GFL Series - 2 Pole + N, B Trip, 30 mA
10kA UL489 Listed Branch Circuit Breaker with
Equipment Ground Fault Protection (RCBO)
The GFL Series range is a combined Branch Circuit Breaker and
Equipment Ground Fault Protector, featuring dual pole switching (live
and neutral disconnect) and designed to provide protection against
short circuits, overloads, AC ground faults (residual current faults) as
well as pulsating DC ground faults.
N
3
1
LINE
C.B. W/EQ.GFP
E483494
Ordering Information
Rated
Voltage
120/240V AC
120/240V AC
120/240V AC
120/240V AC
120/240V AC
120/240V AC
120/240V AC
120/240V AC
120/240V AC
120/240V AC
120/240V AC
120/240V AC
120/240V AC
120/240V AC
Technical Specification
Number of Poles
Voltage Rating (maximum)
Ground Fault Sensitivity Level
Rated Short Circuit Interrupt Capacity
Rated Frequency
Trip Characteristic
Cable Size & Tightening Torque
Electrical Life
Mechanical Life
N
4
2
GFL Series RCBO
Overload Trip Curves
Characteristics B, C, D
7200
3600
2400
1200
600
480
360
240
120
t(s)
Type/
Cat. No.
GFL2B05030SN
GFL2B06030SN
GFL2B08030SN
GFL2B10030SN
GFL2B12030SN
GFL2B13030SN
GFL2B15030SN
GFL2B16030SN
GFL2B20030SN
GFL2B25030SN
GFL2B30030SN
GFL2B32030SN
GFL2B35030SN
GFL2B40030SN
60
40
20
Switch off time
UL 489
Branch Circuit Breaker
with Ground Fault Relay
Rated
Current
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
35A
40A
2+N
120/240V AC
30 mA
10 kA
50/60Hz
B
Stranded Wire: 16 - 3 AWG (1.5 mm2 - 25 mm2) @ 17.5 lb-in (2.0 Nm)
16 - 10 AWG (1.5 mm2 - 5.5 mm2) @ 17.5 lb-in (2.0 Nm)
Solid Wire:
18 - 16 AWG (1 mm2 - 1.5 mm2) @ 25 lb-in (2.8 Nm)
6000 Switching Operations
10000 Switching Operations
10
5
1
0.5
B
0.1
C
D
0.05
0.01
1
1.05 1.35
2
3
4
5
6
7 8 9 10
Rated current multiple
12 14 16 18 20
x In
Dimensions
(to convert to inches multply by 0.03937)
GFL Series RCBO
Ground Fault Trip Curve
105mm
45mm
t(s)
53mm
0.5
0.4
0.2
0.3
0.15
71mm
60mm
44mm
0.1
0.05
0.04
0.03
0.02
0.015
0.01
0.005
Weight
0.5
1
0.85 1.15
5
I∆
I∆n
353 g
1
35 Royal Road • Flemington, NJ 08822-6000 • t 908-806-9400 • f 908-806-9490 • www.altechcorp.com
GFL Series - 2 Pole + N, B Trip, 30 mA
Applicable voltage systems and wiring examples.
GFL...SN
UL 489
Branch Circuit Breaker
with Ground Fault Relay
L2
N
4
2
LINE
1
3
N
LOAD
240 V
N
120 V
120 V
L1
L1
120 V
N
4
2
LINE
3
1
N
LOAD
JUMPER
from terminal 2 to N
240 V
N
120 V
No N Connection
on Load
L2
2
35 Royal Road • Flemington, NJ 08822-6000 • t 908-806-9400 • f 908-806-9490 • www.altechcorp.com
很抱歉,暂时无法提供与“GFL2B10030SN”相匹配的价格&库存,您可以联系我们找货
免费人工找货