
VCC
V1A (AD7751)
NC* (AD7755)
F1
V1N (AD7751)
V1N (AD7755)
V1B (AD7751)
V1P (AD7755)
AD7751/
AD7755
74HC08
CF
F2
FAULT
REVP
V2N
V2P
VPLUS
H11L1
GND
AD780
*NC = NO CONNECT
CFOUT
PROTOTYPE
AREA
REV. 0
Information furnished by Analog Devices is believed to be accurate and
reliable. However, no responsibility is assumed by Analog Devices for its
use, nor for any infringements of patents or other rights of third parties
which may result from its use. No license is granted by implication or
otherwise under any patent or patent rights of Analog Devices.
One Technology Way, P.O. Box 9106, Norwood, MA 02062-9106, U.S.A.
Tel: 781/329-4700
World Wide Web Site: http://www.analog.com
Fax: 781/326-8703
© Analog Devices, Inc., 1999
EVAL-AD7751/AD7755EB
If Channel 2 is being used in a single-ended mode of operation,
the unused input of the pair should be connected to analog
ground (AGND) via an antialias filter. This is shown in Figure 2
where V2N is connected to AGND using jumper JP10.
ANALOG INPUTS (SK1 AND SK2)
Voltage and current signals are connected at the screw terminals
SK1 and SK2 respectively. All analog input signals are filtered
using the on-board antialias filters before being presented to the
analog inputs of the AD7751 or AD7755. Some analog inputs
offer additional signal conditioning, e.g., attenuation on the
voltage channel. The default component values shipped with
the evaluation board are the recommended values to be used
with the AD7751 and AD7755. The user can easily change
these components, however this is not recommended unless the
user is familiar with sigma-delta converters and also the criteria
used for selecting the analog input filters—see AD7751 and
AD7755 data sheets.
JP9
TP5
R57
V2N
JP10
C54
Figure 2. Unused Analog Inputs Connected to AGND
All passive components (resistors and capacitors) which make
up the attenuation network and antialias filters may be modified
by the user. The components at mounted using PCB jack sockets
which allow for easy removal and replacement of components.
Voltage Input
SK1 is a two-way connection block that can be directly connected to a high voltage source, e.g., 220 V rms. The resistor
network R53, R54, R55, R56 and R31 make up a very flexible
attenuation and calibration network—see schematic. The attenuation network is designed such that the corner frequency (–3 dB
frequency) of the network matches that of the RC (antialiasing)
filters on the other analog inputs. This is important, because if
they do not match there will be large errors at low power factors. Figure 1 shows how the attenuation network may be used
with fixed resistors or the trim pot. The trim pot allows the
voltage signal on V2P to be scaled to calibrate the frequency on
CF to some given constant, e.g., 3200 imp/kWhr. Some examples are given later.
Current Input
SK2 is a three-way connection block which allows the AD7751/
AD7755 to be connected to a current transducer. The AD7751
has three inputs which are used with two current transducers,
e.g., two CTs (current transformers). The AD7755 has one
differential input channel for connection to the current transducer, i.e., two inputs. When using the AD7755 in the evaluation board the input SK2A is not used. PCB jack sockets allow
CT burden resistors to be placed on the evaluation board at
positions SH1 and SH2. Figures 3 and 4 show some typical
connection diagrams for CT and shunt connection.
JP7
JP1
R53
R55
JP52
R50
SK2A
SK1A
TP1
V1A
CT
R54
JP2
A
V2P
R31
SH1
B
JP8
R56
JP4
SH2
CT
TP2
V1N
C51
JP5
R52
SK2C
AD7751
JP3
R51
SK2B
JP51
C53
C50
TP3
V1B
a. Attenuation Using Trim Pot (R31)
C52
BURDEN RESISTORS
JP7
R53
Figure 3. Typical Connection for Channel 1 of the AD7751
JP52
SK1A
R54
R55
A
R31
JP1
V2P
B
JP8
R50
JP51
C53
JP2
R56
SH1
JP4
b. Attenuation Using Fixed Resistors
Figure 1. Attenuation Network on Channel 2
SH2
SHUNT
AD7755
TP2
V1N
C51
JP5
R52
SK2C
NC
C50
JP3
R51
SK2B
TP1
TP3
V1P
C52
TP11
AGND
NC = NO CONNECT
Figure 4. Typical Connection for Channel 1 of the AD7755
–2–
REV. 0
EVAL-AD7751/AD7755EB
AD7751/AD7755 EVALUATION BOARD SETUP
LOGIC OUTPUTS
Figure 5 shows how the AD7751/AD7755 evaluation board can
be set up for a simple evaluation. Two signal generators are
used to provide the sinusoidal (ac) signals for Channel 1 and
Channel 2. The user must have some way of phase locking the
generators. This will ensure that the sinusoidal signals remain in
phase. Also if the AD7751 and AD7755 performance-over-power
factor is being evaluated, two separate signal sources will be
required. The generators are shown connected in a single-ended
configuration. The grounded analog inputs of Channel 1 and
Channel 2 (V1N and V2N) are connected to AGND via an
antialias filter. In Figure 5, analog input V2N is grounded via
R55 and R56. The capacitor C53 is connected in parallel.
AD7751 and AD7755 provide the active power information in
the form of an output frequency. The three frequency outputs
are F1, F2 and CF. Consult the AD7751 and AD7755 data
sheets for more information on these outputs. The logic outputs
F1 and F2 are intended to be used to drive an impulse counter
or stepper motor. The outputs are buffered and available at the
connector SK6. A stepper motor may be directly connected
here. The power supply for the buffer is VCC (SK4A) and may
be connected to either the AD7751/AD7755 supply using
jumper JP21, or to its own supply.
The logic output CF can be directly connected to an LED using
JP19 (Position B) or to an optically isolated output (Position A).
By closing Positions A and B, both options are selected. The
optically isolated output is available at connector SK5. This
isolated output is useful when the evaluation board is connected
directly to a high voltage (e.g., 220 V residential). A typical connection diagram for this isolated output is shown in Figure 6.
JP1
R50
SK2A
JP2
50Hz
SH1
JP4
V1N
JP19
C51
A
B
JP5
VPLUS
TP3
R52
SK2C
TP2
C50
R51
SH2
V1A
JP3
200mV
SK2B
TP1
+
5V–12V
R23
JP6
C52
U4
CFOUT
50Hz
SK5A
R20
V1B
R22
SK5B
JP7
200mV
SK1A
R53
JP52
R54
R55
R31
JP8
C53
N
V2N
B
P
V2P
JP51
JP50
A
TP4
GND
TP5
R57
JP10
The logic output REVP indicates negative power measurement.
Since the frequency outputs can only convey magnitude information, the sign of the power calculation is given by the REVP
logic output. For more information regarding this output see the
AD7751/AD7755 data sheet. This output is connected to an
LED on the evaluation board. The LED will be illuminated if
negative power is detected.
N
P
C54
SK5C
Figure 6. Typical Connection for Opto Output
R56
JP9
SK1B
COUNTER
H11L1
JP11
Figure 5. Typical Connection for Analog Inputs
The AD7751 also has a logic output called FAULT. This output goes active when the signal levels on V1A and V1B differ by
more than 12.5% (see Figure 3). This output is also connected
to an LED on the evaluation board. Jumper J22 should be open
when evaluating the AD7751.
All logic outputs can be monitored via test points 6 to 10 (TP6
to TP10). These test points provide easy access for scope probes
and meter probes.
REV. 0
–3–
EVAL-AD7751/AD7755EB
AD7751/AD7755 OUTPUT FREQUENCY SELECTION
AD7755 EVALUATION BOARD SET UP AS AN ENERGY
METER
AD7751 and AD7755 provide up to four different output frequencies on F1 and F2. The output frequency selection is made
via the logic inputs S0 and S1—see AD7751/AD7755 data
sheet. On the evaluation board these inputs are set by using
jumpers JP15 and JP16. The logic input SCF is set via jumper
14 (JP14). For a full explanation of the AD7751/AD7755 output frequency selection see the data sheet.
Figure 7 shows a wiring diagram that allows a simple energy
meter to be implemented using the AD7755 evaluation board.
The current transducer used in this example is a shunt (400 µΩ).
The meter is intended to be used with a line voltage of 220 V
and a maximum current of 25 A. The frequency outputs F1 and
F2 can be used to drive a mechanical counter. These outputs
will be calibrated to provide 100 imp/kWhr. The logic output
CF has an output frequency that can be up to 128 times higher
than the frequency on F1 and F2. This output can be used for
calibration purposes and is shown connected to a frequency
counter via the optoisolator in Figure 7.
AD7751/AD7755 INPUT GAIN SELECTION
AD7751 and AD7755 provide up to four different gain settings
on the analog input Channel 1. These gain settings are 1, 2, 8
and 16. The gain selection on the evaluation board is made via
JP17 and JP18.
At maximum current (25 A), the power seen by the meter will
be 5.5 kW. This will produce a frequency of 0.153 Hz on F1
and F2 when these outputs are calibrated to 100imp/kWhr
(100imp/hr = 0.02777 Hz, 0.02777 × 5.5 = 0.153 Hz). From
Table III in the AD7755 data sheet, the closest frequency to
0.153 Hz in the half-scale ac inputs column is for F2, i.e., 0.17 Hz.
Therefore F2 is selected by setting S0 = 1 and S1 = 0. The
choice of CF frequencies in this mode (see Table IV in the
AD7755 data sheet) are 32 times F1 and 64 times F1. For this
example 64 times F1 is selected by setting SCF = 1.
EXTERNAL CLOCK INPUT
AD7751 and AD7755 are specified with a CLKIN value of
3.579545 MHz. The evaluation board uses a crystal of this value
for the on-chip gate oscillator circuit. However, an input is
provided to allow an external clock source to be used. An impedance matching resistor (R11) of 50 Ω is also available on the
board. NOTE: when using the on-chip oscillator this resistor
must be removed or the on-chip oscillator circuit will not start
up.
5.000V
5.000V
SK3B
First we can calculate the voltage required in Channel 2 in order
to calibrate the frequency on the logic outputs F1 and F2 to
100imp/kWhr. The AD7755 data sheet gives the equation which
relates the voltage on Channel 1 and Channel 2 to the output
frequency on F1 and F2.
JP20 = CLOSED
JP21 = CLOSED
SK5A
220V
5A
SK3A
AGND AVDD
NEUTRAL PHASE
SHUNT
Since the voltage on Channel 1 is fixed, the only possible way of
calibrating (adjusting) the output frequency in F1 and F2 is by
varying the voltage on Channel 2. This is carried out by varying
the attenuation of the line voltage using the trim pot.
SK2B
JP1 = OPEN
JP2 = CLOSED
JP3 = OPEN
JP4 = OPEN
JP5 = OPEN
JP6 = OPEN
V1N
2mV
TP11
AGND
JP7
SK1A
R53
R54
SK1B
LOAD
JP52
R55
SK5C
R31
(1)
The output frequency at 5 A on F1 and F2 should be 0.02777 Hz
(100imp/kWhr) × 1.1 (220 V × 5 A = 1.1 kW) = 0.03055 Hz.
218mV
V2P
B
From Equation 1 the voltage on Channel 2 should be set to
218 mV. The attenuation network as shown in Figure 1 is used
to attenuate 220 V to 218 mV. R53 = 660 kΩ, R54 = 100 kΩ,
R56 = 500 Ω and the trim pot R31 = 500 Ω.
JP51
R56
JP50 = P
JP51A = CLOSED
JP52 = CLOSED
R55 = REMOVED
2
First a current is selected for calibration, 5 A for example. This
gives a Channel 1 voltage of 400 µΩ × 5 A = 2 mV rms. The
gain of Channel 1 on the AD7755 is set to 16 (G0 = G1 = 1).
The on-chip or external reference of 2.5 V is selected using
JP13.
JP14 = A
JP15 = B
JP16 = A
JP17 = A
JP18 = A
A
8.06 × V 1 × V 2 × Gain × F1− 4
VREF
JP8
C53
JP7 = OPEN
JP8 = OPEN
JP9 = OPEN
JP10 = CLOSED
JP11 = N
Freq =
JP12 = B
JP19A = CLOSED
JP22 = CLOSED
V1P
SK2C
6400
imp/kWhr
SK5B
1.9555 Hz
However, since the meter is being calibrated at CF and CF is
set to 64 times F1, the voltage on Channel 2 should be adjusted
until CF = 64 × 0.03055 Hz = 1.9555 Hz is registered on the
frequency counter. The counter should be set up to display the
average of ten frequency measurements on CF. This will
remove any ripple due to the instantaneous power signal. See
the AD7755 data sheet for more details.
Figure 7. AD7755 Evaluation Board as an Energy Meter
–4–
REV. 0
EVAL-AD7751/AD7755EB
AD7751 EVALUATION BOARD SET UP AS AN ENERGY
METER
Figure 8 shows a wiring diagram that allows a simple energy
meter to be implemented using the AD7751 evaluation board.
Because the AD7751 monitors both the phase and neutral currents, isolation is required on at least one of the current transducers. One convenient way to provide isolation and eliminate
problems with matching is to use two CTs (current transformers). The CTs are connected as shown in Figure 8. The CTs
have a turns ratio of 1:2500. The burden resistance for the CTs
can be placed on the evaluation board at SH1 and SH2. The
meter is intended to be used with a line voltage of 240 V and a
maximum current of 60 A. The frequency outputs F1 and F2
can be used to drive a mechanical counter. These outputs will
be calibrated to provide 100 imp/kWhr. The logic output CF
has an output frequency that can be up to 128 times higher than
the frequency on F1 and F2. This output can be used for calibration purposes and is shown connected to a frequency counter
via the optoisolator in Figure 8.
5.000V
240V
SK5A
V1A
SH1
1.2V
15A
SH1
1.2V
15A
CT
1:2500
TP11
AGND
3200
imp/kWhr
7.2mV
JP1 = OPEN
JP2 = OPEN
JP3 = OPEN
V1N JP4 = CLOSED
7.2mV JP5 = OPEN
JP6 = OPEN
SK5B
SK1A
SK1B
R54
12kV
LOAD
R31
500V
C53
JP7 = OPEN
JP8 = OPEN
JP9 = OPEN
JP10 = CLOSED
JP11 = N
R55
JP50 = P
JP51A = CLOSED
JP52 = CLOSED
R55 = REMOVED
A
However since the meter is being calibrated at CF and CF is set
to 32 times F1, the voltage on Channel 2 should be adjusted
until CF = 32 × 0.1 Hz = 3.2 Hz is registered on the frequency
counter. The counter should be set up to display the average of
ten frequency measurements on CF. This will remove any ripple
due to the instantaneous power signal. See the AD7751 data
sheet for more details.
278mV
V2P
B
3.2000 Hz
Figure 8. AD7751 Evaluation Board as an Energy Meter
REV. 0
(2)
From Equation 2 the voltage on Channel 2 should be set to
278 mV. The attenuation network as shown in Figure 1 is used
to attenuate 240 V to 278 mV. R53 = 580 kΩ, R54 = 12 kΩ,
R56 = 500 Ω and the trim pot R31 = 500 Ω.
JP51
R56
500V
2
The output frequency at 15 A on F1 and F2 should be
0.02777 Hz (100imp/kWhr) × 3.6 (240 V × 15 A = 3.6 kW) =
0.1 Hz.
SK5C
V1B JP12 = B
JP19A = CLOSED JP14 = A
JP22 = OPEN
JP7
JP15 = A
JP16 = B
R53
JP17 = A
JP52
580kV
JP18 = B
JP8
5.74 × V 1 × V 2 × Gain × F1− 4
First a current is selected for calibration, 15 A for example. This
gives a Channel 1 voltage of 15 A/2500 × 1.2 Ω = 7.2 mV rms.
The gain of Channel 1 on the AD7755 is set to 8 (G0 = 0, G1 =
1). The on-chip or external reference of 2.5 V is selected using
JP13.
JP20 = CLOSED
JP21 = CLOSED
SK2
1:2500
CT
First we can calculate the voltage required on Channel 2 in
order to calibrate the frequency on F1 and F2 to 100imp/kWhr.
The AD7751 data sheet gives the equation which relates the
voltage on Channel 1 and Channel 2 to the output frequency on
F1 and F2.
VREF
SK3A
AGND AVDD
NEUTRAL PHASE
Since the voltage on Channel 1 is fixed, the only possible way of
calibrating (adjusting) the output frequency on F1 and F2 is by
varying the voltage on Channel 2. This is carried out by varying
the attenuation of the line voltage using the trim pot.
Freq =
5.000V
SK3B
At maximum current (60 A) the power see by the meter will
be 14.4 kW. This will produce a frequency of 0.4 Hz on the
logic outputs F1 and F2 when these outputs are calibrated to
100imp/kWhr (100imp/hr = 0.02777 Hz, 0.02777 × 14.4 =
0.4 Hz). From Table III in the AD7751 data sheet, the closest frequency to 0.4 Hz in the half-scale ac inputs column is for
F3, i.e., 0.34 Hz. Therefore F3 is selected by setting S0 = 0 and
S1 = 1. The choice of CF frequencies in this mode (see Table
IV in the AD7751 data sheet) are 16 times F1 and 32 times F1.
For this example 32 times F1 is selected by setting SCF = 1.
–5–
EVAL-AD7751/AD7755EB
JUMPER SELECTION
The AD7751/AD7755 evaluation board comes with several
jumper selections that allow the user to exercise all of the
AD7751 and AD7755 functionality. There are also some options such as attenuation networks and optically isolated outputs
that allow the AD7751 and AD7755 to be evaluated under the
same conditions as the end application. Table I outlines all the
jumper options and explains how they are used. Table I should
be used in conjugation with Figure 9, which will make it easier
to locate the jumper in question.
Jumper
Option
Description
JP7
Closed
Closing this jumper will short resistors
R53 and R54. The analog input V2P is
connected directly to SK1A. This has the
effect of removing the antialias filter and
attenuation network from this input. Note:
if the board is being connected to a high
voltage, this jumper must be left open.
Antialias filter and attenuation network on
the input V2P is enabled.
Open
Table I.
JP8
Jumper
Option
Description
JP1
Closed
Closing this jumper will short resistor R50
and connect analog input V1A directly to
SK2A. This has the effect of removing the
antialias filters from this input.
Antialias filter in input V1A is enabled.
Open
JP2
Closed
Open
JP3
Closed
Open
JP4
Closed
Open
JP5
Closed
Open
JP6
Closed
Open
Closed
Open
JP9
Analog input V1A is connected to analog
ground (AGND) via the antialias filter.
Normal operation.
Closed
Open
Closing this jumper will short resistor R51
and connect analog input V1N directly to
SK2B. This has the effect of removing the
antialias filters from this input.
Antialias filter in input V1A is enabled.
JP10
Closed
Open
Analog input V1N is connected to analog
ground (AGND) via the antialias filter.
This jumper should be closed if the AD7751
is being used as these inputs are used
single-ended on the AD7751.
When evaluating the AD7755, Channel 1
is best used in a differential mode and this
jumper should be left open. An example is
shown in Figure 4. In this example a shunt
is used to sense the current. The shunt can
be referenced to the AGND of the board
by using TP11 as shown.
JP11
N
P
JP12
A
B
JP13
Closing this jumper will short resistor R52
and connect analog input V1B (V1P
AD7755) directly to SK2C. This has the
effect of removing the antialias filters from
this input.
Antialias filter in input V1A (V1P) is
enabled.
Analog input V1B (V1P) is connected to
analog ground (AGND) via the antialias
filter.
Normal operation.
–6–
Open
Analog input V1A is connected to analog
ground (AGND) via the antialias filter.
Note: SK1A is also connected to AGND
and care should be taken if this input is
connected to a high voltage source.
Normal operation.
Closing this jumper will short resistor R57
and connect analog input V2N directly to
SK2B. This has the effect of removing the
antialias filters from this input.
Antialias filter in input V2N is enabled.
Analog input V2N is connected to analog
ground (AGND) via the antialias filter.
This option should be selected if Channel
2 is being used in a single-ended mode.
V2N connected to SK2B for differential
operation.
SK1B connected to V2N (AD7751/
AD7755).
SK1B connected to V2P (AD7751/
AD7755).
Logic input AD/DC is connected to
DGND.
Logic input AD/DC is connected to
DVDD.
Closed
AD7751/AD7755 internal (on-chip) reference selected.
External (AD780) reference selected.
JP14
1
0
SCF connected to DVDD.
SCF connected to DGND.
JP15
1
0
S1 connected to DVDD.
S1 connected to DGND.
JP16
1
0
S0 connected to DVDD.
S0 connected to DGND.
JP17
1
0
G1 connected to DVDD.
G1 connected to DGND.
JP18
1
0
G0 connected to DVDD.
G0 connected to DGND.
REV. 0
EVAL-AD7751/AD7755EB
Jumper
Option
Description
Jumper
Option
Description
JP19
A
JP51
A
B
CF logic output connected to optically
isolated output at SK5.
CF logic output connected to LED.
JP20
Closed
AVDD and DVDD connected together.
Trim pot R31 is connected to V2P (depending on the position of JP50)—see
Figure 1. This allows the AD7751/
AD7755 output frequency to be scaled
using the voltage on V2P.
JP21
Closed
DVDD and VCC connected together.
B
JP22
Closed
Output FAULT (NC on AD7755) is
connected to DGND via R7. JP22 should
be closed when using the AD7755.
Should be open when evaluating the
AD7751. Leaving closed will disable the
FAULT LED.
When option B is selected, the jumper JP52
should be left open. In this configuration
the attenuation for V2P is provided via the
fixed resistors R53, R54, R55 and R56.
Open
When open, the attenuation on V2P is
provided by fixed resistor as explained
above. Also see Figure 1.
Closed
When closed, the trim pot becomes part of
the attenuation network. In this mode of
operation the resistor R55 should be removed from its PCB jack sockets.
Open
JP50
N
P
JP52
SK1A connected to V2N (AD7751/
AD7755).
SK1A connected to V2P (AD7751/
AD7755).
JP1
JP21
JP2
A
JP3
JP4
JP6
JP5
JP51A
JP51B
JP12
JP22
B
JP20
JP52
N
A B
P
JP7
JP19
JP50
JP13
JP8
N P
JP9
JP10
1
JP11
JP18
JP17
JP16
JP14
JP15
0
Figure 9. AD7751/AD7755 Evaluation Board Jumper Positions
REV. 0
–7–
EVAL-AD7751/AD7755EB
Evaluation Board Bill of Material
Designator
Value
Description
R1, R2, R3, R4, R5, R23
1 kΩ, 5%, 1/4 W
Resistor, No Special Requirements.
R6, R22
100 Ω, 5%, 1/4 W
Resistor, No Special Requirements.
R7, R8, R9, R10, R58
10 kΩ, 5%, 1/4 W
Resistor, No Special Requirements.
R11
51 Ω, 1%, 1/4 W
FARNELL Part No. 335-629. Not placed unless external clock is being used.
R14, R18, R19, R20
820 Ω, 5%, 1/4 W
Resistor, No Special Requirements.
R16, R17
20 Ω, 5%, 1/4 W
Resistor, No Special Requirements.
R31
500 Ω, 10%, 1/2 W
Trim Pot Resistor, 25 Turn.
BOURNS.
FARNELL Part No. 348-247.
R50, R51, R52, R57
1 kΩ, 0.1%, 1/4 W
± 15 ppm/°C Resistor, good tolerance, used as part of the analog filter network. These resistors are not soldered, but are plugged into PCB mount
sockets for easy modification by the customer. Low drift WELWYN RC55
Series, FARNELL Part No. 339-179.
R53
1 MΩ, 10%, 0.6 W
± 50 ppm/°C, FARNELL Part No. 336-660.
R54
100 kΩ, 10%, 1/4 W
± 15 ppm/°C, FARNELL Part No. 341-094.
R55, R56
499 Ω, 0.1%, 1/4 W
± 15 ppm/°C Resistor, Good Tolerance. Low Drift.
FARNELL Part No. 338-886.
C5, C7, C24, C28, C30
10 µF, 10 V dc
Power supply decoupling capacitors, 20%, Philips CW20C 104, FARNELL
Part No. 643-579.
C14, C15
22 pF, Ceramic
Gate Oscillator Load Capacitors, FARNELL Part No. 108-927.
C6, C8, C27, C29, C23,
C20, C21, C55
100 nF, 50 V
Power Supply Decoupling Capacitors, 10%, X7R type, AVX-KYOCERNA,
FARNELL Part No. 146-227.
C9, C10, C11, C12, C13
10 nF
Philips CW15C 103 M, FARNELL Part No. 146-224.
C50, C51, C51, C53, C54
33 nF, 10%, 50 Volt
X7R Capacitor, Part of the Filter Network. These resistors are not soldered,
but are plugged into PCB mount sockets for easy modification by the customer. SR15 series AVX-KYOCERNA, FARNELL Part No. 108-948.
U1
AD7751 or AD7755
Supplied by Analog Devices Inc.
U2
74HC08
Quad CMOS AND gates.
U3
AD780
2.5 V Reference, Supplied by Analog Devices Inc.
U4
H11L1
Optical Isolator, by QT, FARNELL Part No. 326-896.
D1, D2, D3
LED
Low Current, Red, FARNELL Part No. 637-087.
Y1
3.579545 MHz
Quartz Crystal, IQD A119C, 50 ppm/°C, FARNELL Part No. 170-229.
HC49 Can Style, Pitch 4.88 mm.
SK1, SK3, SK6
Screw Terminal
15 A, 2.5 mm Cable Screw Terminal Sockets. FARNELL Part No. 151-785.
Length 10 mm, Pitch 5 mm, Pin diameter 1 mm.
SK2, SK4, SK5
Screw Terminal
15 A, 2.5 mm Cable Screw Terminal Sockets. FARNELL Part No. 151-786.
Length 15 mm, Pitch 5 mm, Pin diameter 1 mm.
BNC
BNC Connector
Straight Square, 1.3 mm Holes, 10.2 mm × 10.2 mm.
FARNELL Part No. 149-453.
–8–
REV. 0
EVAL-AD7751/AD7755EB
SK3B
SK3A
AVDD
DVDD
C24
C23
U2
TP1
JP2
C50
JP3
SH1
R51
JP4
74HC08
F1
AD7751/
AD7755
SK6A
C20
TP7 R8
4
CF
A
9
8
10
TP3
JP6
C52
D3
JP19
R18
JP22
V1B/V1P
V1B (AD7751)
V1P (AD7755)
7
R20
JP7
SK5A
4
A
CFOUT
V2N
B
P
JP51
JP50
JP8
C53
C14
P
C54
C10
SCF
AVDD
C9
REFIN/OUT
C5
2
C8
U3
AD780
C11
S1
JP11
BNC
EXTERNAL
CLOCK IN
C13
C12
S0
SK1B
JP10
R11
G0
G1
TP5
GND
R6
CLKIN
V2P
N
R57
H11L1
5
SK5C
Y1
R56
JP9
2
CLKOUT
N
TP4
R22
SK5B
D1
C15
R55
R31
R23
R14
JP52
R54
C7
U4
6
REVP
R53
SK1A
VPLUS
D2
1
TP10
TO IMPULSE
COUNTER /
STEPPER MOTOR
R19
11
13
FAULT/NC*
R52
SK6B
B
12
TP9 R7
SK2C
R17
C21
6
5
TP8 R10
JP5
R16
3
2
F2
V1N
V1N (AD7751)
V1N (AD7755)
C51
14
1
TP6 R9
V1A/NC*
TP2
SK2B
SH2
U1
V1A (AD7751)
NC* (AD7755)
DGND
AC/DC DVDD
AVDD
JP1
R50
DVDD
VCC
AGND
SK2A
SK4C
C28
C27
A B
AVDD
SK4B
JP12
C29
C30
SK4A
C6
RESET
JP13
6
AGND DGND
R58
R1
R2
R3
R4
R5
A
A
A
A
A
B
B
B
B
B
JP14
JP15
JP16
JP17
JP18
DVDD
AVDD
4
C55
SW1
AVDD
PCB MOUNT SOCKETS
AGND
TP11
NC = NO CONNECT
JP20
Figure 10. Evaluation Board Schematic
REV. 0
DVDD
–9–
VCC
DGND
TP12
JP21
EVAL-AD7751/AD7755EB
Figure 11. PCB Layout–Component Side
–10–
REV. 0
EVAL-AD7751/AD7755EB
Figure 12. PCB Layout–Solder Side
REV. 0
–11–
C3620–2–8/99
EVAL-AD7751/AD7755EB
PRINTED IN U.S.A.
Figure 13. PCB Layout–Component Placement
–12–
REV. 0