DATA SHEET
DFS 2 063-2/0,03-A HD
sensitive to pulsating and alternating currents Type A, for harsh
environments:
Internetlink
Article number 09144601HD
symbolic image
1ATV
Function
Residual current circuit-breakers (RCCBs) are components for implementing protective measure "Automatic disconnection of the power
supply" as per VDE 0100 part 410 or corresponding international installation regulations. Series DFS 2 devices are compact two-pole
residual current circuit-breakers for single-phase networks. In the standard design, they only take up two module-width units of space.
In spite of the compact dimensions, a number of different tripping currents and characteristics are available at rated currents, depending
on the design, up to 125 A. They also have large two-tier terminals for large conductor cross-sections, a practical multifunctional switch
toggle and can be provided with pre-prepared labels using free-of-charge software. Switches with residual current characteristic A allow
the mains voltage independent detection of sinusoidal AC currents and pulsating DC residual currents. Any possible additional functions
may be voltage-dependent. Devices in the standard design are intended for monitoring circuits with a rated voltage of 230 V/400 V and
a rated frequency of 50 Hz. With an airtight, encapsulated tripping mechanism from a special alloy and the stainless steel latch, residual
current circuit-breakers in HD design are protected, in particular from corrosion, corrosive gases, moisture and extreme temperature
fluctuations.
Features
tripping not dependent on mains and auxiliary voltage, sensitive to AC residual currents and pulsating DC residual currents (type A) ,
compact design for all rated currents, high short-circuit resistance, double-sided two-tier terminals for large conductor cross-section and
busbar, switch position indicator, viewing window for labels, multifunction switch toggle with three positions: "on", "off" and "tripped",
Neutral conductors with standard design left, for two-terminal-pair devices type A/AC/F up to 125 A and type B/B+ up to 80 A; N-right
available at no extra charge.
Mounting
quick fastening to mounting rail, any installation position, supply from any direction
Applications
Power supplies to residential and purpose-built buildings as well as industrial facilities with TN-S, TT and TN-C-S networks. In IT networks,
the residual current circuit-breakers of this series can be set to switch off in the event of a second fault, Excluded is the application in TNC systems and for the protection of installations in which electronic equipment could generate smooth DC currents or residual currents
with frequencies other than 50 Hz. Comprehensive protection is not provided in this case. For these applications we recommend our AC/
DC sensitive residual current circuit-breakers (Type B or B+).
Accessories
Automatic reclosing devices DFA, Clamp covers KA, Information stickers HAS, Auxiliary Switches DHi, Software DBS
Technical Data
Technical Data
Series
Number of poles
Residual current type
Rated current (AC)
Rated residual current I∆n
Short-time delayed
Selective
min. Operating voltage range of
test circuit
2020_01_31
DFS 2 063-2/0,03-A HD
DFS 2 A HD
2
A
63 A
0.03 A
false
false
150 V
doepke_09144601HD_dbl_en.pdf
1/3
Doepke
The experts in residual current protection technology
Technical Data
max. Operating voltage range of
test circuit
Maximum disconnection times
Specification
min. Contact opening
Rated voltage (AC)
Rated current (AC)
Rated short-circuit current
Surge current strength
max. total rated switching
capacity
Rated insulation voltage
Rated impulse withstand voltage
Rated frequency
Current heat loss per current
path
thermal Backup-fuse OCPD
short-circuit backup-fuse SCPD
Back-up fuse type
Neutral conductor position
Protection against direct contact
Connection C1 Maximum
number of conductors per
terminal
Cross section solid
Connecting capacity flexible
Cross section stranded
Tightening torque
Operating position
max. Operating altitude above
MSL
Mechanical endurance
Electrical endurance
Surrounding atmosphere
Storage temperature
Ambient temperature
Climate resistance
Shock resistance
Fatigue limit
Housing type
Mounting type
Housing material
Protection class
sealable
Width
Height
Depth
Installation depth
2020_01_31
DFS 2 063-2/0,03-A HD
250 V
1 · IΔn: ≤ 300 ms; 5 · IΔn: ≤ 40 ms
Load circuit
Load switch contact
4 mm
230 V
63 A
10 kA
0.25 kA
800 A
400 V
4 kV
50 Hz
2.8 W
63 A
100 A
gG
Screw-type terminal top and bottom (Load circuit)
arbitrary
DGUV V3, VDE 0660-514, finger-safe and safe for back-of-hand
2 (conductors of same type and cross-section)
1-wire: 1.5 mm² ... 50 mm²; 2-wire: 1.5 mm² ... 16 mm²
1-wire: 1.5 mm² ... 50 mm²; 2-wire: 1.5 mm² ... 16 mm²
1-wire: 1.5 mm² ... 50 mm²; 2-wire: 1.5 mm² ... 16 mm²
2.5 Nm ... 3 Nm
General data
any
2000 m
min. 5000 cycles
min. 2000 cycles
harsh environmental conditions
-35 °C ... 75 °C
-25 °C ... 60 °C
according to IEC 60068-2-30: humid heat / cyclic (25 °C / 55 °C; 93 % / 97 % RH)
20 g / 20 ms Duration
> 5 g (f ≤ 80 Hz, duration > 30 min.)
Distributor housing
Mounting rail (35 mm)
Thermoplastic resin
IP20 (installed: IP40)
true
36 mm
85 mm
75 mm
69 mm
doepke_09144601HD_dbl_en.pdf
2/3
Doepke
The experts in residual current protection technology
Technical Data
Width (modules)
Design requirements/Standards
Certifications
Degree of pollution according to
EN 60664
Dimensions
DFS 2 063-2/0,03-A HD
2
VDE 0664-10, EN 61008-1
VDE
2
Wiring example
Dimensional drawing Group view
Wiring diagram
2020_01_31
doepke_09144601HD_dbl_en.pdf
3/3