GFL Series - 1 Pole+N, C Trip, 30 mA
10kA UL489 Listed Branch Circuit Breaker with
Equipment Ground Fault Protection (RCBO)
The GFL Series range is a combined Branch Circuit Breaker and
Equipment Ground Fault Protector, featuring dual pole switching (live
and neutral disconnect) and designed to provide protection against
short circuits, overloads, AC ground faults (residual current faults) as
well as pulsating DC ground faults.
C.B. W/EQ.GFP
E483494
Rated
Voltage
5.0A
GFL2C050302
240V AC
6.0A
GFL2C060302
240V AC
8.0A
GFL2C080302
240V AC
10A
GFL2C100302
240V AC
12A
GFL2C120302
240V AC
13A
GFL2C130302
240V AC
15A
GFL2C150302
240V AC
16A
GFL2C160302
240V AC
20A
GFL2C200302
240V AC
25A
GFL2C250302
240V AC
GFL Series RCBO
Overload Trip Curves
3600
2400
1200
600
480
360
240
120
Electrical Life
Mechanical Life
60
40
20
Technical Specification
Number of Poles
Voltage Rating (maximum)
Ground Fault Sensitivity Level
Rated Short Circuit Interrupt Capacity
Rated Frequency
Trip Characteristic
Cable Size & Tightening Torque
Characteristics B, C, D
7200
t(s)
Type/
Cat. No.
time
Rated
Current
Switch
UL 489
Branch Circuit Breaker
with Ground Fault Relay
Ordering Information
1+N
240V AC
30 mA
10 kA
50/60Hz
C
Stranded Wire: 16 - 3 AWG (1.5 mm2 - 25 mm2) @ 17.5 lb-in (2.0 Nm)
16 - 10 AWG (1.5 mm2 - 5.5 mm2) @ 17.5 lb-in (2.0 Nm)
Solid Wire:
18 - 16 AWG (1 mm2 - 1.5 mm2) @ 25 lb-in (2.8 Nm)
6000 Switching Operations
10000 Switching Operations
10
5
1
0.5
C
B
0.1
D
0.05
0.01
2
1
1.05 1.35
Dimensions
3
4
5
6
Rated current multiple
7 8 9 10
12 14 16 18 20
xIn
GFL Series RCBO
Ground Fault Trip Curve
(to convert to inches multply by 0.03937)
45mm
35mm
t(s)
105mm
0.5
0.4
0.2
0.3
0.15
0.1
71mm
60mm
44mm
0.05
0.04
0.03
0.02
0.015
0.01
0.005
0.5
1
0.85 1.15
5
I∆
I∆n
17.5mm
Weight
220 g
1
35 Royal Road • Flemington, NJ 08822-6000 • t 908-806-9400 • f 908-806-9490 • www.altechcorp.com
GFL Series - 1 Pole+N, C Trip, 30 mA
Applicable voltage systems and wiring examples.
GFL...2
L1
240 V
400 V
400 V
L2
240 V
400 V
400Y/240V AC
LOAD
N
240 V
L3
208 V
208 V
UL 489
120 V
Branch Circuit Breaker
with Ground Fault Relay
GFL...2
L1
L2
120 V
208 V
208Y/120V AC
LOAD
N
120 V
L3
GFL...2
L2
120 V
LOAD
N
1
N
N
2
120/240V AC
240 V
LINE
120 V
L1
GFL...2
N
2
1
N
LINE
240 V
N
120 V
LOAD
L2
NOTE:
Wiring a hot leg/phase to
N terminal is not permitted.
120 V
L1
2
35 Royal Road • Flemington, NJ 08822-6000 • t 908-806-9400 • f 908-806-9490 • www.altechcorp.com