Bulletin 700-SK
Solid-State Relays
Overview/Product Selection Bulletin 700-SK
• • • • • High Response Speed Models Input Sensor Module to Allow High Voltage 100…240V AC or 12…24V DC Sensor Interface to Low Voltage (Logic) Device Such as a PC Output Module For Typical SSR Applications LED Indicator Input Modules and Output Modules Can Be Used With the 700-HN121 Socket
Table Of Contents
Product Selection . . . . . . . . 58 Accessories . . . . . . . . . . . . 58 Specifications . . . . . . . . . . . 60 Approximate Dimensions . . . . . . . . . . . . . 62
Product Selection
Input/Sensor Module
Input-to-Output Isolation Method LED Indicator Response Speed 10 Hz Photocoupler Yes High-speed (1 kHz) 4…32V DC 0.1…100 mA Logic Level Supply Voltage Supply Current Rated Input Sensor Voltage 100…240V AC 12…24V DC Cat. No. 700-SKICA18 700-SKICZ24 Factory-stocked item (Single Pack) ✔ ✔
Output/SSR Module
Input-to-Output Isolation Method Zero Cross Function Yes No N/A Yes LED Indicator Rated Output (Load) Max. Current and Voltage Range 2 A at 100…240V AC 2 A at 5…48V DC 1.5 A at 48…200V DC 5…24V DC Rated Input Control Voltage Factory-stocked item (Single Pack) ✔ ✔ ✔ ✔
Cat. No. 700-SKOZ2Z25 700-SKON2Z25 700-SKOC2Z25 700-SKOC1Z25
Phototriac Photocoupler
58
Bulletin 700-SK
Solid-State Relays
Accessories
Description Pcs./Pkg. Cat. No. Factory-stocked Item
Screw Terminal Socket — Panel or DIN Rail Mounting Order must be in multiples of ten
10
700-HN121
✔
Cat No. 700-HN121
DIN Rail Mounting Pack Standard 35 x 7.5 mm DIN Rail, 1 meter long, 10 rails per package. Order must be for 10 rails or multiples of 10.
Cat No. 199-DR1
10
199-DR1
✔
Pre-printed identification tags — contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays. Blank identification tags — contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10
700-N40
10
700-N41
59
Bulletin 700-SK
Solid-State Relays
Specifications Input Sensor Module
Input Sensor Ratings Cat, No. 700-SKICZ24 700-SKICA18 Rated Input Voltage 12…24V DC 100…240V AC Operating Voltage Range 6.6…32V DC 60…264V AC Input Current 8 mA max. 15 mA max. Pick-up Voltage 6.6V DC max. 60V AC max. Drop-out Voltage 3.6V DC min. 20V AC min.
Output Logic Ratings Cat. No. 700-SKICZ24 700-SKICA18 Cat. No. Pick-up time Drop-out time Response frequency Output ON voltage drop Leakage current VDRM VCEO (V) Output di/dt (A/uS) Output dv/dt (V/uS) Output I2t (A2S) Output Tj (°C) Max. Insulation resistance Dielectric strength Vibration resistance (max.) Shock resistance Ambient temperature Standards Ambient humidity Weight Operating (max.) Operating Storage 80 (ref. value) — — — 150 100 MΩ min. between input and output 4,000V AC, 50/60 Hz for 1 min. between input and output 10…55 Hz, 1.5 mm double amplitude (10 G) 1,000 m/s2 (100 G) –30…80°C (–22…176°F) with no icing or condensation –30…100°C (–22…212°F) with no icing or condensation UL 508 CSA C22.2 CE, TÜV 45…85% (No condensation) Approx. 18 g Logic Level Supply Voltage 4…32V DC Characteristics 700-SKICA18 20 ms max. 20 ms max. 10 Hz 1.6 V max. 5 µA max. 80 (ref. value) — — — 150 700-SKICZ24 0.1 ms max. 0.1 ms max. 1 kHz Logic Level Supply Current Draw 0.1…100 mA
Output SSR Module
Control/Input Ratings Cat. No. 700-SKOZ2Z25 700-SKON2Z25 700-SKOC2Z25 700-SKOC1Z25 Load/Output Ratings Cat. No. — 700-SKOZ2Z25 700-SKON2Z25 700-SKOC2Z25 700-SKOC1Z25 Rated Load Voltage — 100…240V AC 5…48V DC 48…200V DC Load Voltage Range — 75…264V AC 4…60V DC 40…200V DC Continuous Load Current (Resistive) Min. 0.05 A 0.01 A 0.01 A Max.➌ 2A 2A 1.5 A Max. Inrush Current➋ — 30 A (@50/60 Hz, 1 cycle) 8 A (10 ms) 8 A (10 ms) 5…24V DC 4…32V DC Rated Control Voltage Operating Control Voltage Range Impedance➊ 15 mA max. at 25°C (77°F) 8 mA max. Pick-up Voltage Drop-out Voltage
4V DC max.
1V DC min.
➊ With a constant current input system. SSR impedance varies with a change in input voltage. ➋ If the SSR operation is continuous ON/OFF, this value should be reduced by 50%. Refer to the “Inrush Current Resistivity” graphs on page 61 for more details. ➌ Refer to "Load Current Versus Ambient Temperature Characteristics" graphs on page 61 for additional details.
60
Bulletin 700-SK
Solid-State Relays
Specifications, Continued Output Module, Continued
Characteristics Cat. No. Load Switching Method/Device Pick-up time Drop-out time Response frequency Output ON voltage drop Leakage current VDRM VCEO (V) Output di/dt (A/uS) Output dv/dt (V/uS) Output I2t (A2S) Output Tj (°C) Max. Insulation resistance Dielectric strength Vibration resistance (max.) Shock resistance (max.) Ambient temperature Standards Ambient humidity Weight Operating Operating Storage 600 (ref.value) 30 300 10.4 125 1.5 mA max. 600 (ref.value) 30 300 10.4 125 80 (ref.value) — — — 150 700-SKOZ2Z25 Triac 1/2 of load power source cycle + 1 ms max. 1/2 of load power source cycle + 1 ms max. 20 Hz 1.6 V max. 1 mA max. 400 (ref.value) — — — 150 700-SKON2Z25 700-SKOC2Z25 700-SKOC1Z25 Transistor 1 ms max. 2 ms max. 100 kHz 2.5V max.
100 MΩ min. between input and output 4,000V AC, 50/60 Hz for 1 min. between input and output 10…55 Hz, 1.5 mm double amplitude (10 G) 1,000 m/s2 (100 G) –30…80°C (–22…176°F) with no icing or condensation –30…100°C (–22…212°F) with no icing or condensation UL 508 CSA C22.2, CE TÜV 45…85% (no condensation) Approx. 18 g
Load Current vs. Ambient Temperature Characteristics
For 2 A Versions
Maximum Load Current (A)
2 1.5 1 0.5
˚c
Maximum Load Current (A)
2 1.5 1 0.5
˚c
Inrush Current Resistivity➊
700-SKOZ / SKON 700-SE05
700-SKOC2
700-SKOZ /SKOC1
2000
➊ Inrush current resistivity is the ability of an SSR to withstand a large surge current for a short period of time. Surges are considered non-repetitive (max. repeatability once every 2…5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitive inrush current will damage the SSR.
61
Bulletin 700-SK
Solid-State Relays
Approximate Dimensions
All units are in millimeters unless otherwise indicated. Dimensions are not to be used for manufacturing purposes. Note: The input module (700-SKI) and output module (700-SKO) are compatible with the 700-HN121 socket.
1 5.2 3 0.5
29 max.
Terminal Arrangement/ Internal Connections (Bottom View) (+)
3
4 9.6 17.4
(–)
4.75 1 5
4
Load
13 max. 4 10
28 max.
5 0.5 4.75
7.5
4.7
Input
1 5
(–)
2 20
Bulletin 700-SK
(+)
Application Considerations of Bulletin 700-SK
Connection
For DC load switching, Bulletin 700-SK SSR will operate properly if the load is connected to either the positive or negative SSR load terminal. The load can be connected to either positive or negative output terminals of the SSR.
Protective Element (to extend SSR life)
Since the SSR does not incorporate a surge absorption component, be sure to connect a surge absorption component when using the SSR to control an inductive load. For additional details applying solid-state relays, refer to pub. number 700-AT001A-EN-E, "Solid-State Relay Application Guide." Document available at www.theautomationbookstore.com.