GFR Series - 1 Pole+N, B Trip, 10 mA
277V AC Ground Fault Relay
with Overload Protection (RCBO)
The GFR Series is a combined Equipment Ground Fault Relay and
Supplementary Protector (RCBO), featuring dual pole switching (live
and neutral) and designed to provide protection against overloads and
AC ground faults (residual current faults) as well as pulsating DC
ground faults.
Type/
Cat. No.
GFR2B05010
GFR2B06010
GFR2B08010
GFR2B10010
GFR2B12010
GFR2B13010
GFR2B15010
GFR2B16010
GFR2B20010
GFR2B25010
Rated
Voltage
277V AC
277V AC
277V AC
277V AC
277V AC
277V AC
277V AC
277V AC
277V AC
277V AC
Technical Specification
Number of Poles
Voltage Rating (maximum)
Ground Fault Sensitivity Level
Short Circuit Withstand Rating
Rated Frequency
Trip Characteristic
Cable Size & Tightening Torque
Electrical Life
Mechanical Life
Dimensions
1+N
277V AC
10 mA
30 kA
50/60Hz
B
Stranded Wire: 16 - 3 AWG (1.5 mm2 - 25 mm2) @ 17.5 lb-in (2.0 Nm)
16 - 10 AWG (1.5 mm2 - 5.5 mm2) @ 17.5 lb-in (2.0 Nm)
Solid Wire:
18 - 16 AWG (1 mm2 - 1.5 mm2) @ 25 lb-in (2.8 Nm)
6000 Switching Operations
10000 Switching Operations
Ground Fault Sensing
& Relaying Equipment
E483493
GFR Series RCBO
Overload Trip Curves
Characteristics B, C, D
7200
3600
2400
1200
t(s)
Rated
Current
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
600
480
360
240
120
60
40
Switch off time
UL 1077
Ground Fault Relay
with Overload Protection
Ordering Information
20
10
5
1
0.5
(to convert to inches multply by 0.03937)
B
0.1
85mm
C
D
0.05
45mm
35 mm
0.01
2
1
1.05 1.35
3
4
5
6
7 8 9 10
71mm
60mm
44mm
Rated current multiple
12 14 16 18 20
n
xI
t(s)
GFR Series RCBO
Ground Fault Trip Curve
17.5mm
Weight
217 g
0.5
0.4
0.2
0.3
0.15
0.1
GFR Series RCBO Short Circuit Withstand Rating
V
1+N Pole
277V AC
I
≤20A
IR
10kA
>20A
10kA
Backup
None
Class J Fuse 250A or lower
Altech L Series Branch Circuit Breaker
Altech R Series Supplementary Protector
0.05
0.04
0.03
0.02
0.015
0.01
0.005
0.5
1
0.85 1.15
5
I∆
I∆n
1
35 Royal Road • Flemington, NJ 08822-6000 • t 908-806-9400 • f 908-806-9490 • www.altechcorp.com
GFR Series - 1 Pole+N, B Trip, 10 mA
Applicable voltage systems and wiring examples.
L1
GFR2
277 V
480 V
480 V
L2
277 V
480 V
LOAD
N
277 V
L3
L1
400 V
400 V
Ground Fault Relay
with Overload Protection
240 V
GFR2
L2
UL 1077
240 V
400 V
LOAD
N
240 V
L3
L1
120 V
208 V
GFR2
208 V
L2
120 V
208 V
LOAD
N
120 V
L3
LOAD
N
2
N
L1
120 V
1
N
LINE
240 V
120 V
L2
GFR2
NOTE:
Wiring a hot leg/phase to
N terminal is not permitted.
2
35 Royal Road • Flemington, NJ 08822-6000 • t 908-806-9400 • f 908-806-9490 • www.altechcorp.com
很抱歉,暂时无法提供与“GFR2B05010”相匹配的价格&库存,您可以联系我们找货