OP10 HMI
The TECO OP10 monochrome HMI offers a simple but
powerful user interface for the SG2 (Ver 3) programmable
Logic Relay. Monitor data registers in real time, change
parameters, perform switching functions, list alarms, and
transfer data between networked SG2’s*.
Description
OP10
4.3" Monochrome Graphic Panel, 192 x 64 pixels, 4 Function Keys, Numeric
Keypad, 2 serial ports, 24VDC input power
Price
OP10-PL01
Cable (9-pin Serial, PC to 9-pin Serial, OP10)
SG2-PL01
SG2 to OP10 Communication Cable
SG2-Software
SG2 & OP10 Programming S/W. Available on CD or
FREE via download.
General Specifications
• 192 x 64 pixel display
• 24-key keypad
• Two serial ports:
– COM1 supports programming and
point-to-point communications
– RS485 supports multi-drop
networks
• Supports Modbus RTU
• Password protection
• Import bitmaps
• Offline program simulation
• Bar graphs, trend charts, alarm
logging
!
EW
N
Power
DC24V, -15% ~ +10%
Current Consumption
80mA Max
Approvals
UL, CE
Communication Interface
COM1: (9-pin, D-SUB, female) RS-232/422; RS485: terminal screws
Environmental Rating
IP65 (front of panel)
Maximum Devices
8 without repeater; 255 with repeater
Dimensions
179.5 x 101.5 x 33mm (7.07 x 4.00 x 1.30”)
Weight
460g (~1 lb)
Environmental
Programming Software
Program the OP10 using simple fill-in-the-blank object windows.
Establish network links to remote devices. Create dynamic text, trend
charts, bargraphs, alarm logs, and more. View and verify your program
in simulation mode. Download software free at:
www.bb-elec.com/bb-elec/software/PLC/OP10-PCLINKV2.1setup.exe
Dynamic Text
Operating Temperature
0°C ~ 55°C (32°F ~ 131°F)
Storage Temperature
-40°C ~ 70°C (-40°F ~ 158°F)
Relative Humidity
10% ~ 95%, non-condensing
Vibration
1.75mm displacement, 5 - 9Hz
Impact
15G, 11ms, vertical from X, Y, Z directions
Dimensions
101.5mm (4.00”)
FRE E
Part Number
5.5mm
(0.22”)
179.5mm (7.07”)
33mm
(1.30”)
Trending
Cutout
163.8mm (6.45”)
85.8mm
(3.38”)
Bar Graphs
Simulation
Communication with one SG2 via programming port
SG2-PL01
Simple Setup
Multi-drop Modbus communications over RS485 network
*
*SG2 must be V-series to communicate on RS485.
International Headquarters: 70 7 D a yto n R oad P O B ox 1040 O ttaw a, IL 613 50 U S A
815 -433 -5100 F ax 433 -5104 www.bb-elec.com orders@bb-elec.com support@bb-elec.com
European Headquarters: W estlink C om m ercial P ark O ranm ore C o. G alw a y Ireland
+ 353 91 79244 4 F ax + 3 53 91 79 2445 www.bb-europe.com orders@bb-europe.com support@bb-europe.com
很抱歉,暂时无法提供与“OP10-PL01”相匹配的价格&库存,您可以联系我们找货
免费人工找货