Wzzard™ Mesh Wireless Sensors
– for Industrial Applications
BB-WSD2x series
www.advantech.com
PRODUCT FEATURES
+ Ultra-low power 802.15.4e SmartMesh® IP technology
+ Communicates with SmartSwarm-342 gateway via scalable and
reliable wireless mesh networks
+ Connect to most any industry standard sensors
+ Rugged, IP67 rated, fiber reinforced polyester PBT enclosure
+ MQTT and JSON IoT protocol to application platform
+ Sensor interface cable and antenna included
+ UL Listed C1/D2 for hazardous locations (conduit models only)
Wireless Connectivity Where You Need It
The Wzzard™ intelligent wireless sensor platform creates a complete, quick
and easy connectivity stack between your sensors and application – on your
network or the Internet. The platform uses Wzzard mesh sensor edge nodes
and a wireless 802.15.4e SmartMesh IP network to transmit sensor data to
a SmartSwarm Gateway. The gateway can connect to the Internet via wired
connections or cellular data networks and communicate with application
platforms using the MQTT IoT protocol and JSON data formats.
Wzzard mesh wireless sensor nodes can accommodate virtually any
industry-standard external sensors. Connections can be made via M12
connector or conduit fitting. The nodes provide a wide variety of sensor
interface options, including general purpose analog input, digital input/output
and thermocouple. All nodes contain an internal temperature sensor.
Secure, Reliable and Highly Scalable Wireless Networking
The 802.15.4e Wzzard platform uses mesh networking and timesynchronized channel hopping to provide up to 99.999% connectivity, even
in the most demanding RF environments. New nodes may be added at any
time and the SmartMesh IP network will dynamically self-configure as new
nodes are added or removed.
Easy Configuration and Installation
Configuration of the Wzzard sensor platform is easy via the SmartSwarm
Gateway. Nodes can be configured with scaling information, eng. units,
friendly names, geo-location and other descriptive information.
The platform simplifies physical installation, too. Nodes can be attached to
any surface via mounting ear flanges and screws or the embedded magnetic
base. Magnetic mount is convenient for RF link location determination or
other purposes. (Permanent use of the magnetic mount is not approved for
UL installations.) The IP67 rated, fiber reinforced polyester PBT housing
makes the units deployable in any industrial or commercial environment.
Intelligence at the Network Edge
The Wzzard wireless platform places intelligence at the network edge. The
Wzzard mesh wireless sensor nodes can be configured to communicate data
only when specified threshold or alert levels are exceeded. When reporting,
they can associate useful information like geo-location, device name and
uptime. This eliminates unnecessary network traffic, eases the processing
burden on upstream resources and cuts the cost of cellular data plans when
the gateway is using the cellular data network. Thanks to low-power wireless
technology and programmable time synchronization, the Wzzard mesh
wireless sensor nodes can operate for many years on battery power.
SPECIFICATIONS
POWER
Internal
(2) 3.6V 2400 mAH Lithium Thionyl Chloride AA Batteries
Battery Life
Optional External
Input Voltage
SENSOR POWER OUT
Switched Vbat
Switched Vref
MECHANICAL
>5 years – based on 1 min. sensor sampling and reporting
Connection Options
Sensors
External Antenna
(included)
Mounting Options
Enclosure
Weight
TECHNOLOGY
Wireless
Protocols
LED
ENVIRONMENTAL
Installation
10-30 VDC @ 40mA peak
Battery Power – Turned on at time of measurement (20 mA max)
3.3V (+/- 0.1%) – Turned on at time of measurement (20 mA max)
Conduit (UL Type 3 outdoor approved): 12.7mm (0.5 in)
- includes (1) one sensor interface cable - 8-pin 26-gauge wire
harness, 1.8 m (6 ft) (Model# BB-WSCACO-6)
M12 connector (Not UL rated for outdoor installations.)
Analog Input (0 -10 VDC, 0 - 20 mA, 4 - 20 mA)
Digital Input (0 - 48 VDC)
Digital Input Frequency 1-1K Hz (accuracy +/- 1 Hz)
Digital Input Counter
Integrated Temperature
Thermocouple (J, K, N, R, S, T, B, E)
Digital Output, Sinking, up to 100mA @ 30VDC
RP-SMA, Omni-directional, 3.8 dBi, 2.4 GHz (included)
Dimensions: 194 mm (7.64 in)
(4) Mounting Ears, M5 (#10) screws (UL approved option)
Magnetic Mounting (via internal enclosure magnet)
Pull Force 2.13 kg (4.7 lb)
Note: Magnetic mounting (all models) not rated for UL installations.
IP67 rated fiber reinforced polyester PBT
0.34 kg (0.75 lb)
802.15.4e, SmartMesh IP
MQTT, JSON
Network Connectivity
Indoor/Outdoor
Note: M12 models are rated for outdoor use (except in UL installations).
Operating Temperature -40 to +80 °C (-40 to +176 °F)
Storage Temperature
-40 to +85 °C (-40 to +185 °F)
Operating Humidity
0 to 95% Non-condensing
WIRELESS SECURITY
Device Authentication
128-bit, AES-based Encryption – with multiple keys
Message Integrity Check (MIC)
Synchronized Key Changeovers
Customized Key Rotation
All product specifications are subject to change without notice.
BB-WSD2x_WzzardWirelessSensorNodes-Ind_4019ds
Advantech B+B SmartWorx, 707 Dayton Road, PO Box 1040 Ottawa, IL 61350 USA 1 (800)346-3119/Toll Free | orders@advantech-bb.com | support@advantech-bb.com
Wzzard™ Mesh Wireless Sensors
– for Industrial Applications
BB-WSD2x series
ORDERING INFORMATION
MODEL NUMBER
DESCRIPTION
BB-WSD2C21150
Industrial Cooler/HVAC Node
CONNECTOR INCLUDES
2 Analog Inputs, 1 Digital Input, 1 Digital Output, 2 Thermocouples,
Conduit
2 Thermistors, Internal Temperature
BB-WSD2C06010
Industrial Digital Input Node
Conduit
6 Digital Inputs, Internal Temperature
BB-WSD2C31010
Industrial Power Monitor Node
Conduit
3 Analog Inputs, 1 Digital Input, Internal Temperature
Indoor / Outdoor,
w/ mounting ear installation
BB-WSD2M06010
Industrial Digital Input Node
M12
6 Digital Inputs, Internal Temperature
No (M12 connector not UL.)
BB-WSD2M31010
Industrial Power Monitor Node
M12
3 Analog Inputs, 1 Digital Input, Internal Temperature
No (M12 connector not UL.)
M12
2 Analog Inputs, Vbat measurement, 1 Digital Input, Internal Temperature, No (M12 connector not UL.)
Switched Vbat Power Out (2 sec.)
12 Analog Inputs, Vref measurement, 1 Digital Input, Internal Temperature, No (M12 connector not UL.)
Switched 3.3V Power Out (100 ms)
BB-WSD2M3101P2K
Industrial Power Monitor Node
BB-WSD2M3101R100 Industrial Power Monitor Node M12
UL LISTED C1/D2
Indoor / Outdoor,
w/ mounting ear installation
(pending)
ACCESSORIES - sold separately
MODEL NUMBER
BB-ACH2-DBAT-DP002
BB-ZXTMT
BB-WSCACO-6
BB-WSCAM12-6
BB-JC10F50-V
BB-JC24S250-V
BB-JC36S500-V
BB-WCD-TM2M
BB-WTJ-10-36-TT
BB-HS-104T2505402
BB-WSDCBL-ACL-2
BB-T9602-3-A-1-G2
DESCRIPTION
Antenna - dipole, 2.4/5 GHz, 2dBi, RPSMA, rubber duck, hinged
(Replacement; 1 included with all nodes.)
Kit - Zlinx™ Xtreme conduit cable gland & hub
Sensor interface cable, 8-pin 26-gauge wire harness, 1.8m (6ft)
(Replacement; 1 included with conduit nodes.)
Cable - M12 pigtail, 8-pin, 1.8 m (6 ft)
Sensor - 50A clamp-on AC current, 0-5VDC Out
Sensor - 250A clamp-on AC current, 0-5VDC Out
Sensor - 500A clamp-on AC current, 0-5VDC Out
Thermistor cable
Sensor - J-type thermocouple, #10 mounting hole, ungrounded
Sensor - low power vibration/temperature sensor, 250mV/g
M12 signal conditioning cable for model# BB-HS-104T2505402
Sensor cable - temperature/humidity, 1.8 m (6 ft)
COMPATIBLE NODES
All Industrial Nodes
All Conduit Nodes
All Conduit Nodes
All M12 Nodes
All Analog Input Nodes
All Analog Input Nodes
All Analog Input Nodes
BB-WSD2C21150
BB-WSD2C21150
BB-WSD2M3101P2K
BB-WSD2M3101P2K
BB-WSD2M3101R100
MECHANICAL DIAGRAM
Units = [Millimeters] Inches
Advantech B+B SmartWorx, 707 Dayton Road, PO Box 1040 Ottawa, IL 61350 USA (800)346-3119/Toll Free | orders@advantech-bb.com | support@advantech-bb.com
Wzzard™ Mesh Wireless Sensors
– for Industrial Applications
BB-WSD2x series
SENSOR INTERFACE SPECIFICATIONS
DIGITAL INPUTS
Voltage Range
VIL
VIH
Pull-up Current
Type
Isolation
RATE/FREQUENCY INPUTS
Frequency
COUNTER INPUT
Counter Inputs
Channels
ANALOG INPUTS
Analog Inputs
Input Range
Resolution
Input Load Resistance
Accuracy Variance
THERMOCOUPLE INPUT
Types Supported
Accuracy
0-48 VDC
0.4 V, maximum
2.5 V, minimum
65 uA
Sinking input (NPN)
None
Performs a 1 second measurement at each measurement/publish interval
Digital input frequency: 1 - 1KHz (accuracy +/- 1 Hz)
Uses falling edge or rising edge – based on Invert Enabled Setting
1
Actively counts either falling edge (Invert Enabled) or rising edge (Invert Disabled)
Can use a multiplier to convert to a unit type or count
Shared with digital inputs
Rolls over at 999999.9
2 or 3 (model dependent)
0-10 VDC, 0-20 mA (software selectable)
0.3 mV/1.3 uA
59 K Ohms
+/-25mV +/-0.05 mA
J, K, N, R, S, T, B, E
THERMOCOUPLE
Type B
Type E
Type J
Type K
Type N
Type R
Type S
Type T
Resolution
Accuracy Variance
THERMISTOR INPUT
Type Supported
Temperature Range
Resolution
Accuracy
Accuracy Variance
DIGITAL OUTPUTS
Voltage Range
Output Type
Output Current
Protection
Isolation
Temperature
Range
+95 to +1798 °C
-200 to +1000 °C
-210 to +1200 °C
-200 to +1372 °C
-200 to +1300 °C
-50 to +1768 °C
-50 to +1768 °C
-200 to +400 °C
Ambient
Temperature
Worst Case
RSS Error
Probe Error
B Type @ +25 °C
9.4 °C
0.5% of T, 0.25% of T
B Type @ -40 to +85 °C
47.1 °C
0.5% of T, 0.25% of T
C Type @ +25 °C
1.4 °C
1.7 °C, 1 °C
C Type @ -40 to +85 °C
5.2 °C
1.7 °C, 1 °C
J Type @ +25 °C
1.5 °C
2.2 °C, 1.1 °C
J Type @ -40 to +85 °C
5.9 °C
2.2 °C, 1.1 °C
K Type @ +25 °C
1.8 °C
2.2 °C, 1.1 °C
K Type @ -40 to +85 °C
7.3 °C
2.2 °C, 1.1 °C
N Type @ +25 °C
2.3 °C
2.2 °C, 1.1 °C
N Type @ -40 to +85 °C
10.3 °C
2.2 °C, 1.1 °C
R Type @ +25 °C
5.4 °C
1.5 °C, 0.6 °C
R Type @ -40 to +85 °C
26.0 °C
1.5 °C, 0.6 °C
S Type @ +25 °C
6.7 °C
1.5 °C, 0.6 °C
S Type @ -40 to +85 °C
33.0 °C
1.5 °C, 0.6 °C
T Type @ +25 °C
1.7 °C
1 °C, 0.5 °C
T Type @ -40 to +85 °C
7.2 °C
1 °C, 0.5 °C
0.0078 °C
0.20% of full-scale reading (0.25%, maximum)
10K NTC
-40 to +85 °C
0.01 °C
THERMISTOR
Typ. Error
Worst Case Error
853 ppm (0.1 °C)
4103 ppm
Maximum +/- 0.5 °C over -40 to +85 °C temperature range
Worst Case
RSS Error
2101 ppm
Probe Error
n/a
0-30 VDC
Open drain
Not to be less than 100 mA
Current limit protection
None
Advantech B+B SmartWorx, 707 Dayton Road, PO Box 1040 Ottawa, IL 61350 USA (800)346-3119/Toll Free | orders@advantech-bb.com | support@advantech-bb.com
Wzzard™ Mesh Wireless Sensors
– for Industrial Applications
BB-WSD2x series
INTEGRATED SENSORS
TEMPERATURE
Offset
Slope Error
CONDITIONS
Temperature Offset Error @ 25 °C
-
SMARTMESH IP 802.15.4E RADIO SPECIFICATIONS
PARAMETER
Frequency Band
Number of Channels
Channel Separation
Channel Clear Frequency
Modulation
Raw Data Rate
Range
Receiver Sensitivity
Output Power
CONDITIONS
MINIMUM
TYPICAL
+/- 0.25
+/- 0.033
TYPICAL
UNITS
°C
°C / °C
MINIMUM
2.400
TYPICAL
MAXIMUM
2.4835
UNITS
GHz
Where k = 11 to 25, as defined by IEEE 802.4.15
IEEE 802.15.4 Direct Sequence Spread Spectrum (DSSS)
25 °C, 50% RH, +2dBi Omni-Directional Antenna, Antenna 2m above ground
Indoor
Outdoor
Packet Data Error Rate (PER) = 1%
P.E.R. = 50%
Delivered to a 50 Ω load
15
5
2405 + 5*(k-11)
MHz
MHz
250
kbps
100
300
m
m
dBm
dBm
dBm
-93
-95
8
THIONYL CHLORIDE LITHIUM BATTERIES (2 supplied with product)
CHARACTERISTICS
Temperature Range
Nominal Capacity
Nominal Voltage
Diameter
Height
CONDITIONS
-40 to +85 °C
2.4 Ah
3.6 V
14.5mm
50.5mm
*Potential Hazard: Do not recharge, crush, disassemble or heat above 100 °C (212 °F).
APPROVALS, DIRECTIVES, STANDARDS (WSD2M31010, WSD2C21150, WSD2C31010)
CE - DIRECTIVES
2014/35/EU
2014/53/EU
2011/65/EU
2012/19/EU
CE - EMC
ETSI EN 300 328 v2.1.1
ETSI EN 301 489-1 v2.1.1
ETSI EN 301 489-17 v3.2.0
EN 55032+AC, Class A
EN 55024
CE - SAFETY
EN/IEC 61010-1 (3rd ed.)
EN/IEC 61010-2-201 (1st ed.)
CE - RF EXPOSURE
EN 62479
Low Voltage Directive (LVD)
Radio Equipment Directive (RED)
Reduction of Hazardous Substances Directive (RoHS)
Waste Electrical and Electronic Equipment Directive (WEEE)
EMC & Radio Spectrum Matters (ERM)
Wideband Transmission Systems, 2.4 GHz ISM Band
Applied in accordance with the specific requirements of: EMC and Radio Spectrum Matters: Broadband Data Systems
Information Technology Equipment (ITE) - RF Emissions
Information Technology Equipment (ITE) - Immunity Characteristics - Limits and Methods of Measurement
Safety requirements for electrical equipment for measurement, control, and laboratory use (general requirements).
Particular requirements for control equipment
Assessment of compliance of low power electronics and electrical equipment with basic restrictions related to human exposure to electromagnetic
fields (10 MHz to 300 GHz)
ENVIRONMENTAL
IEC 60068-2-6
Sine Vibration: 4G, 10-500 Hz, 0.06 in. displacement
IEC 60068-2-27
Mechanical Shock: 50G, 11ms, 18 pulses
FCC, IC
FCC Part 15 Class A, FCC Part 15.247
ICES-003
ITE Emissions for Canada
UL (All models w/ mounting ear installation; M12 model indoors only.)
UL/CSA Class 1/Division 2, Groups A, B, C, D (Conduit Models Only)
Advantech B+B SmartWorx, 707 Dayton Road, PO Box 1040 Ottawa, IL 61350 USA (800)346-3119/Toll Free | orders@advantech-bb.com | support@advantech-bb.com