UL 489
CircuitProtection_2016.QXD_CircuitProtection 4/8/16 1:47 PM Page 20
L-Series
AC or DC
UL489 Listed
Circuit Breakers
• Available in AC and DC models
• DIN Rail Mounted
• 17.5mm width
• Thermal Magnetic
• 240V, 480Y/277V AC, 50/60Hz
• 125VDC (1 pole); 250VDC (2 pole)
• 10kA Short Circuit
Interrupting Capacity
• Positive Trip indicator
(Green - off/tripped, Red - on)
• HACR Type 40°C
• Line/Load reversible
UL 1077
Equipment Breakers
UL 1077
UL 508
Miniature Molded Case
Circuit Breakers
Earth Leakage
Circuit Breakers
LISTED
E305318
AC Version Current/ Voltage Rating
0.2-63A/240VAC, 0.2-32A/480Y/277VAC*
DC Version Current/ Voltage Rating
0.2-63A/125/250VDC
Calibration Temperature
40°C (104°F)
Operating Temperature
-25° to 60°C (-13° to 140°F)
Storage Temperature
-25° to 75°C (-13° to 167°F)
Terminal Size Acceptability
14-3 AWG: 17.5 lb-in. (2.0 Nm)
and Torque
18-16 AWG: 25 lb-in. (2.8 Nm)
Terminal Protection Degree
IP20 at front
Electrical Life
6,000 cycles on/off
Mechanical Life
10,000 cycles on/off
Wire Connection
copper wire only 60/75°C
Vibration Resistance
3g (18-50Hz)
Mounting Orientation
In any plane
*One device dual voltage ratings.
ANNEX
aC - short CirCuit interruptinG ratinG
20
DC - short CirCuit interruptinG ratinG
No.
Poles
Type
0.2-32A
33-63A
No.
Poles
Type
0.2-32A
33-63A
1
AC
10kA@120, 240, 277V
10kA@120, 240V
1
DC
10kA@125V
10kA@125V
2-4
AC
10kA@120, 240V, 480Y/277V
10kA@120, 240V
2
DC
10kA@250V
10kA@250V
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • P 908.806-9400 • F 908.806.9490 • www.altechcorp.com
Time
versus
Current Trip Curve
10
4
1
1
Dimensions in mm
side view
0.4
C
D
45mm (1.77 in.)
10-1
10-2
4x10-3
10-3
3 4
6 8 10 16 20
Multiple of Rated Current
6.5mm
(0.26 in.)
UL 1077
2
44mm (1.73 in.)
60mm (2.36 in.)
3 PoLe
17.5mm (0.69 in.)
14.5mm (0.57 in.)
UL 1077
Equipment Breakers
109mm (4.29 in.)
69mm (2.72 in.)
17.5mm (0.69 in.)
14.5mm (0.57 in.)
69mm (2.72 in.)
2 PoLe
109mm (4.29 in.)
14.5mm (0.57 in.)
69mm (2.72 in.)
1 PoLe
109mm (4.29 in.)
Seconds
4x10-2
17.5mm (0.69 in.)
35mm (1.38 in.)
35mm (1.38 in.)
52.5mm (2.07 in.)
Trip-Characteristics*
Type
Characteristic Trip Boundaries
Thermal Trip
Applications
Lighting
Wiring
Protection
Magnetic Trip
Control
Circuits
Must not Must Trip Must not Must Trip
Trip>100ms
100ms at 100ms
Business
Equipment
Transformers
Appliances
Earth Leakage
Circuit Breakers
Time t
4
UL 508
For the exact trip curve,
please refer to page 25.
10
Motors
Power
Supplies
Reactive
Load
Heaters
Low
Inrush
High
Inrush
C-Characteristics
1.05xRC
1.3xRC
5xRC
10xRC
AC
1.05xRC
1.3xRC
5xRC
10xRC
DC
D-Characteristics
1.05xRC
1.3xRC
10xRC
16xRC
AC
1.05xRC
1.3xRC
10xRC
16xRC
DC
*The value of each characteristic is shown vertically beneath its corresponding heading.
ANNEX
Minutes
60
40
UL 489
CircuitProtection_2016.QXD_CircuitProtection 4/4/16 12:22 PM Page 21
Warning!
This information should only be used as a selection guide. The use of a Miniature Circuit
Breaker in an application with a certain Trip-Characteristic always requires prototype
testing! It is the responsibility of the circuit design engineer to select the appropriate
Miniature Circuit Breaker for his specific application.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • P 908.806-9400 • F 908.806.9490 • www.altechcorp.com
21
UL 489
CircuitProtection_2016.QXD_CircuitProtection 4/4/16 12:22 PM Page 22
AC C-Trip
Characteristics
Application Examples:
Low inrush motors, resistive loads, wiring
protection, receptacles, lighting, and
control circuit applications. Relatively
short thermal trip delay and medium
magnetic trip point.
UL 508
LISTED
E305318
Earth Leakage
Circuit Breakers
UL 1077
Equipment Breakers
UL 1077
One Pole
ANNEX
Three Pole
Rated
Current
0.2A
0.5A
1.0A
1.6A
2.0A
3.0A
4.0A
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
Type/
Cat. No.
1CU02L
1CU05L
1CU1L
1CU1.6L
1CU2L
1CU3L
1CU4L
1CU5L
1CU6L
1CU8L
1CU10L
1CU12L
1CU13L
1CU15L
1CU16L
1CU20L
1CU25L
1CU30L
1CU32L
1CU40L
1CU50L
1CU60L
1CU63L
Two Pole
Rated
Current
0.2A
0.5A
1.0A
1.6A
2.0A
3.0A
4.0A
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
Type/
Cat. No.
2CU02L
2CU05L
2CU1L
2CU1.6L
2CU2L
2CU3L
2CU4L
2CU5L
2CU6L
2CU8L
2CU10L
2CU12L
2CU13L
2CU15L
2CU16L
2CU20L
2CU25L
2CU30L
2CU32L
2CU40L
2CU50L
2CU60L
2CU63L
Standard Pack: 12
Standard Pack: 6
Weight: 1.7kg (3.74 lb.)
Weight: 1.7kg (3.74 lb.)
Rated
Current
0.2A
0.5A
1.0A
1.6A
2.0A
3.0A
4.0A
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
Type/
Cat. No.
3CU02L
3CU05L
3CU1L
3CU1.6L
3CU2L
3CU3L
3CU4L
3CU5L
3CU6L
3CU8L
3CU10L
3CU12L
3CU13L
3CU15L
3CU16L
3CU20L
3CU25L
3CU30L
3CU32L
3CU40L
3CU50L
3CU60L
3CU63L
Four Pole
Please contact
Altech.
Standard Pack: 4
Weight: 1.7kg (3.74 lb.)
For ring tongue terminal version, replace “U” with “R” in part number. For example 1CR20L instead of 1CU20L.
22
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • P 908.806-9400 • F 908.806.9490 • www.altechcorp.com
CircuitProtection_2016.QXD_CircuitProtection 4/4/16 12:22 PM Page 23
Application Examples:
High inrush motors, transformers, power
supplies, heaters and reactive loads.
Relatively long thermal trip delay and very
high magnetic trip point.
UL 489
AC D-Trip
Characteristics
LISTED
E305318
Standard Pack: 12
Standard Pack: 6
Weight: 1.7kg (3.74 lb.)
Weight: 1.7kg (3.74 lb.)
Rated
Current
0.2A
0.5A
1.0A
1.6A
2.0A
3.0A
4.0A
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
Type/
Cat. No.
3DU02L
3DU05L
3DU1L
3DU1.6L
3DU2L
3DU3L
3DU4L
3DU5L
3DU6L
3DU8L
3DU10L
3DU12L
3DU13L
3DU15L
3DU16L
3DU20L
3DU25L
3DU30L
3DU32L
3DU40L
3DU50L
3DU60L
3DU63L
UL 1077
UL 508
Type/
Cat. No.
2DU02L
2DU05L
2DU1L
2DU1.6L
2DU2L
2DU3L
2DU4L
2DU5L
2DU6L
2DU8L
2DU10L
2DU12L
2DU13L
2DU15L
2DU16L
2DU20L
2DU25L
2DU30L
2DU32L
2DU40L
2DU50L
2DU60L
2DU63L
UL 1077
Equipment Breakers
Two Pole
Rated
Current
0.2A
0.5A
1.0A
1.6A
2.0A
3.0A
4.0A
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
Earth Leakage
Circuit Breakers
Three Pole
Type/
Cat. No.
1DU02L
1DU05L
1DU1L
1DU1.6L
1DU2L
1DU3L
1DU4L
1DU5L
1DU6L
1DU8L
1DU10L
1DU12L
1DU13L
1DU15L
1DU16L
1DU20L
1DU25L
1DU30L
1DU32L
1DU40L
1DU50L
1DU60L
1DU63L
Four Pole
Please contact
Altech.
ANNEX
One Pole
Rated
Current
0.2A
0.5A
1.0A
1.6A
2.0A
3.0A
4.0A
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
Standard Pack: 4
Weight: 1.7kg (3.74 lb.)
For ring tongue terminal version, replace “U” with “R” in part number. For example 1CR20L instead of 1CU20L.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • P 908.806-9400 • F 908.806.9490 • www.altechcorp.com
23
UL 489
CircuitProtection_2016.QXD_CircuitProtection 4/4/16 12:22 PM Page 24
DC C- & D-Trip
Characteristics
Application Examples:
Telecommunication equipment,
computer equipment, uninterruptable
power supplies.
LISTED
E305318
UL 1077
UL 508
C-Trip
UL 1077
Equipment Breakers
One Pole
Earth Leakage
Circuit Breakers
D-Trip
ANNEX
One Pole
Rated
Current
0.2A
0.5A
1.0A
1.6A
2.0A
3.0A
4.0A
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
Type/
Cat. No.
DC1CU02L
DC1CU05L
DC1CU1L
DC1CU1.6L
DC1CU2L
DC1CU3L
DC1CU4L
DC1CU5L
DC1CU6L
DC1CU8L
DC1CU10L
DC1CU12L
DC1CU13L
DC1CU15L
DC1CU16L
DC1CU20L
DC1CU25L
DC1CU30L
DC1CU32L
DC1CU40L
DC1CU50L
DC1CU60L
DC1CU63L
Two Pole
Rated
Current
0.2A
0.5A
1.0A
1.6A
2.0A
3.0A
4.0A
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
Standard Pack: 12
Standard Pack: 6
Weight: 1.7kg (3.74 lb.)
Weight: 1.7kg (3.74 lb.)
Rated
Current
0.2A
0.5A
1.0A
1.6A
2.0A
3.0A
4.0A
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
Type/
Cat. No.
DC1DU02L
DC1DU05L
DC1DU1L
DC1DU1.6L
DC1DU2L
DC1DU3L
DC1DU4L
DC1DU5L
DC1DU6L
DC1DU8L
DC1DU10L
DC1DU12L
DC1DU13L
DC1DU15L
DC1DU16L
DC1DU20L
DC1DU25L
DC1DU30L
DC1DU32L
DC1DU40L
DC1DU50L
DC1DU60L
DC1DU63L
Two Pole
Rated
Current
0.2A
0.5A
1.0A
1.6A
2.0A
3.0A
4.0A
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
Standard Pack: 12
Standard Pack: 6
Weight: 1.7kg (3.74 lb.)
Weight: 1.7kg (3.74 lb.)
Type/
Cat. No.
DC2CU02L
DC2CU05L
DC2CU1L
DC2CU1.6L
DC2CU2L
DC2CU3L
DC2CU4L
DC2CU5L
DC2CU6L
DC2CU8L
DC2CU10L
DC2CU12L
DC2CU13L
DC2CU15L
DC2CU16L
DC2CU20L
DC2CU25L
DC2CU30L
DC2CU32L
DC2CU40L
DC2CU50L
DC2CU60L
DC2CU63L
Type/
Cat. No.
DC2DU02L
DC2DU05L
DC2DU1L
DC2DU1.6L
DC2DU2L
DC2DU3L
DC2DU4L
DC2DU5L
DC2DU6L
DC2DU8L
DC2DU10L
DC2DU12L
DC2DU13L
DC2DU15L
DC2DU16L
DC2DU20L
DC2DU25L
DC2DU30L
DC2DU32L
DC2DU40L
DC2DU50L
DC2DU60L
DC2DU63L
For ring tongue terminal version, replace “U” with “R” in part number. For example 1CR20L instead of 1CU20L.
24
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • P 908.806-9400 • F 908.806.9490 • www.altechcorp.com
CircuitProtection_2016.QXD_CircuitProtection 4/4/16 12:22 PM Page 25
C and D Trip
Less than 10A
C and D Trip
10A and higher
7200
3600
2400
20
1200
10
8
6
4
600
480
360
240
2
120
1
40
60
40
20
20
10
10
5
1
UL 508
Minutes
60
40
Tripping time t
5
1
0.5
0.1
C
0.05
0.01
1
2
3
4
Seconds
0.5
D
0.1
C
0.05
0.01
1
5 6 7 8 9 10 12 14 16 20
1.05 1.3
2
3
4
UL 1077
Tripping time t
Minutes
120
Seconds
UL 489
L-Series Trip Curves
D
5 6 7 8 9 10 12 14 16 20
1.05 1.3
Multiple of Rated Current
Multiple of Rated Current
Internal
impedance
Z (m Ω)
char. B, C, D, K
Power Loss
B, C, D, K
P (W)
-20
-10
0
10
20
30
40
50
60
0.2
0.24
0.24
0.23
0.22
0.21
0.2
0.19
0.18
0.17
45100.0
1.80
0.5
0.61
0.59
0.57
0.55
0.53
0.5
0.47
0.44
0.42
8000.0
2.00
1
1.21
1.18
1.14
1.1
1.05
1.0
0.93
0.88
0.83
2000.0
2.00
2
2.42
2.36
2.28
2.2
2.1
2.0
1.86
1.76
1.67
490.0
1.96
3
3.63
3.54
3.42
3.3
3.15
3.0
2.79
2.64
2.5
230.0
2.07
4
4.84
4.72
4.56
4.4
4.2
4.0
3.72
3.52
3.33
150.0
2.40
5
6.1
5.9
5.7
5.5
5.3
5.0
4.7
4.4
4.2
95.0
2.38
6
7.3
7.1
6.8
6.6
6.3
6.0
5.6
5.3
5.0
69.0
2.48
7
8.5
8.2
8.0
7.7
7.4
7.0
6.5
6.2
5.8
52.0
2.55
8
9.7
9.4
9.1
8.8
8.4
8.0
7.4
7.0
6.7
35.0
2.24
10
12.1
11.8
11.4
11.0
10.5
10.0
9.3
8.8
8.3
23.5
2.35
12
14.5
14.2
13.7
13.2
12.6
12.0
11.2
10.6
10.0
18.7
2.69
13
15.7
15.3
14.8
14.3
13.7
13.0
12.1
11.5
10.8
14.3
2.42
14
16.9
16.5
16.0
15.4
14.7
14.0
13.0
12.3
11.7
12.4
2.43
15
18.2
17.7
17.1
16.5
15.8
15.0
14.0
13.2
12.5
10.1
2.27
16
19.4
18.9
18.2
17.6
16.8
16.0
14.9
14.1
13.3
7.5
1.92
20
24.2
23.6
22.8
22.0
21.0
20.0
18.6
17.6
16.7
6.3
2.52
25
30.3
29.5
28.5
27.5
26.3
25.0
23.3
22.0
20.8
4.6
2.88
30
36.3
35.4
34.2
33.0
31.5
30.0
27.9
26.5
25.0
3.6
3.24
32
38.7
37.8
36.5
35.2
33.6
32.0
29.8
28.2
26.7
3.6
3.69
35
42.3
41.3
39.9
38.5
36.8
35.0
32.6
30.8
29.2
3.6
4.41
40
48.4
47.2
45.6
44.0
42.0
40.0
37.2
35.2
33.3
3.0
4.80
50
60.5
59.0
57.0
55.0
52.5
50.0
46.5
44.1
41.7
2.4
6.00
60
72.6
70.9
68.4
66.0
63.0
60.0
55.9
52.9
50.1
1.8
6.48
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • P 908.806-9400 • F 908.806.9490 • www.altechcorp.com
Earth Leakage
Circuit Breakers
rated current allowing for ambient temperature
I cor (A)
ANNEX
Rated
current
In (A)
UL 1077
Equipment Breakers
Temperature and Power Loss Specifications
25
CircuitProtection_2016.QXD_CircuitProtection 4/4/16 12:22 PM Page 26
UL 489
Accessories
L-Series
Circuit Breakers
Accessories can be factory or field mounted on L-Series miniature molded case circuit
breakers for enhanced control and monitoring capabilities. Field mounting kits include all
necessary parts and instructions. Accessories can be gang mounted on a single controller
(the Auxiliary Switch in the outside position). The mounting arrangement links the internal
latch-pins for the tripping mechanisms, ensuring simultaneous trips. Handles are linked to
simplify manual resetting.
UL 508
LISTED
E305318
Neutral
Pole
(63A/240VAC; 32A/480Y/277VAC)
Description
Neutral
Type/
Cat. No.
ALTN2L
Cable
Max
25mm2
3 AWG
Standard Pack: 10
UL 1077
17.5 mm
Cable
Min
2.5mm2
12 AWG
Torque
Max
2Nm
17.5 lb-in
Torque
Min
1.5Nm
12 lb-in
Weight: 1.2kg (2.64 lb.)
Shunt Trip and
Undervoltage Trip
UL 1077
Equipment Breakers
Description
Earth Leakage
Circuit Breakers
Shunt Trip
17.5 mm
Shunt Trip
Type/Cat. No.
Operational
Voltage
Rated
Coil Current
Undervoltage Trip*
Type/Cat. No.
FA12ACL
FA24ACL
FA48ACL
FA60ACL
FA110ACL
FA120ACL
FA230ACL
FA277ACL
FA400ACL
8.4 - 13.2V
16.8 - 26.4V
33.6 - 52.8V
42 - 66V
77 - 121V
84 - 132V
161 - 253V
194 - 305V
280 - 440V
6A
2.8A
0.8A
~0.7A
0.5A
~0.5A
0.6A
~0.5A
0.5A
UV12ACL
UV24ACL
UV48ACL
UV60ACL
UV110ACL
UV120ACL
UV230ACL
UV277ACL
UV400ACL
FA12DCL
FA24DCL
FA48DCL
FA110DCL
8.4 - 13.2V
16.8 - 26.4V
33.6 - 52.8V
77 - 121V
~6A
3A
2A
0.6A
UV12DCL
UV24DCL
UV48DCL
UV110DCL
AC Coil:
12V AC
24V AC
48V AC
60V AC
110V AC
120V AC
230V AC
277V AC
400V AC
DC Coil:
12V DC
24V DC
48V DC
110V DC
* Reset-Hold Voltage = 0.85 x VE; Drop-Out Voltage = 0.2 x VE
Standard Pack: 10
Weight: 1.1kg (2.43 lb.)
Undervoltage
Trip
17.5 mm
2.5 mm2 (12 AWG) / 25mm2 (3 AWG)
1.5 Nm (12 lb. in.) / 2 Nm (17.5 lb. in.)
ANNEX
Terminal Size - min/max
Terminal Torque - min/max
26
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • P 908.806-9400 • F 908.806.9490 • www.altechcorp.com
CircuitProtection_2016.QXD_CircuitProtection 4/4/16 12:22 PM Page 27
UL 489
Accessories
L-Series
Circuit Breakers
LISTED
E305318
Description
8.9 mm
1 x CO
Type/
Cat. No.
H1COL
2 x CO
H2COL
1 x CO, 1 Signal
& Test Button
HSTCOL
Cable
Max
Cable
Min
2.5mm2
12 AWG
0.5mm2
20 AWG
Torque
Max
UL 508
Auxiliary
Contact (6A/120V AC; 3A/240V AC; 6A/24V DC; 0.5A/125V DC)
Torque
Min
0.5Nm
4 lb-in
0.33Nm
3 lb-in
UL 1077
Standard Pack: 15
Weight: 0.5kg (1.32 lb.)
Wiring
Diagram
Auxiliary Circuit
Switch Breaker
11
Circuit
Breaker
Auxiliary
Switch
1
95
14 12
HSTCOL
98
96
11
1
14 12
Regular
Auxiliary
Switch
Signal
Switch
95
98
Circuit
Breaker
11
96
1
14 12
>
>
>
2
2
2
Lock-out Adapter
Description
Yellow
Standard Pack: 10
Front Mounting Kit
Description
1 Pole
2 Pole
3 Pole
Type/
Cat. No.
FMA1PL
FMA2PL
FMA3PL
with hardware
Weight
40g (1.41 oz.)
45g (1.59 oz.)
50g (1.76 oz.)
Standard Pack: 1
ANNEX
Weight: 50g (1.76 oz.)
Type/
Cat. No.
EASS2L
Luggage
Lock
UL 1077
Equipment Breakers
H2COL
Earth Leakage
Circuit Breakers
H1COL
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • P 908.806-9400 • F 908.806.9490 • www.altechcorp.com
27
很抱歉,暂时无法提供与“1DU20L”相匹配的价格&库存,您可以联系我们找货
免费人工找货