IEC Load Switches
Bulletin 194E
125 Amps to 315 Amps Features
• • • • • • • • • • At-Motor Disconnect Switch 125, 160, 250, 315 A Versions of Inductive Load-Rated Switches IP65/Type 1/3/3R/12 Operating Handles IP2LX Finger-Safe Terminals 3- and 4-Pole Versions Front/Door or DIN/Base Mounting Configurations OFF-ON Configurations Box Lug and Bolt-on Terminals Available Switches Include Operating Shaft Suitable as Motor Disconnect
Description
Bulletin 194E load switches are designed for use in North America as local motor isolation and for IEC disconnect switch applications outside of North America. Available in 3- and 4-pole versions with add-on grounding and neutral terminals and auxiliary contacts, Bulletin 194Es use similar operating handles as the Bulletin 194L Control and Load Switches. Bulletin 194E switches are offered in two mounting styles, Front/ Door and Base/DIN configurations, for a variety of installations. Switch body styles for Bulletin 194E base-mounted switches include standard interlock shaft; Bulletin 194E front-mounted switches include standard shaft. Two-position OFF-ON switch is used to connect or disconnect a variety of inductive loads, including solenoids, actuators, valves, magnetic starters, relays, and motors up to 100 HP.
Conformity to Standards • IEC 207 • IEC 947-1 • IEC 947-3 low-voltage switchgear and control gear part 3: switches, disconnecters, switch-disconnecters and fusecombination units. CE • UL 508: Industrial Control Equipment. CUL Approvals • UL listed (Box Lug Version) • UR recognized (Bolt-on Version) • CUL listed (Box Lug Version) • CUR recognized (Bolt-on Version) • Meets IEC, VDE and BS standard requirements • IEC/CE marked for all applicable directives (per EN 60947-3) Your order must include: • Catalogue Number of switch body. • Catalogue Number of actuator. • If required, Catalogue Number of accessories.
10-25
IEC Load Switches
Bulletin 194E
125 Amps to 315 Amps Product Selection
OFF-ON Base-Mounted Switch — with Box Lugs — UL Listed
Switch Body Function Sw. Angle
ON 1
No. of Poles
OFF/0 0 0 0
ON/1 X X X
Max. Load (Amps) 125 160 250 315 125
AC23 Rated kw 690V AC 50 Hz 37 37 45 45 37 37 45 45
Hp @ 480V AC 60 Hz 3 ∅ 60 60 75 100 60 60 75 100
Catalogue Number 194E-A125-1753 194E-A160-1753 194E-A250-1753 194E-A315-1753 194E-A125-1754 194E-A160-1754 194E-A250-1754 194E-A315-1754
3
OFF 0 90
O
ON 1
4
OFF 0 90
O
0 0 0 0
X X X X
160 250 315
OFF-ON Base-Mounted Switch — with Bolt-on Wiring — UR Recognized
Switch Body Function Sw. Angle
ON 1
No. of Poles
OFF/0 0 0 0
ON/1 X X X
Max. Load (Amps) 125 160 250 315
AC23 Rated kw 690V AC 50 Hz 37 37 45 45 37 37 45 45
Hp @ 480V AC 60 Hz 3 ∅ 60 60 75 100 60 60 75 100
Catalogue Number 194E-B125-1753 194E-B160-1753 194E-B250-1753 194E-B315-1753 194E-B125-1754 194E-B160-1754 194E-B250-1754 194E-B315-1754
3
OFF 0 90
O
ON 1
125 4 0 0 0 0 X X X X 160 250 315
OFF 0
90
O
OFF-ON Front-Mounted Switch — with Box Lugs — UL-Listed
Switch Body Function Sw. Angle
ON 1
No. of Poles 1 2 3
OFF/0 0 0 0
ON/1 X X X
Max. Load (Amps) 125 160 250 315 125
AC23 Rated kw 690V AC 50 Hz 37 37 45 45 37 37 45 45
Hp @ 480V AC 60 Hz 3 ∅ 60 60 75 100 60 60 75 100
Catalogue Number 194E-E125-1753 194E-E160-1753 194E-E250-1753 194E-E315-1753 194E-E125-1754 194E-E160-1754 194E-E250-1754 194E-E315-1754
OFF 0
90
O
ON 1
OFF 0
90
O
1 2 3 4
0 0 0 0
X X X X
160 250 315
OFF-ON Front-Mounted Switch — with Bolt-on Wiring — UR-Recognized
Switch Body Function Sw. Angle
ON 1
No. of Poles 1 2
OFF/0 0 0 0
ON/1 X X X
Max. Load (Amps) 125 160 250 315
AC23 Rated kw 690V AC 50 Hz 37 37 45 45 37 37 45 45
Hp @ 480V AC 60 Hz 3 ∅ 60 60 75 100 60 60 75 100
Catalogue Number 194E-F125-1753 194E-F160-1753 194E-F250-1753 194E-F315-1753 194E-F125-1754 194E-F160-1754 194E-F250-1754 194E-F315-1754
OFF 0
90
O
3
ON 1
125 1 2 3 4 0 0 0 0 X X X X 160 250 315
OFF 0
90
O
10-26
IEC Load Switches
Bulletin 194E
125 Amps to 315 Amps Accessories
Handles
Actuators 194E — 125…315 A Actuators with Screw Fixing (Includes Legend Plate and Control Knob) Use with Catalogue Number
Rating
Colour
Legend Plate Size 88 mm x 88 mm 3-15/32 in. x 3-15/32 in. 130 mm x 130 mm 5-1/8 in. x 5-1/8 in. 88 mm x 88 mm 3-15/32 in. x 3-15/32 in.
Legend Marking
Catalogue Number 194E-HE8A-175 194E-HE13A-175
Black Type A
194E-125…315A 194E-HE8I-175
ON 1
Red/Yellow Type I IP65 Type 3/3R/12 Black Type G
130 mm x 130 mm 5-1/8 in. x 5-1/8 in. 90 mm x 90 mm 3-35/64 in. x 3-35/64 in. 135 mm x 135 mm 5-5/16 in. x 5-5/16 in. 90 mm x 90 mm 3-35/64 in. x 3-35/64 in. 194E-125…315A
OFF 0
194E-HE13I-175 194E-HE8G-175 194E-HE13G-175 194E-HE8N-175 194E-HE13N-175
90
O
Red/Yellow Type N Auxiliary Contacts—2 N.O./1 N.C.
135 mm x 135 mm 5-5/16 in. x 5-5/16 in. Use with 194E-A125-160 194E-B125-160 194E-A250-315 194E-B250-315 194E-E125-160 194E-F125-160 194E-E250-315 194E-F250-315 Use with 194E-A135-160 194E-E135-160 194E-A250-315 194E-E250-315 194E-B135-160 194E-F135-160 194E-B250 194E-F250 194E-B315 194E-F315 Use with 194E-A125-160 194E-E125-160 194E-A250-315 194E-E250-315 194E-B125-160 194E-F125-160 194E-B250 194E-F250 194E-B315 194E-F315
Catalogue Number 194E-AB-P21-160 194E-AB-P21-315 194E-EF-P21-160 194E-EF-P21-315 Catalogue Number 194E-AE160-PE 194E-AE315-PE 194E-BF160-PE 194E-BF250-PE 194E-BF315-PE Catalogue Number 194E-AE160-TN 194E-AE315-TN 194E-BF160-TN 194E-BF250-TN 194E-BF315-TN
Earthing/Grounding Terminal
PE
PE
Neutral Terminal
N
N
10-27
IEC Load Switches
Bulletin 194E
125 Amps to 315 Amps Accessories
Handles (continued)
Terminal Cover 194E-A125-160 194E-E125-160 194E-A250-315 194E-E250-315 194E-B125-160 194E-F125-160 194E-B250-315 194E-F250-315 Use with 2 covers per pole required 2 covers per pole required 2 covers per pole required 2 covers per pole required Catalogue Number 194E-AE125-C1 194E-AE250-C1 194E-BF125-C1 194E-BF250-C1
Legend
Additional Name Plate and Frame Colour Legend Size Use with Legend Marking MAIN SWITCH HAUPTSCHALTER INTERR. PRINCIPALE INTERR. PRINCIPAUX INTERR. PRINCIPAL HUVUDBRYTARE WAHLSCHALTER EMERGENCY OFF Catalogue Number 194L-G3515A 194L-G3515B 194L-G3515C 194L-G3515D 194L-G3515E 194L-G3515F 194L-G3515G 194L-G3515H
Gray/Black
19.2 mm x 49 mm 3/4 in. x 1-59/64 in.
10 per package Red/ Yellow
88 mm x 88 mm 90 mm x 90 mm 130 mm x 130 mm 135 mm x 135 mm legend frames (Size 8,13)
10-28
IEC Load Switches
Bulletin 194E
125 Amps to 315 Amps Specifications
IEC Performance Data for 194E
Rated insulation voltage Ui: ➊ Rated impulse withstand voltage Uimp Test voltage 1 min Rated voltage Ue ➊➋ Rated frequency Rated thermal current Ith open Rated thermal current Ithe enclosed Rated current Ie AC-1 / Non inductive or slightly induc. load Switching of resistive loads with slight AC-21A overload Rated power Pe AC-23A Occasional switching of motor and other highly inductive loads Squirrel-cage motors: starting and stopping of running motors 230V 400V 690V 230V 400V 690V 400/415V [A] 125 160 250 315 [V] [kV] [kV] [V] [Hz] [A] [A] 194E-125 1000 8 3.5 1000 50/60 125 125 194E-160 1000 8 3.5 1000 50/60 160 160 194E-250 1000 8 3.5 1000 50/60 250 250 194-315 1000 8 3.5 1000 50/60 315 315
AC-3
Conditional rated short-circuit current Max. fuse rating of circuit (type g, G) Rated short-time current Icw 1S Rated breaking capacity AC-23A (cos ϕ 0.45)
230V 400V 690V
[kW] [kW] [kW] [kW] [kW] [kW] [kA] [A] [A] [A] [A] [A]
30 45 37 22 37 30 30 125 2500 800 750 340
30 55 37 30 45 37 30 160 3000 900 850 340
37 90 45 37 55 45 30 250 4600 1600 1380 400
55 110 45 45 75 45 30 315 5800 1800 1650 400
➊ Valid for line with grounded common neutral termination, over voltage category III, pollution degree 3. Other values on request. ➋ Not suitable for load-switching applications (AC-20A) above 690V.
10-29
IEC Load Switches
Bulletin 194E
125 Amps to 315 Amps Specifications
IEC Performance Data for 194E (continued)
DC Switching Capacity 194E-125 Rated current Ie DC-21A For resistive loads T≤1 ms Rated voltage [V] 60 110 220 Rated voltage [V] 110 220 440 Rated voltage [V] 24 48 60 110 220 Rated voltage [V] 24 48 60 110 220 No. Poles in series 3 3 3 No. Poles in series 4 4 4 No. Poles in series 4 4 4 4 4 No. Poles in series 4 4 4 4 4 [A] [A] [A] [A] [A] [A] 125 110 45 125 80 16 160 140 55 160 100 20 250 220 85 250 150 32 315 280 110 315 200 40 194E-160 194E-250 194E-315
Rated power Pe DC-22A, DC-3 For Inductive loads T≤2.5 ms [kW] [kW] [kW] [kW] [kW] 3 6 7.5 10 4.5 3.8 7.5 9.5 12.5 5.5 6 12 15 20 8 7.5 15 19 25 10
Rated Power Pe DC-23A, DC-5 For Inductive loads T≤15 ms [kW] [kW] [kW] [kW] [kW] 3 6 7.5 8.8 2.5 3.8 7.5 9.5 11 3.5 6 12 15 17.5 5.5 7.5 15 19 22 7
UL CSA Performance Data for 194E
Rated Insulation Voltage Rated voltage Continuous current Ampere rating for general use Heavy Pilot Duty Standard Duty Motor rating 60Hz 120V, 1 P 240V, 1 P 1-phase (2-poles) 480V, 1 P 600V, 1 P 120V, 3 P 240V, 3 P 3-Phase 480V, 3 P 600V, 3 P [V] [V] [A] [A] [AC] [DC] [FLA] [HP] [FLA] [HP] [FLA] [HP] [FLA] [HP] [FLA] [HP] [FLA] [HP] [FLA] [HP] [FLA] [HP] 194E-125 600 600 150 150 194E-160 600 600 200 200 194E-250 600 600 250 250 194E-315 600 600 300 300
80 7.5 88 20 78 35 62 35 84 15 8 30 77 60 62 60
100 10 110 25 88 40 70 40 108 20 104 40 77 60 62 60
135 15 136 30 99 45 86 50 160 30 154 60 96 75 77 75
180 20 155 35 108 50 104 60 208 40 192 75 124 100 99 100
10-30
IEC Load Switches
Bulletin 194E
125 Amps to 315 Amps Specifications
Mechanical Data
Actuators Protection class according to IEC 529 Front side Front unit Box lugs ➊ Bolt-on straight version ➊ bent version Mechanical life Box lugs — max. wire gauges Terminal sizes according to IEC 947-1 Fine strands, 1 conductor Rigid wire, 1 conductor Wire gauges according to UL / CSA Gauge Max. Min. Max. Min. Max. Min. ➊ When provided with terminal covers. [Million operations] No. mm2 mm2 mm
2
194E-125 IP65 — IP65 IP20 IP20 — 0.1 — B11 70 16 95 10 3/0 — 8
194E-160 IP65 — IP65 IP20 IP20 — 0.1 — B11 70 16 95 10 3/0 — 8
194E-250 IP65 — IP65 IP20 IP20 — 0.075 — B14 150 25 185 16 — 350 4
194E-315 IP65 — IP65 IP20 IP20 — 0.075 — B14 150 25 185 16 — 350 4
mm2 AWG MCM AWG
Approvals
UL-Listed (marked w/UL) A A A A — — — — Z Z Z UR-Recognized (marked w/UR) — — — — A A A A Z Z Z UL-Listed for Canada (marked with cUL) A A A A — — — — Z Z Z UR-Recognized for Canada (marked w/cUR) — — — — A A A A Z Z Z
Catalogue No. or Designation 194E-A125 194E-E125 194E-A160 194E-E160 194E-A250 194E-E250 194E-A315 194E-E315 194E-B125 194E-F125 194E-B160 194E-F160 194E-B250 194E-F250 194E-B315 194E-F315 Aux. switch blocks Ground terminal Neutral terminal
CE A A A A A A A A Z Z Z
A = approved or test passed Z = accessories are covered by the approval for the switch
10-31
IEC Load Switches
Bulletin 194E
125 Amps to 315 Amps Approximate Dimensions—mm (inches)
Dimensions are not intended to be used for manufacturing purposes. Front-Installation Box Lugs, 3- and 4-Pole
max. E mm 2
I
A F G H
C B D
Switch Body 194E-E [A] 125 160 250 315
A 91 (3-19/32) 91 (3-19/32) 103 (4-3/64) 103 (4-3/64)
B 112 (4-13/32) 112 (4-13/32) 145 (5-23/32) 145 (5-23/32)
C 36 (1-13/32) 36 (1-13/32) 44 (1-23/32) 44 (1-23/32)
D 38 (1-1/2) 38 (1-1/2) 52.5 (2-1/16) 52.5 (2-1/16)
E 95 (3-23/64) 95 (3-23/64) 185 (7-9/32) 185 (7-9/32)
F 88 (3-7/16) 88 (3-7/16) 88 (3-7/16) 88 (3-7/16)
G 68 (2-5/8) 68 (2-5/8) 68 (2-5/8) 68 (2-5/8)
H 108 (4-1/4) 108 (4-1/4) 120 (4-11/16) 120 (4-11/16)
I M5 (3/16) M5 (3/16) M5 (3/16) M5 (3/16)
Front-Installation Bolt-on Terminals, 3- and 4-Pole
O F G P
D A H I N M
E
L B C
Switch Body 194E-F [A] A 91 125 (3-19/32) 91 160 (3-19/32) 103 250 (4-3/64) 103 315 (4-3/64)
B 112 (4-3/32) 112 (4-3/32) 145 (5-23/32) 145 (5-23/32)
C 38 (1-1/2) 38 (1-1/2) 52.5 (1-22/32) 52.5 (1-22/32)
D 65.5 (2-9/16) 65.5 (2-9/16) 60.4 (2-3/8) 60.4 (2-3/8)
E 3 (1/8) 3 (1/8) 4 (5/32) 4 (5/32)
F 2 (3/32) 2 (3/32) 2 (3/32) 2 (3/32)
G 36 (1-13/32) 36 (1-13/32) 44 (1-23/32) 52 (2-1/16)
H 88 (3-7/16) 88 (3-7/16) 88 (3-7/16) 88 (3-7/16)
I 68 (2-5/8) 68 (2-5/8) 68 (2-5/8) 68 (2-5/8)
L 10 (13/32) 10 (13/32) 13 (1/2) 13 (1/2)
M 90 (3-17/32) 90 (3-17/32) 100 (3-15/16) 100 (3-15/16)
N 64 (2-17/32) 64 (2-17/32) 70 (2-3/4) 70 (2-3/4)
O M5 (3/16) M5 (3/16) M5 (3/16) M5 (3/16)
P M10 (3/8) M10 (3/8) M12 (15/32) M12 (15/32)
10-32
IEC Load Switches
Bulletin 194E
125 Amps to 315 Amps Approximate Dimensions—mm (inches)
Dimensions are not intended to be used for manufacturing purposes. Base-Mounting Box Lugs, 3- and 4-Pole
E L
max. D mm 2
A F H I
B
C
E
G
Switch Body 194E-A [A] A 91 125 (3-19/32) 91 160 (3-19/32) 98 250 (3-27/32) 98 315 (3-27/32)
B 112 (4-13/32) 112 (4-13/32) 145 (5-23/32) 145 (5-23/32)
C 38 (1-1/2) 38 (1-1/2) 52.5 (1-23/32) 52.5 (1-23/32)
D 95 (3-23/64) 95 (3-23/64) 185 (7-9/32) 185 (7-9/32)
E 2 (3/32) 2 (3/32) 2 (3/32) 2 (3/32)
F 118 (4-5/8) 118 (4-5/8) 140 (5-1/2) 140 (5-1/2)
G 6.4 (1/4) 6.4 (1/4) 6.4 (1/4) 6.4 (1/4)
H 108 (4-1/4) 108 (4-1/4) 126 (4-15/16) 126 (4-15/16)
I 64 (2-17/32) 64 (2-17/32) 70 (2-3/4) 70 (2-3/4)
L 36 (1-13/32) 36 (1-13/32) 44 (2-1/16) 44 (2-1/16)
Base-Mounting Bolt-on Terminals, 3- and 4-Pole
Q F P O N
E A G LM
D
F B C H I
Switch Body 194E-B [A] A B C 91 112 38 125 (3-19/32) (4-13/32) (1-1/2) 91 112 38 160 (3-19/32) (4-13/32) (1-1/2) 98 145 52.5 250 (3-27/64) (5-23/32) (1-23/32) 98 145 52.5 315 (3-27/64) (5-23/32) (1-23/32)
D 36.5 (1-7/16) 36.5 (1-7/16) 38.6 (1-1/2) 38.6 (1-1/2)
E 3 (1/8) 3 (1/8) 4 (5/32) 4 (5/32)
F 2 (3/32) 2 (3/32) 2 (3/32) 2 (3/32)
G 76 (3) 76 (3) 80 (3-1/8) 80 (3-1/8)
H I L M N 36 20 90 64 10 (1-13/32) (3/4) (3-17/32) (2-17/32) (13/32) 36 20 90 64 10 (1-13/32) (3/4) (3-17/32) (2-17/32) (13/32) 44 26 100 70 13 (1-23/32) (1-1/64) (3-15/16) (2-3/4) (1/2) 44 26 100 70 13 (1-23/32) (1-1/64) (3-15/16) (2-3/4) (1/2)
O M10 (3/8) M10 (3/8) M12 (15/32) M12 (15/32)
P 36 (1-13/32) 36 (1-13/32) 44 (1-23/32) 52 (2-1/16)
Q 6.4 (1/4) 6.4 (1/4) 6.4 (1/4) 6.4 (1/4)
10-33
IEC Load Switches
Bulletin 194E
125 Amps to 315 Amps Approximate Dimensions—mm (inches)
Dimensions are not intended to be used for manufacturing purposes. Box Ground and Neutral Terminal
Switch Body 194E-F [A] 125 160 250 315
A 37.8 (1-1/2) 37.8 (1-1/2) 52.3 (2-1/16) 52.3 (2-1/16)
B 64 (2-17/32) 64 (2-17/32) 71.1 (2-25/32) 71.1 (2-25/32)
C 108 (4-1/4) 108 (4-1/4) 126 (4-15/16) 126 (4-15/16)
D 37.8 (1-1/2) 37.8 (1-1/2) 52.3 (2-1/16) 52.3 (2-1/16)
E 64 (2-17/32) 64 (2-17/32) 80.6 (3-1/8) 80.6 (3-1/8)
F 108 (4-1/4) 108 (4-1/4) 126 (4-15/16) 126 (4-15/16)
Bolt Ground and Neutral Terminal
FRONT L D B F H N BASE
A
Switch Body 194E-F [A] A 37.8 125 (1-1/2) 37.8 160 (1-1/2) 52.3 250 (2-1/16) 52.3 315 (2-1/16) Auxiliary Contacts
G C
B 64 (2-17/32) 64 (2-17/32) 68 (2-21/32) 68 (2-21/32) C 10 (13/32) 10 (13/32) 13 (1/2) 13 (1/2)
E
D M10 (13/32) M10 (13/32) M12 (15/32) M12 (15/32)
FRONT
I
M
E 90 (3-17/32) 90 (3-17/32) 100 (3-15/16) 100 (3-15/16)
F 3 (1/8) 3 (1/8) 4 (5/32) 4 (5/32)
G 37.8 (1-1/2) 37.8 (1-1/2) 52.3 (2-1/16) 52.3 (2-1/16)
H 64 (2-17/32) 64 (2-17/32) 68 (2-21/32) 68 (2-21/32)
BASE
I 10 (13/32) 10 (13/32) 13 (1/2) 13 (1/2)
L M10 (13/32) M10 (13/32) M12 (15/32) M12 (15/32)
M 90 (3-17/32) 90 (3-17/32) 100 (3-15/16) 100 (3-15/16)
N 3 (1/8) 3 (1/8) 4 (5/32) 4 (5/32)
14 (9/16)
50 (1 31/32)
14 (9/16)
50 (1 31/32)
10-34
IEC Load Switches
Bulletin 194E
125 Amps to 315 Amps Approximate Dimensions—mm (inches)
Dimensions are not intended to be used for manufacturing purposes. Terminal Cover
A
Switch Body 194E-F A 76.2 125 (3) 76.2 160 (3) 88 250 (3-15/32) 88 315 (3-15/32) Door Clutches
L for Standard Shaft
B
B 95 (3-3/4) 95 (3-3/4) 109.5 (4-5/16) 109.5 (4-5/16)
93…199 mm (3-21/32in…7-27/32in)
Shaft must be cut to length at installation.
5.4 mm (7/32)
fl 27 (1-1/16)
88 (3-15/32)
68 (2-11/16) L
10-35
IEC Load Switches
Bulletin 194E
125 Amps to 315 Amps Approximate Dimensions—mm (inches)
Dimensions are not intended to be used for manufacturing purposes. Actuators (Type 194E-HE-8A-8I-8G-8N)
1-4 mm (1/32-1/8) 1-4 mm (1/32-1/8) 68 (2-11/16) fl 5.3 (7/32) 88 x 88 (3-15/16 x 3-15/16) 92 x 92 (1-5/8 x 1-5/8) fl 12 (15/32)
68 (2-11/16)
45 (1-49/64)
49 (1-15/16)
Actuators (Type 194E-HE-13A-13I-13G-13N)
1-4 mm (1/32-1/8) 1-4 mm (1/32-1/8) 68 (2-11/16) fl 5.3 (7/32) 130 x 130 (5-1/8 x 5-1/8)
135 x 135 (5-5/16 x 5-5/16) fl 20 (15/32)
68 (2-11/16)
55 (2-5/32)
68 (2-11/16)
Additional Name Plate Frame and legend snaps on to actuator bezel. Fits size 8 and 13 actuators.
84 (3-5/16) 18 (23/32)
G3515
6.7 (9/32)
10-36
很抱歉,暂时无法提供与“194E-E250-1754”相匹配的价格&库存,您可以联系我们找货
免费人工找货