UR-Series
UL1077 Recognized
Supplementary Protector
•
•
•
•
•
DIN Rail Mounted
17.5mm width per pole
Thermal Magnetic
480Y/277V AC, 50/60Hz
10kA Short Circuit
Withstand Capacity
• Applications (on the load side
of Branch Circuit Protection)
include: Sensitive Electronics,
Power Supplies, Appliance
circuits, etc.
E137915
PENDING
UR - Series
Voltage Rating
480Y/ 277 VAC
Short Circuit Withstand Rating
0.5 - 10A (RC): 10 kA with no back-up fuse
8 - 63A (RC): 10 kA with UL-listed Class J back-up fuse;
5 kA with no back-up fuse
Calibration Temperature
30ºC (86ºF)
Ambient Temperature
-25ºC to +55ºC (-13ºF to 131ºF )
Storage Temperature
-40ºC to +70ºC (-40ºF to 158ºF )
Terminal Torque
max. 2.5Nm (22.2 lb.in)
Electrical Life
6000 switching cycles ON/ OFF
Mechanical Life
10000 switching cycles ON/ OFF
Vibration Resistance
> 15g according to DIN EN 60069-2-59 during a load with 1.05 x IN
Resistance to mechanical shocks
25g @ 11ms
s h o r t c ir c u it Wit h s t AND r At iNg s f o r r -s e r ie s s u p p l e me Nt Ar y p r o t e c t o r
Backup Protection
Trip
Curve
Amp
Range
UL-Listed
Class J Fuse
up to 10kA
No Backup Fuse
Required
up to:
All
0.3 - 10A
70A
10kA
All
12 - 60A
4xRC*
5kA
*up to nearest rated current
38
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
9
Time versus Current
Trip Curve
Minutes
60
40
10
4
1
10
Time t
4
1
0.4
B
C
D
10-1
Seconds
4x10 -2
For exact trip curves and
additinal technical data
please refer to pages 44-46.
10-2
4x10 -3
10-3
2
3 4
6 8 10 16 20
Multiple of Rated Current
Dimensions in mm
Application Overview
Trip-Characteristics*
Characteristic Trip Boundaries
Thermal Trip
Magnetic Trip
Must not Must Trip Must not Must Trip
100ms at 100ms
Trip>100ms
Applications
Lighting
Wiring
Protection
Control
Circuits
Business
Equipment
Control
Transformers
Power
Supplies
General
Electronics
Reactive
Load
Appliances
B-Characteristics
1.13xRC
1.45xRC
3xRC
5xRC
C-Characteristics
1.13xRC
1.45xRC
5xRC
10xRC
D-Characteristics
1.13xRC
1.45xRC
10xRC
20xRC
*The value of each characteristic is shown vertically beneath its corresponding heading.
Warning!
This information should only be used as a selection guide. The use of a Miniature Circuit Breaker/Supplementary Protector
in an application with a certain Trip-Characteristic always requires prototype testing! It is the responsibility of the circuit
design engineer to select the appropriate Miniature Circuit Breaker/Supplementary Protector for his specific application.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
39
UR - Series
B-Trip
Characteristic
C
Application Examples:
Business equipment, wiring protection, lighting, appliances, control
circuits, some motors and some electronic applications. Relatively long
thermal trip delay but low magnetic trip point.
US
UL Recognized
E137915
One Pole
Weight:
0.3A - 32A
1.75kg (3.86 lb.)
40A - 63A
2.07kg (4.56 lb.)
Rated
Voltage
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
Type/
Cat. No.
1B05UR
1B1UR
1B2UR
1B3UR
1B4UR
1B5UR
1B6UR
1B8UR
1B10UR
1B12UR
1B13UR
1B15UR
1B16UR
1B20UR
1B25UR
1B30UR
1B32UR
1B40UR
1B50UR
1B60UR
1B63UR
Rated
Voltage
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
Type/
Cat. No.
2B05UR
2B1UR
2B2UR
2B3UR
2B4UR
2B5UR
2B6UR
2B8UR
2B10UR
2B12UR
2B13UR
2B15UR
2B16UR
2B20UR
2B25UR
2B30UR
2B32UR
2B40UR
2B50UR
2B60UR
2B63UR
Standard Pack: 4
Weight:
0.3A - 32A
1.75kg (3.86 lb.)
40A - 63A
2.07kg (4.56 lb.)
Weight:
0.3A - 32A
1.75kg (3.86 lb.)
40A - 63A
2.07kg (4.56 lb.)
Rated
Current
0.3-63A
Rated
Type/
Voltage
Cat. No.
277/480VAC N63UM
Standard Pack: 5
Weight:
0.775kg (1.71)
Standard Dual
Connection Terminal
Ring
tongue
• Box clamp terminals
Top: 18-3 AWG;
Bottom: 18-2 AWG
(Line/Load reversible)
Box
clamp
• Ring tongue terminals
11.3 mm
(0.44 in.)
5.3 mm
(0.21 in.)
Standard Pack: 6
Type/
Cat. No.
3B05UR
3B1UR
3B2UR
3B3UR
3B4UR
3B5UR
3B6UR
3B8UR
3B10UR
3B12UR
3B13UR
3B15UR
3B16UR
3B20UR
3B25UR
3B30UR
3B32UR
3B40UR
3B50UR
3B60UR
3B63UR
Add-on Neutral Pole
Two Pole
Rated
Current
0.5A
1.0A
2.0A
3.0A
4.0A
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A*
Rated
Rated
Current Voltage
0.5A 480Y/277VAC
1.0A 480Y/277VAC
2.0A 480Y/277VAC
3.0A 480Y/277VAC
4.0A 480Y/277VAC
5.0A 480Y/277VAC
6.0A 480Y/277VAC
8.0A 480Y/277VAC
10A
480Y/277VAC
12A
480Y/277VAC
13A
480Y/277VAC
15A
480Y/277VAC
16A
480Y/277VAC
20A
480Y/277VAC
25A
480Y/277VAC
30A
480Y/277VAC
32A
480Y/277VAC
40A
480Y/277VAC
50A
480Y/277VAC
60A
480Y/277VAC
63A* 480Y/277VAC
max. 8-12 mm
(0.31-0.47 in.)
Standard Pack: 12
Rated
Current
0.5A
1.0A
2.0A
3.0A
4.0A
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A*
Three Pole
18.3 mm
(0.72 in.)
M5 screw
* May differ by manufacturer. Top terminal ring tongue max. thickness 1.6mm.
*63A is not UL Recognized.
40
UR - Series
C-Trip
Characteristic
C
Application Examples:
Low inrush motors, lighting, wiring protection, appliances,
business equipment, and control circuit applications. Relatively
long thermal trip delay and medium magnetic trip point.
US
UL Recognized
E137915
One Pole
Weight:
0.3A - 32A
1.75kg (3.86 lb.)
40A - 63A
2.07kg (4.56 lb.)
Rated
Voltage
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
Type/
Cat. No.
1C05UR
1C1UR
1C2UR
1C3UR
1C4UR
1C5UR
1C6UR
1C8UR
1C10UR
1C12UR
1C13UR
1C15UR
1C16UR
1C20UR
1C25UR
1C30UR
1C32UR
1C40UR
1C50UR
1C60UR
1C63UR
Standard Pack: 4
Weight:
0.3A - 32A
1.75kg (3.86 lb.)
40A - 63A
2.07kg (4.56 lb.)
Weight:
0.3A - 32A
1.75kg (3.86 lb.)
40A - 63A
2.07kg (4.56 lb.)
Type/
Cat. No.
2C05UR
2C1UR
2C2UR
2C3UR
2C4UR
2C5UR
2C6UR
2C8UR
2C10UR
2C12UR
2C13UR
2C15UR
2C16UR
2C20UR
2C25UR
2C30UR
2C32UR
2C40UR
2C50UR
2C60UR
2C63UR
Rated
Current
0.3-63A
Rated
Type/
Voltage
Cat. No.
277/480VAC N63UM
Standard Pack: 5
Weight:
0.775kg (1.71)
Standard Dual
Connection Terminal
Ring
tongue
• Box clamp terminals
Top: 18-3 AWG;
Bottom: 18-2 AWG
(Line/Load reversible)
Box
clamp
• Ring tongue terminals
11.3 mm
(0.44 in.)
5.3 mm
(0.21 in.)
Standard Pack: 6
Rated
Voltage
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
Type/
Cat. No.
3C05UR
3C1UR
3C2UR
3C3UR
3C4UR
3C5UR
3C6UR
3C8UR
3C10UR
3C12UR
3C13UR
3C15UR
3C16UR
3C20UR
3C25UR
3C30UR
3C32UR
3C40UR
3C50UR
3C60UR
3C63UR
Add-on Neutral Pole
Two Pole
Rated
Current
0.5A
1.0A
2.0A
3.0A
4.0A
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A*
Rated
Rated
Current Voltage
0.5A 480Y/277VAC
1.0A 480Y/277VAC
2.0A 480Y/277VAC
3.0A 480Y/277VAC
4.0A 480Y/277VAC
5.0A 480Y/277VAC
6.0A 480Y/277VAC
8.0A 480Y/277VAC
10A
480Y/277VAC
12A
480Y/277VAC
13A
480Y/277VAC
15A
480Y/277VAC
16A
480Y/277VAC
20A
480Y/277VAC
25A
480Y/277VAC
30A
480Y/277VAC
32A
480Y/277VAC
40A
480Y/277VAC
50A
480Y/277VAC
60A
480Y/277VAC
63A* 480Y/277VAC
max. 8-12 mm
(0.31-0.47 in.)
Standard Pack: 12
Rated
Current
0.5A
1.0A
2.0A
3.0A
4.0A
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A*
Three Pole
18.3 mm
(0.72 in.)
M5 screw
* May differ by manufacturer. Top terminal ring tongue max. thickness 1.6mm.
*63A is not UL Recognized.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
41
UR - Series
D-Trip
Characteristic
C
Application Examples:
Control transformers, power supplies, reactive loads. Relatively long
thermal trip delay and very high magnetic trip point.
US
UL Recognized
E137915
One Pole
Weight:
0.3A - 32A
1.75kg (3.86 lb.)
40A - 63A
2.07kg (4.56 lb.)
Rated
Voltage
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
277VAC
Type/
Cat. No.
1D05UR
1D1UR
1D2UR
1D3UR
1D4UR
1D5UR
1D6UR
1D8UR
1D10UR
1D12UR
1D13UR
1D15UR
1D16UR
1D20UR
1D25UR
1D30UR
1D32UR
1D40UR
1D50UR
1D60UR
1D63UR
Standard Pack: 4
Weight:
0.3A - 32A
1.75kg (3.86 lb.)
40A - 63A
2.07kg (4.56 lb.)
Weight:
0.3A - 32A
1.75kg (3.86 lb.)
40A - 63A
2.07kg (4.56 lb.)
Rated
Voltage
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
480Y/277VAC
Type/
Cat. No.
2D05UR
2D1UR
2D2UR
2D3UR
2D4UR
2D5UR
2D6UR
2D8UR
2D10UR
2D12UR
2D13UR
2D15UR
2D16UR
2D20UR
2D25UR
2D30UR
2D32UR
2D40UR
2D50UR
2D60UR
2D63UR
Rated
Current
0.3-63A
Rated
Type/
Voltage
Cat. No.
277/480VAC N63UM
Standard Pack: 5
Weight:
0.775kg (1.71)
Standard Dual
Connection Terminal
Ring
tongue
• Box clamp terminals
Top: 18-3 AWG;
Bottom: 18-2 AWG
(Line/Load reversible)
Box
clamp
• Ring tongue terminals
11.3 mm
(0.44 in.)
5.3 mm
(0.21 in.)
Standard Pack: 6
Type/
Cat. No.
3D05UR
3D1UR
3D2UR
3D3UR
3D4UR
3D5UR
3D6UR
3D8UR
3D10UR
3D12UR
3D13UR
3D15UR
3D16UR
3D20UR
3D25UR
3D30UR
3D32UR
3D40UR
3D50UR
3D60UR
3D63UR
Add-on Neutral Pole
Two Pole
Rated
Current
0.5A
1.0A
2.0A
3.0A
4.0A
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A*
Rated
Rated
Current Voltage
0.5A 480Y/277VAC
1.0A 480Y/277VAC
2.0A 480Y/277VAC
3.0A 480Y/277VAC
4.0A 480Y/277VAC
5.0A 480Y/277VAC
6.0A 480Y/277VAC
8.0A 480Y/277VAC
10A
480Y/277VAC
12A
480Y/277VAC
13A
480Y/277VAC
15A
480Y/277VAC
16A
480Y/277VAC
20A
480Y/277VAC
25A
480Y/277VAC
30A
480Y/277VAC
32A
480Y/277VAC
40A
480Y/277VAC
50A
480Y/277VAC
60A
480Y/277VAC
63A* 480Y/277VAC
max. 8-12 mm
(0.31-0.47 in.)
Standard Pack: 12
Rated
Current
0.5A
1.0A
2.0A
3.0A
4.0A
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A*
Three Pole
18.3 mm
(0.72 in.)
M5 screw
* May differ by manufacturer. Top terminal ring tongue max. thickness 1.6mm.
*63A is not UL Recognized.
42
For the latest on Altech Circuit Breakers specifications please visit www.altechcorp.com/breaker.
UR Series Accessories
C
For mounting instructions
please refer to page 47.
US
UL Listed
E137938
Auxiliary Contact, Alarm Switch
Contacts Type
Std Pk
Rated Operating
Currents
6
6
6
6
6
10A@240V AC
3A@110V AC
1A@220V AC
1mA @ 24VDC
max. 0.8Nm (7 lb.in)
Minimum Contact Load
Torque
Wire Range:
Single Wire
Stranded Wire
Stranded Wire
with Ferrule
45 mm
1 Auxiliary Contact
1NO
2 Auxiliary Contacts
1NO + 1NC
3 Auxiliary Contacts
1NO + 2NC
3 Auxiliary Contacts
2NO + 1NC
1 Auxiliary/ 1 Signal Contacts 1NO + 1 Signal
87 mm
52.7 mm
H10UM
H11UM
H12UM
H21UM
HLS11M
Description
17.7 mm
Type/ Cat No.
6 mm
63.8 mm
8.8 mm
Dimensions HxxUM.
1.0mm² - 2.5mm² (18-14 AWG)
1.0mm² - 1.5mm² (18-16 AWG)
1.0mm² - 1.5mm² (18-16 AWG)
Shunt Trip
44 mm
Std Pk
25.5 mm
20.4 mm
12 V AC/DC
24 V AC/DC
48 - 72 V AC/DC
FA110UM
110 - 240 V AC/DC,
277V AC
1.3A
0.6A
0.2A
0.25A @ 110V
0.5A @ 240V
0.58A @ 277V
5
5
5
89.3 mm
44.5 mm
FA12UM
FA24UM
FA48UM
5
Undervoltage Trip
Type/ Cat No.
Line Voltage VE
Std Pk
UA120UM
120 VAC, 60Hz
5
6 mm
7 mm
45 mm
Description
37.5 mm
34.5 mm
Type/ Cat No.
Max. Operating
Current @ Un
8 mm
14.5 mm
17.5 mm
4 mm
30.5 mm
44 mm
Reset-Hold Voltage = 0.85 x VE
Drop-Out Voltage = 0.35 ~ 0.7 x VE
68.4 mm
Dimensions FAxxUM, UA120UM, N63UM.
Neutral Pole
Type/ Cat No.
Rated Current In
Rated Voltage
Std Pk
N63UM
0.3 - 63A
277Y/ 480 VAC
5
Mounting Screw 34mm
to connect the auxiliary contact and shunt
trip or neutral Pole to the circuit breaker.
Touch Protection Caps
to cover the terminal screws on the switching
devices, neutral Poles and shunt trips for
increased touch protection.
Type/ Cat No.
Standard Pack
E983419
10
Lock-out Adapter
Type/ Cat No.
Standard Pack
Type/ Cat No.
Standard Pack
BS.UL
100
EASS
10
43
UR Series Trip Curves
C Trip Curve
Minutes
10
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
4
1.13-1.45xIN
1.13-1.45xIN
60
40
60
40
10
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
4
10
10
1
Tripping time t
10
Tripping time t
1
4
4
1
0.4
0.4
10-1
4x10-2
10-2
10-2
4x10-3
10-3
2
3 4 5 6 8 10
20
40
100
1
20
40
10-3
100
Minutes
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
10
Seconds
4x10-2
10-2
4x10-3
1
0.4
2
3 4 5 6 8 10
20
40
100
Multiple of Rated Current
13A Through 63A Rated Current
1
0.4
10-1
10-1
4x10-2
10-2
4x10-3
10-3
1
4
4x10-2
Seconds
10-1
Tripping time t
10
Tripping time t
10
4
10-2
4x10-3
10-3
1
2
3 4 5 6 8 10
20
40
Multiple of Rated Current
13A Through 63A Rated Current
“B” Magnetic Trip Parameters
Rated current 1.0A to 63A.
“C” Magnetic Trip Parameters
Rated current 0.3A to 63A.
1. Hold for a minimum of 100ms at
surge of 3 times rated current.
2. Trip in under 100ms at 5 times rated
current.
1. Hold for a minimum of 100ms at
surge of 5 times rated current.
2. Trip in under 100ms at 10 times
rated current.
100
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
4
1
1
100
10
1
0.4
40
1.13-1.45xIN
60
40
1
4
3 4 5 6 8 10 16 20
0.3A Through 10A Rated Current
10
4
2
Multiple of Rated Current
1.13-1.45xIN
60
40
10
10-3
1
0.3A Through 10A Rated Current
1.13-1.45xIN
Minutes
3 4 5 6 8 10
10-2
4x10-3
Multiple of Rated Current
60
40
4
2
Minutes
1
Seconds
10-1
4x10-2
1.0A Through 10A Rated Current
Tripping time t
1
0.4
10-1
Multiple of Rated Current
Seconds
4
4x10-2
4x10-3
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
4
1
10-3
44
10
1
Seconds
Seconds
Tripping time t
Minutes
1.13-1.45xIN
60
40
D Trip Curve
Minutes
B Trip Curve
1
2
3 4 5 6 8 10 16 20
40
100
Multiple of Rated Current
13A Through 63A Rated Current
“D” Magnetic Trip Parameters
Rated current 0.3A to 63A.
1. Hold for a minimum of 100ms at
surge of 10 times rated current.
2. Trip in under 100ms at 16 times
rated current.
For the latest on Altech Circuit Breakers specifications please visit www.altechcorp.com/breaker.
UR Series Internal Resistance
Rated Current
(A)
0.5
1.0
2.0
3.0
4.0
5.0
6.0
8.0
10
12/ 13
15/ 16
20
25
30/ 32
40
50
60/ 63*
B
(Ohm)
Trip Characteristic
C
(Ohm)
D
(Ohm)
1.7000
0.4190
0.2020
0.1090
0.0654
0.0528
0.0278
0.0216
0.0113
0.0085
0.0067
0.0050
0.0032
0.0025
0.0019
0.0018
6.8540
1.7000
0.4190
0.2020
0.1090
0.0654
0.0528
0.0278
0.0216
0.0084
0.0085
0.0067
0.0050
0.0032
0.0025
0.0019
0.0018
6.0009
1.7560
0.4190
0.2020
0.1090
0.0654
0.0491
0.0240
0.0187
0.0085
0.0076
0.0064
0.0041
0.0027
0.0022
0.0018
0.0017
Mounting Instructions for UL489, UL508 and UL1077 Accessories
Neutral / Shunt Trip plus possibly Auxiliary Contact
Switching
Device
Neutral Switch/
Shunt Trip
Neutral Switch/
Shunt Trip
Auxiliary
Contact
5.
6.
7mm
4.
1.
Mounting screw
34mm
3.
6.
24 mm
2.
1. Neutral Poles N63UM, N32UL, N63UL or Shunt Trips FA..UM, FA..UL can be mounted on right or
left side of device.
2. Bring blue knob of all devices into “OFF” position.
3. Remove grey cover from the switching device and attachment.
4. Insert drive plate between switching device and Neutral Poles N63UM, N32UL, N63UL or Shunt Trips
FA..UM, FA..UL.
5. Insert connecting pin into knob.
6. Combine switching device and Neutral Poles N63UM, N32UL, N63UL or Shunt Trips FA..UM, FL..UL.
7. Screw device together.
8. Possibility of mounting Auxiliary contact H...UM, H...UL additionally on the right only, different
screw type (see E983419 accessories) necessary.
Auxiliary Contact
Switching
Device
Auxiliary
Contact
3.
4.
1.
2.
90°
1.
2.
3.
4.
Auxiliary can be mounted on right side of device only.
Bring blue knob of both devices into “OFF” poistion.
Remove grey cover from switching device.
Combine switching device and Auxiliary Contact
H...UM, H...UL.
5. Insert connection screws and connect the two devices
by turning the screws by 90°.
6. After mounting close and open to check operation.