AMES150-NZ
AC-DC Converter
Click to
ORDER
AMES150-NZ
samples
The new AMES150-NZ is a brand-new AC/DC converter that offers much greater cost
effectiveness due to material normalization and production automation also leading
to improved reliability and performance. Offering a commercial input voltage range of
85-264VAC and an output voltage range from 12-48V, this series will offer many
benefits to your new system design.
This new series offers great operating temperatures, from -30°C to 70°C also features
an isolation of 4000VAC for improved reliability and system safety. Furthermore, a
higher MTBF of 300,000h, output short circuit protection (OSCP), output over-current
protection (OCP), output over-voltage protection (OVP) and over-temperature
protection (OTP) come standard with the series.
The AMES150-NZ is perfect for street lighting controls, grid power, LED,
instrumentation, industrial controls, communication, and civil applications.
Enclosed
Summary
Features
•
•
•
•
•
•
•
•
•
Universal Input: 85 - 264VAC/120 - 373VDC
Operating Temp: -30 °C to +70 °C
High isolation voltage: Up to 4000VAC
Low ripple & noise, 200mV(p-p) max.
Output short circuit, over-current, over-voltage
and over temperature protection
Regulated Output
Optional conformal coating
Surge immunity: 300VAC for 5s
AMES150-NZ
528
48
4000
250
125
125
158.4
150
264
70
12
45
1000
85
0
3.3
1
Input voltage Output voltage
(VAC)
(V)
Isolation
(VAC)
Power
(W)
-30
-40
-25
Temp. range
(℃)
Derating
(℃)
-40
Applications
Training
Press Release
Coming Soon!
Power Grid
Product Training Video
(click to open)
F 052e R4
REV:02/21/A
Industrial
Telecom
Instrumentation
Application Notes
www.Aimtec.com
1
AMES150-NZ
AC-DC Converter
Models & Specifications
Single Output
Model
Input Voltage
(VAC/Hz)
Input
Voltage
(VDC)
Output Output Voltage
Max Output
Voltage
Adjustable
Wattage (W)
(V)
Range (V)
Output
Current
max (A)
Maximum
capacitive
load (µF)
Efficiency
@230VAC
(%)
AMES150-12SNZ
85-264/47-63
120-373
150
12
10.2-13.8
12.5
10000
86
AMES150-15SNZ
85-264/47-63
120-373
150
15
13.5 -18
10
6000
87
AMES150-24SNZ
85-264/47-63
120-373
156
24
21.6 - 28.8
6.5
2400
88
AMES150-36SNZ
85-264/47-63
120-373
154.8
36
32.4 - 39.6
4.3
1200
88
AMES150-48SNZ
85-264/47-63
120-373
158.4
48
43.2 -52.8
3.3
600
89
Add suffix “-P” for optional terminal protective cover (ex. AMES150-12SNZ-P is terminal with protective cover version) or suffix “-Q” for optional
conformal coating (ex. AMES150-12SNZ-Q is conformal coating version).
Input Specifications
Parameters
Input current
Inrush current
Leakage current
Conditions
115VAC
230VAC
115VAC, Cold start
230VAC, Cold start
240VAC
Typical
Maximum
Units
4
2
0.75
A
A
A
A
mA
Maximum
Units
30
60
Output Specifications
Parameters
Conditions
Typical
Voltage accuracy
Line regulation
Load regulation
Full load
±1
%
Full load
±0.5
%
0-100% load
±0.5
%
12V,15V output
150
mV p-p
Ripple & Noise*
24V,36V,48V output
200
mV p-p
115VAC
≥8
ms
Hold up time
230VAC
≥ 16
ms
* Ripple and Noise are measured at 20MHz bandwidth with a 47μF electrolytic capacitor and a 0.1μF ceramic capacitor. Please refer to the
application note for specific details.
Isolation Specifications
Parameters
Tested I/O voltage
Tested Input to GND voltage
Tested Output to GND voltage
Resistance (I/O, I/O to GND)
F 052e R4
REV:02/21/A
Conditions
60 sec, leakage current < 10mA
60 sec, leakage current < 10mA
60 sec, leakage current < 10mA
500VDC
www.Aimtec.com
Typical
Rated
Units
4000
2000
1250
50
VAC
VAC
VAC
MΩ
2
AMES150-NZ
AC-DC Converter
General Specifications
Parameters
Safety class
Switching Frequency
Over Current protection
Over voltage protection
Over temperature protection
Short circuit protection
Operating temperature
Storage temperature
No-load power consumption
Power derating
Ambient temperature derating
Temperature coefficient
Cooling
Conditions
Typical
Maximum
Units
Class I
65
Auto recovery
≥ 110
Output voltage turn off, Manual recovery, 12V output
Output voltage turn off, Manual recovery, 15V output
Output voltage turn off, Manual recovery, 24V output
Output voltage turn off, Manual recovery, 36V output
Output voltage turn off, Manual recovery, 48V output
Output voltage turn off, Auto recovery
Hiccup, Continuous, Auto recovery, Recover time < 5 sec
See derating graph
-30 to +70
-40 to +85
150
16.2
21.75
33.6
48.6
60
0.5
-30 °C to -25 °C, 85VAC ~ 100VAC
45 °C to 70 °C, 12V output
50 °C to 70 °C, 15V,24V,36V,48V output
85VAC ~ 100VAC
Operating altitude > 2000m
5
2
2.5
1.33
5
±0.03
KHz
% of Iout
VDC
VDC
VDC
VDC
VDC
°C
°C
W
% / °C
% / °C
% / °C
% / VAC
°C / 1000m
% / °C
Free air convection
Non-condensing, Storage
≥ 10
95
% RH
Humidity
Non-condensing, Operating
≥ 20
90
% RH
Case material
Metal (1100 Aluminum, SGCC)
Weight
410
g
Dimensions (L x W x H)
6.26 x 3.82 x 1.18inch (159.0 x 97.0 x 30.0mm)
MTBF
> 300 000 hrs (MIL-HDBK -217F, t=+25oC)
NOTE: All specifications in this datasheet are measured at an ambient temperature of 25°C, humidity