ULI-242T
ULI-244TI
ULI-244T
ULI-246T
BB-232HESP
BB-HESP4DR
3-Stage RS-232/422/485
Serial Surge Suppressors
BB-422HESP
BB-485HESP
Features
• Three stages of protection on every data line:
1) Gas discharge tube
2) Series resistor
3) Transient voltage suppressor
• Protected signal ground connection
• Rugged terminal block connections
• Dedicated chassis ground lugs
ULI-244TI
ULI-242T
BB-HESP4DR
BB-232HESP
Introduction
These three-stage surge suppressors protect against lightning strikes and other voltage disturbances with three stages of protection for each line: a gas discharge tube
followed by a series resistor and finally a Transient Voltage Suppresser (TVS). The devices are housed in rugged cases with a protected signal ground connection and dedicated
chassis ground lugs. In order to work properly, it is important to have a good connection between the #10 screws and a solid earth ground.
Specifications
Meantime Between Failures (MTBF)
• Calculation Method
Serial Interface
Model:
ULI-242T
ULI-244TI
ULI-244T
ULI-246T
Line Connectors:
Equipment Connectors:
Terminal blocks
Interfaces:
RS-232
Terminal blocks
RS-422, RS-485
RS-485
Clamping Voltage Series Resistance Clamping Voltage Clamping
- Stage 1:
- Stage 2:
- Stage 3:
Time:
14.3 Vdc, min.
15.8 Vdc, max.
ULI-242T*
ULI-244TI#
ULI-244T*
ULI-246T*
72 Vdc, min.
108 Vdc, max.
2.7 Ohms
Hours:
7522077
862813
6976322
4664831
Regulatory / Approvals / Certifications
Isolation & Surge Suppression
Model:
Model:
ULI-242T
ULI-244TI
ULI-244T
ULI-246T
MIL217F Parts Count Reliability Prediction
6.45 Vdc, min.
7.14 Vdc, max.
Lines
Protected:
5
9
< 5 x10
seconds
3
*2 terminal posts and 2 metal mounting brackets provide a good ground connection.
#1 terminal post provides a good ground connection.
• FCC, CE (all models)
Model:
ULI-242T
ULI-244TI
ULI-244T
ULI-246T
CE Standards
CE Directives
2014/30/EU – Electromagnetic
Compatibility Directive
2011/65/EU – amended by (EU)
2015/863 Reduction of Hazardous
Substance Directive (RoHS)
2012/19/EU -–Waste Electrical and
Electronic Equipment (WEEE)
EMC:
EN 55032 Class B – Electromagnetic Compatibility of
Multimedia Equipment – Emission Requirements
EN 55024 – Information Technology Equipment –
Immunity Characteristics – Limits and Methods of
Measurement
Mechanical
Model:
ULI-242T
ULI-244TI
ULI-244T
ULI-246T
Enclosure:
Metal
Plastic
Metal
Dimensions, mm:
114 x 84 x 46
35.5 x 78.8 x 105.3
114 x 84 x 46
Mounting:
Panel
DIN rail
Panel
Weight, gm
190
114
190
Environmental
Model:
ULI-242T
ULI-244TI
ULI-244T
ULI-246T
Operating Temperature: Storage Temperature: Operating Humidity:
0 to +70 °C
-40 to +80 °C
-40 to +85 °C
0 to 95%, non-condensing
0 to +70 °C
Intelligent Connectivity
All product specifications are subject to change without notice.
Last updated: 10-Aug-2021
ULI-242T
ULI-244TI
ULI-244T
ULI-246T
BB-232HESP
BB-HESP4DR
BB-422HESP
BB-485HESP
Dimensions
- ULI-242T, ULI-244TI, ULI-246T
Unit = mm
82.71±0.76
3.26±.03
5.16
.20
4.98
.20
86.61±0.51
3.41±.02
64.10
2.52
29.50
1.16
46.54
1.83
114.80
4.52
Dimensions
- ULI-244TI
Unit = mm
105.3 mm
4.2 in
78.8 mm
3.1 in
35.5 mm
1.4 in
Ordering Information
Model
Part Number to Order
Description
ULI-242T
ULI-244TI
ULI-244T
ULI-246T
BB-232HESP
3-stage RS-232 Surge Suppressor, 5 Protected Lines, Panel Mount.
3-stage RS-422/485 Surge Suppressor, 5 Protected Lines, Wide Temperature, DIN Rail Mount.
3-stage RS-422/485 Surge Suppressor, 5 Protected Lines, Panel Mount.
3-stage RS-485 Surge Suppressor, 3 Protected Lines, Panel Mount.
BB-HESP4DR
BB-422HESP
BB-485HESP
Online Download www.advantech.com/products
ULI-240 Series Selection Guide
3-Stage RS-232/422/485
Serial Surge Suppressors
Common Features
• Three stages of protection on every data line:
1) Gas discharge tube
2) Series resistor
3) Transient voltage suppressor
• Protected signal ground connection
• Rugged terminal block connections
• Dedicated chassis ground lugs
Surge Suppressor Comparison Table
Model Number
ULI-242T
ULI-244T
ULI-244TI
ULI-246T
Part Number to Order
BB-232HESP
BB-422HESP
BB-HESP4DR
BB-485HESP
Description
Key Features
Serial Protocol
Serial Line Connectors
Equipment Line Connectors
Stage 1: Clamping Voltage
Stage 2: Series Resistance
Stage 3: Clamping Voltage
Clamping Time
Lines Protected
Enclosure
Dimensions, mm
Mounting Installation
Operating Temperature
MTBF (MIL217F), hours
Regulatory/Approvals/
Certifications
3-Stage Surge Suppressors
DIN Rail Mount, Plastic Case,
Rugged Metal Case,
Rugged Metal Case, Panel Mount
Wide Operating Temperature
Panel Mount
RS-232
RS-422/485
RS-485
Terminal blocks
Terminal blocks
72 to 108 Vdc (min./max.)
2.7 Ohms
14.3 - 15.8 Vdc (min./max.)
6.45 - 7.14 Vdc (min./max.)
Less than 5 x109 seconds
5
3
Metal
Plastic
Metal
114 x 84 x 46
35.5 x 78.8 x 105.3
114 x 84 x 46
Panel
DIN rail
Panel
0 to +70 °C
-40 to +80 °C
0 to +70 °C
7522077
6976322
862813
4664831
FCC, CE, ECD, RoHS, WEEE
2014/30/EU – Electromagnetic Compatibility Directive
2011/65/EU – amended by (EU) 2015/863 Reduction of Hazardous Substance Directive (RoHS)
2012/19/EU -–Waste Electrical and Electronic Equipment (WEEE)
EN 55032 Class B – Electromagnetic Compatibility of Multimedia Equipment – Emission Requirements
EN 55024 – Information Technology Equipment – Immunity Characteristics – Limits and Methods of Measurement
Intelligent Connectivity
All product specifications are subject to change without notice.
Last updated: 10-Aug-2021
很抱歉,暂时无法提供与“BB-HESP4DR”相匹配的价格&库存,您可以联系我们找货