    TR-11BY6315A - UL1077 Recognized Supplementary Protector/ Circuit Breaker for Equipment - Altech cor...

  • 详情介绍
  • 数据手册
  • 价格&库存
TR-11BY6315A 数据手册
Altech UL1077 TR11 Series E209569 up to 12 Amps UL1077 Recognized Supplementary Protector/ Circuit Breaker for Equipment Applications: Protection of single phase Motors, Transformers, UPS, Power strips, Solenoids etc., against damage due to overcurrent conditions. Current Rating Rated Voltage Initial insulation resistance Dielectric strength Overload Switching Capacity Maximum Breaking Capacity Power Loss Operating Temperature Operational Life at 2xIn Limited short circuit current Terminals Applicable Standards Approvals Accessories 0.5 -16.0A 240V AC, 50/60Hz, 32V DC / 24V DC (VDE) (As per EN 60934) > 100 M ohms. (As per EN 60934) 1.5 KV for One minute. 6 In ~ up to 9.0A (As per EN 60934) 4 In - up to 12.0A 60A Max. ~ from 10.0A to 12.0A 60A Max. - from 10.0A to 12.0A 8x In for 6.0A 1 - 2 Watts Maximum 60°C Ambient 1000 Cycles 1000 Amps PC 1 Operating Characteristic (min) 60 30 20 10 5 1 (S) 50 20 10 5 2 1 Trip time 0.5 0.2 0.1 1.05 1.32 2 3 45 8 10 0.25” Quick connect EN 60934, CSA 22.2 No. 235, UL-1077 up to 16.0 A upto 12.0A Dust Cover, DC-TR11 C (see page 14) Time Current Characteristics: The standard characteristic is valid for ambient temperatures of +23°C. If the device is to be used in an ambient temperature other than +23°C, allowances must be made when selecting the current rating according to the following guidelines: Ambient temp. °C Correction Factor Example : -20 -5 0 +10 0.96 : : : : : +20 1 +30 1.05 +40 1.12 +50 1.2 +60 1.3 0.8 0.88 0.9 Normal Continuous Current Ambient Temperature Correction Factor Recommended Current Rating Select the nearest 1.8A 40°C 1.12 1.8 x 1.12 = 2.016 2.0A Multiple of Rated Current Rated current Ambient Temperature 6A 23°C 16 Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com Application Examples: Protection of single phase Motors, Transformers, UPS, Power strips, Solenoids etc., against damage due to overcurrent conditions. TR-11 Characteristics & Mounting Options E209569 Type/ Cat. No. TR-11CX630.5A TR-11CX630.9A TR-11CX631A TR-11CX631.2A TR-11CX631.5A TR-11CX631.8A TR-11CX632A TR-11CX632.2A TR-11CX632.5A TR-11CX632.7A TR-11CX633A TR-11CX633.3A TR-11CX634A TR-11CX635A TR-11CX636A TR-11CY636.5A TR-11CY637A TR-11CY638A TR-11CY639A TR-11CY6310A TR-11CY6312A TR-11CY6315A TR-11CY6316A Type/ Cat. No. up to 12 Amps Rated Current Type/ Cat. No. Standard Pack: 10 Weight: 0.27kg (0.6 lb.) Central Mounting Rated Current 0.5A 0.9A 1.0A 1.2A 1.5A 1.8A 2.0A 2.2A 2.5A 2.7A 3A 3.3A 4A 5A 6A 6.5A 7A 8A 9A 10A 12A 15A 16A Rated Current Standard Pack: 10 Weight: 0.27kg (0.6 lb.) Wing Clips* Rated Current Type/ Cat. No. Standard Pack: 10 Weight: 0.27kg (0.6 lb.) Snap Fitting* Standard Pack: 10 Weight: 0.27kg (0.6 lb.) Integral Mounting* * SPECIAL ORDER ONLY. Contact Altech for more details. PCB Mounting and additional Shunt Terminal available, please contact Altech. Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com Altech UL1077 17 Altech UL1077 DIA 4 A/F 13 MAXIMUM TORQUE 0.5 Nm 10 9 M10 X 1 13.3/14.5 10.8/12 6 PANEL CUTOUT 19 3 11 27.5 10.2 9 7 0.8 15 9.4 8.7 10.2 Alternate 1 DIA 4 14.5 DIA 12 12 3 Alternate 2 PANEL CUTOUT 15 9+0.1 15.5 27.5 11 19 7 12.7 15.2 13.9 +0.1 0.8 15 DIA 4 11.2 13 12 8.5 PANEL CUTOUT 25.6 21.7 X +0.1 11.3 +0.1 14 11 2 0.8 15 DIA 4 10 9 11.2 11 27.5 19 0.8 18 Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com 7 85 .2 7 Ø1 5 .5
TR-11BY6315A
### 物料型号 - 型号:UL1077系列

### 器件简介 - Altech UL1077系列过载保护器/电路断路器,用于保护单相电机、变压器、不间断电源(UPS)、电源条、电磁阀等设备免受过电流损害。

### 引脚分配 - 引脚:0.25英寸快速连接

### 参数特性 - 电流额定值:0.5-16.0A 240V交流电,50/60Hz,32V直流电/24V直流电(VDE) - 额定电压:未提供具体数值 - 初始绝缘电阻:>100 M欧姆(符合EN 60934标准) - 耐压强度:1.5 KV持续1分钟(符合EN 60934标准) - 过载开关容量:4倍电流额定值,最高12.0A(符合EN 60934标准) - 最大断开容量:6.0A以下8倍电流额定值,6.0A及以上60A最大 - 功率损耗:1-2瓦特 - 操作温度:环境温度最高60°C - 2倍电流额定值下的操作寿命:1000次循环 - 限制短路电流:1000安培PC1

### 功能详解 - 该系列断路器具有标准特性,适用于环境温度+23°C。如果设备在不同于+23°C的环境温度下使用,需要根据以下指南调整电流额定值: - 不同环境温度下的修正系数:-20°C为0.8,-5°C为0.88,0°C为0.9,10°C为0.96,20°C为1.05,30°C为1.12,40°C/50°C/60°C为1.2/1.3。 - 例如,如果正常连续电流为1.8A,环境温度为40°C,则修正系数为1.12,推荐的电流额定值为1.8A x 1.12 = 2.016A,应选择最接近的2.0A。

### 应用信息 - 用于保护单相电机、变压器、不间断电源(UPS)、电源条、电磁阀等设备免受过电流损害。

### 封装信息 - 符合标准:EN 60934, CSA 22.2 No. 235, UL-1077 - 认证:最高16.0A,最高12.0A - 配件:防尘罩,DC-TR11 C(见第14页)