GFL Series - 2 Pole + N, C Trip, 100 mA
10kA UL489 Listed Branch Circuit Breaker with
Equipment Ground Fault Protection (RCBO)
The GFL Series range is a combined Branch Circuit Breaker and
Equipment Ground Fault Protector, featuring dual pole switching (live
and neutral disconnect) and designed to provide protection against
short circuits, overloads, AC ground faults (residual current faults) as
well as pulsating DC ground faults.
N
3
1
LINE
C.B. W/EQ.GFP
E483494
Ordering Information
Type/
Cat. No.
GFL2C05100SN
GFL2C06100SN
GFL2C08100SN
GFL2C10100SN
GFL2C12100SN
GFL2C13100SN
GFL2C15100SN
GFL2C16100SN
GFL2C20100SN
GFL2C25100SN
GFL2C30100SN
GFL2C32100SN
GFL2C35100SN
GFL2C40100SN
Rated
Voltage
120/240V AC
120/240V AC
120/240V AC
120/240V AC
120/240V AC
120/240V AC
120/240V AC
120/240V AC
120/240V AC
120/240V AC
120/240V AC
120/240V AC
120/240V AC
120/240V AC
N
4
2
GFL Series RCBO
Overload Trip Curves
Characteris
7200
B, C, D
3600
2400
1200
600
480
360
240
120
t(s)
UL 489
Branch Circuit Breaker
with Ground Fault Relay
Rated
Current
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
35A
40A
60
40
20
10
Technical Specification
Electrical Life
Mechanical Life
5
2+N
120/240V AC
100 mA
10 kA
50/60Hz
C
Stranded Wire: 16 - 3 AWG (1.5 mm2 - 25 mm2) @ 17.5 lb-in (2.0 Nm)
16 - 10 AWG (1.5 mm2 - 5.5 mm2) @ 17.5 lb-in (2.0 Nm)
Solid Wire:
18 - 16 AWG (1 mm2 - 1.5 mm2) @ 25 lb-in (2.8 Nm)
6000 Switching Operations
10000 Switching Operations
Switch
Number of Poles
Voltage Rating (maximum)
Ground Fault Sensitivity Level
Rated Short Circuit Interrupt Capacity
Rated Frequency
Trip Characteristic
Cable Size & Tightening Torque
1
0.5
C
B
0.1
D
0.05
0.01
1
1.05 1.35
2
3
Rated current
4
5
6
7 8 9 10
12 14 16 18 20
xIn
Dimensions
(to convert to inches multply by 0.03937)
GFL Series RCBO
Ground Fault Trip Curve
105mm
45mm
t(s)
53mm
0.5
0.4
0.2
0.3
0.15
71mm
60mm
44mm
0.1
0.05
0.04
0.03
0.02
0.015
0.01
0.005
Weight
0.5
1
0.85 1.15
5
I∆
I∆n
353 g
1
35 Royal Road • Flemington, NJ 08822-6000 • t 908-806-9400 • f 908-806-9490 • www.altechcorp.com
GFL Series - 2 Pole + N, C Trip, 100 mA
Applicable voltage systems and wiring examples.
GFL...SN
UL 489
Branch Circuit Breaker
with Ground Fault Relay
L2
N
4
2
LINE
1
3
N
LOAD
240 V
N
120 V
120 V
L1
L1
120 V
N
4
2
LINE
3
1
N
LOAD
JUMPER
from terminal 2 to N
240 V
N
120 V
No N Connection
on Load
L2
2
35 Royal Road • Flemington, NJ 08822-6000 • t 908-806-9400 • f 908-806-9490 • www.altechcorp.com
很抱歉,暂时无法提供与“GFL2C20100SN”相匹配的价格&库存,您可以联系我们找货
免费人工找货