UL 489
UL 508
UL 1077
UL 1077
Equipment Breakers
Earth Leakage
Circuit Breakers
DFS Series
RCCB Earth Leakage
Circuit Breakers
RCCB Series compact Earth
Leakage Circuit Breakers detect
and interrupt earth (ground) faults.
They are VDE approved for the European system of protecting people, animals, equipment and property from dangerous line-to-ground
and shock hazard currents.
US applications include groundfault protection of equipment
(GFPE) using the 10mA and 30mA
fault current ratings, especially
when high distributed capacitance
or other leakages cause excessive
nuisance trips at lower fault currents. Applications for the 300mA
and 500mA ratings are equipment
protection and fire prevention, limiting the energy of a fault to less
than the minimum ignition energy
for many materials.
Type Designation
__
__
__
RP
(a)
(b)
(c)
(a): 11 = 16A, 12 = 25A, 13 = 40A,
14 = 63A, 15 = 80A, 16 = 100A,
17 = 125A
(b): 2 = 10mA, 4 = 30mA,
6 = 300mA, 7 = 500mA
(c): 601 = 2 pole, 911 = 4 pole
Voltage Rating (maximum)
Min Operating Voltage Bank
of Test Circuit
DFS2
DFS4
Maximum
Rated
Fault
Line
Trip
Current
Current
Cat. No.
Supersedes
16A
10mA
09112601
RP2101
25A
25A
25A
30mA
300mA
09124601
09126601
40A
40A
40A
30mA
300mA
63A
63A
63A
30mA
300mA
500mA
Fault
Trip
Current
Cat. No.
Supersedes
RP2203
RP2230
30mA
300mA
500mA
09124911
09126911
09127911
RP4203
RP4230
RP4250
09134601
09136601
RP2303
RP2330
30mA
300mA
500mA
09134911
09136911
09137911
RP4303
RP4330
RP4350
09144601
09146601
RP2403
RP2430
30mA
300mA
500mA
09144911
09146911
09147911
RP4403
RP4430
RP4450
80A
80A
80A
30mA
300mA
500mA
09154911
09156911
09157911
RP4503
RP4530
RP4550
100A
100A
100A
30mA
300mA
500mA
09164911
09166911
09167911
RP4603
RP4630
RP4650
125A
125A
125A
30mA
300mA
500mA
09174911
09176911
09177911
RP4703
RP4730
RP4750
Stock items are shown in BOLD.
230V AC, 50Hz
400Y/230V AC, 50Hz
150V
200V
Short Circuit Withstand Rating
No back-up fuse: Rated current (RC) 16/25/40A: 500A; RC 63/80A: 800A; RC 100A: 1000A; RC 125A1250A. With back-up fuse: 10kA; Size of fuse: (2 pole version): RC 25/40/63: 100A; (4 pole version): RC
25/40/63A: 100A; RC 80/100/125A: 125A
Fault Trip Current Calibration
FI trips are calibrated at less than fault trip current for ensured safety (Typical trip range between
66.6-83.3% fault trip current, e.g., typical trip at 20-25mA for fault RC of 30mA)
Typical Life
Fully functional after 5,000 operations to DIN/VDE 0664T10, IEC 61008-1 and 2000 additional fault current trips.
Standard Pack and Weight
1/230g (0.6 lb.)
1/420-460g (0.9 lb.-1.0 lb.)
Terminal Size Acceptability
1.5-50mm2 (16-1 AWG)
1.5-50mm2 (16-1 AWG)
Terminal Torque
3Nm (26.5 lb.in.)
3Nm (26.5 lb.in.)
a For 2-Phase applications, terminal 5
Circuit Diagram
a, b
and 6 (next to Neutral terminals) must
be connected to one phase for the test
circuit to be operable.
b For voltage systems without a neutral
conductor. Please use jumper from “1”
or “3” to top “N” terminal. This will
assure proper functioning of the “test”
circuit.
ANNEX
DHI11 - Auxiliary Switches / Error Signal Switch
Contact
Rating
Note: If the power
system has a marked
conductor, it must
connect through the FI
and not be grounded at
any point downstream.
86
Wire
Size
Torque
6A / 230V AC
1-1.5mm2
max. 0.8Nm
1A / 110V DC
(16 AWG)
(7lb.in.)
Std. Pk.: 1
Unit Weight: 45 grams (0.12 lb.)
Width: 9mm (.354in.)
Cat. No.
Supersedes
DHI11
RH11
Circuit
Diagram
12
21
14
11
22
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • P 908.806-9400 • F 908.806.9490 • www.altechcorp.com
Temperature Range
Environmental Information marked with “Snowflake” approval for -25°C to 40°C (-13°F to 104°F)
ambient temperature. (Temperature effect on RC: for every 10°C temperature rise above 40°C
decrease RC by 7%.)
Fluctuating Climate Conditions
According to IEC 60068-2-30: heat (25°C~55°C), relative humidity (93%~95%)
Electrical Shock Protection
Uninsulated electrically live parts within 30mm of the operating handle are “finger safe” (terminal
screw heads) and uninsulated live parts within 100mm of the operating handle are “back-ofhand safe” (terminals).
Impact/Shock Protection
20g with impact force half-cycle sinusoidal and 20ms duration, 18 impacts total with 6 on each
principal axis (3 impacts each face). FI is DIN Rail mounted during the test, and electrically
loaded with 25% of Fault RC. Successful testing required no trip during the test, no damage and
no loosened parts.
Vibration/Seismic Resistance
5g, at frequency of ≤80Hz, applied for 30 minutes along each of the three principal axes, plus 5
minutes of application at every established critical resonant frequency. FI is DIN Rail mounted
during the test, and loaded with 25% Fault RC. To pass, the FI did not trip at 25% Fault RC, but
did trip between each of the principal axis tests when the fault current was raised to 125% Fault
RC, and there was no damage and no loosened parts. Suitable for machinery and mobile
vehicle applications.
Protection Class
IP20; higher protection Class is dependent on housing.
Non-Sinusoidal Fault
The FI is tested and approval stamped for tripping sensitivity to non-sinusoidal fault currents,
which become zero or almost zero within one cycle of the line frequency. Waveforms and
allowed trip-current ranges are as follows:
1.
AC Sinusoidal Fault - 0.5-1.0 times Fault RC
2a.
Pulsating DC Fault;
Positive and Negative Half-Waves - 0.35-1.4 times Fault RC
Phased Half-Wave, 90° - 0.25-1.4 times Fault RC
Phased Half-Wave, 135° - 0.11-1.4 times Fault RC
2b.
3.
Insulation Category
UL 1077
Equipment Breakers
DFS2 and DFS4
Earth Leakage
Circuit Breakers
DFS4
Pulsating DC on 6mA
DC (continuous) Base - Max. 1.4 times Fault RC + 6mA
ANNEX
DFS2
UL 1077
UL 508
UL 489
Dimensions in mm
At VDE rated voltage, suitable for Class C environments with relatively high dust and moisture