FI Earth Leakage Circuit Breakers
FI compact Earth Leakage Circuit Breakers detect and interrupt earth (ground) faults. They are VDE approved for the European system of protecting people, animals, equipment and property from dangerous line-to-ground and shock hazard currents. US applications include groundfault protection of equipment (GFPE) using the 10mA and 30mA fault current ratings, especially when high distributed capacitance or other leakages cause excessive nuisance trips at lower fault currents. Applications for the 300mA rating are equipment protection and fire prevention, limiting the energy of a fault to less than the minimum ignition energy for many materials. Type Designation __ __ • __ (a) (b) (c)
Maximum Rated Line Current 16A 25A 25A 40A 40A 63A 63A
Fault Trip Current 10mA 30mA 300mA 30mA 300mA
FI 2
Type Cat. No. 15.921 15.922 15.924 15.923 15.925
FI 21.01 FI 22.03 FI 22.30 FI 23.03 FI 23.30
Fault Trip Current 30mA 300mA 30mA 300mA 30mA 300mA
FI 4a
Type FI 42.03 FI 42.30 FI 43.03 FI 43.30 FI 44.03 FI 44.30 Cat. No. 15.926 15.929 15.927 15.930 15.928 15.931
(a) = 2-2 pole; 4-4 pole (b) = 1-16A; 2-25A; 3-40A; 4-63A (c) = 01 - 10mA = 03 - 30mA = 30 - 300mA Voltage Rating (maximum) Short Circuit Capacity Typical Life
Earth Leakage Circuit Breaker with Auxiliary Contactsb 25A 40A 63A 30mA 30mA
FI 22.03Y 15.932 FI 23.03Y 15.934
Earth Leakage Circuit Breaker with Auxiliary Contactsb 30mA 30mA 30mA FI 42.03Y FI 43.03Y FI 44.03Y
15.933 15.935 15.936
240VAC, 50/60Hz (VDE: 125/220VAC, 50Hz)
Fault Trip Current Calibration Standard Pack and Weight Equivalent Circuit
Up to rated current (RC) 40A = 1.5kA, RC 63A = 2kA. 10kA in combination with series fuse of European Operation Class gL/gG: RC 16A = 63A fuse, RC 25/40A = 80A fuse, RC 63A = 100A fuse. FI trips are calibrated at less than fault trip current for ensured safety (Typical trip range between 66.6-83.3% fault trip current, e.g., typical trip at 20-25mA for fault RC of 30mA) 1/290g (0.64 lb.); 1/390g (0.86 lb.) with auxiliary contact 16-6 AWG 1 N
415VAC, 50/60Hz (400Hz available on request) (VDE: 220/380VAC, 50Hz)
Fully functional after 4,000 operations to DIN/VDE 0664 (CEE27) and 16000 additional fault current trips. 1/450g (1.0 lb.) 1/550g (1.21 lb.) with auxiliary contact 14-3 AWG
Terminal Size Acceptability
a For 2-Phase applications, terminal 5
b Provided with mounted Auxiliary
and 6 (next to Neutral terminals) must be connected to one phase for the test circuit to be operable. Switch, one N.O., one N.C. isolated feedthrough contact (Form X double make and Y double break), which adds 9mm (.35 in.) to the width dimension. conductor. Please use jumper from “1” or “3” to top “N” terminal. This will assure proper functioning of the “test” circuit.
1 3 5 Nc
c For voltage systems without a neutral
HFI11 - Auxiliary Switch
6A / 230V AC 1A / 220V DC or pulsed Std. Pk.: 1 Unit Weight: 45 grams (0.12 lb.) Width: 9mm (.354in.) Contact Rating
2
N
Test
2 4 6 N Test Wire Size
Note: If the power system has a marked conductor, it must connect through the FI and not be grounded at any point downstream.
4mm2 (12 AWG)
HFI11
Type
Cat. No. 15.991
74
5.8mm (0.23 in.)
10.9mm (0.43 in.)
8mm (0.31 in.) N 72.5mm (2.85 in.)
13.5mm 13.5mm 13.5mm (0.53 in.) (0.53 in.) (0.53 in.)
64mm (2.52 in.)
58mm (2.28 in.)
22.9mm (0.90 in.)
R1
1 72.5mm (2.85 in.) 36mm (1.42 in.)
1
3
5
N 90.5mm (3.56 in.)
45.4mm (1.79in.) 88°
46°
R1
2 18mm (0.71 in.)
N
2
4
6
N
9mm (0.35 in.)
36mm (1.42 in.)
9mm (0.35 in.)
18mm 18mm 18mm (0.71 in.) (0.71 in.) (0.71 in.) 72mm (2.83 in.)
3.2mm (0.13 in.)
Temperature Range
FI 2
Fluctuating Climate Conditions Electrical Shock Protection Impact/Shock Protection Vibration/Seismic Resistance
Environmental Information marked with “Snowflake” approval for -25°C to 40°C (-13°F to 104°F) ambient temperature. (Temperature effect on RC: for every 10°C temperature rise above 40°C decrease RC by 7%.) To maximum 45°C, 95% relative humidity. Uninsulated electrically live parts within 30mm of the operating handle are “finger safe” (terminal screw heads) and uninsulated live parts within 100mm of the operating handle are “back-of-hand safe” (terminals). 15g with impact force half-cycle sinusoidal and 11ms duration, 18 impacts total with 6 on each principal axis (3 impacts each face). FI is DIN Rail mounted during the test, and electrically loaded with 25% of Fault RC. Successful testing required no trip during the test, no damage and no loosened parts. 5g, at frequency of 55Hz to 2,000Hz, applied for 35 ± 5 minutes along each of the three principal axes, plus 5 minutes of application at every established critical resonant frequency. FI is DIN Rail mounted during the test, and loaded with 25% Fault RC. To pass, the FI did not trip at 25% Fault RC, but did trip between each of the principal axis tests when the fault current was raised to 125% Fault RC, and there was no damage and no loosened parts. Suitable for machinery and mobile vehicle applications.
FI 4
FI 2 and FI 4
68mm (2.68 in.)
44mm (1.73 in.)
31mm (1.22 in.)
15.7mm (0.62 in.)
Housing Class Non-Sinusoidal Fault
Ingress Protection (IP) Class 40; internal working components and live parts (excluding terminals) are protected against ingress of solid objects greater than 1mm diameter (class 4-), but have no protection from ingress of water (class-0). The FI is tested and approval stamped for tripping sensitivity to non-sinusoidal fault currents, which become zero or almost zero within one cycle of the line frequency. Waveforms and allowed tripcurrent ranges are as follows: 1. 2a. 2b. 3. AC Sinusoidal Fault - 0.5-1.0 times Fault RC Pulsating DC Fault; Positive and Negative Half-Waves - 0.35-1.4 times Fault RC Phased Half-Wave, 90° - 0.25-1.4 times Fault RC Phased Half-Wave, 135° - 0.11-1.4 times Fault RC Pulsating DC on 6mA DC (continuous) Base - Max. 1.4 times Fault RC + 6mA
Insulation Category
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
At VDE rated voltage, suitable for Class C environments with relatively high dust and moisture levels and little HVAC control, e.g., industrial, commercial, agricultural; on machine tools, hoists, warehouse equipment, etc.; in boiler rooms, unheated storage, covered shipping/receiving, open workshops, etc.