High Voltage DC Contactor
ALEV200 Series
500A+/900VDC
Product Data Sheet
Features
HIGH CURRENT CARRY AND HIGH VOLTAGE
Inert gas filled arc chamber suitable for high
voltage switching
Sealing Type: Epoxy/Resin
-Bottom mount/side mount options
available
COMPACT STRUCTURE, LOW NOISE
Small, low-profile designs with low noise while
carrying or switching loads
COIL ECONOMIZER
Economized coils for low power consumption
SAFE FOR EXPLOSIVE ENVIRONMENTS
No arc leakage due to a hermetically sealed
design
HIGH RELIABILITY DESIGN
Hermetic sealing creates a stable environment
for high voltage switching
NO SPECIFIC MOUNTING ARRANGEMENT
Mountable in any orientation without reduction of
performance
VARIOUS APPLICATIONS
Battery Disconnect, EV Charging, Energy
Storage Systems, Photo Voltaic, Power Control,
Circuit Protection and much more
Nomenclature
Series code:
“ALEV200” = ALEV200 Series
Coil Voltage Code:
“B” = 12VDC
“C” = 24VDC
“E” = 48VDC
“F” = 72VDC
Options (applied in this order):
Blank = Std. Options (Bottom Mount, Coil Wires,
Without Aux. Contact & Polarized Load Terminals)
“A” = With Aux. Contact (SPST-NO)
“S” = Side Mount Version
“T” = Threaded Coil Terminal (not available with Aux contact)
P age 1
Certification Information
1. Meet RoHS (2011/65/EU)
2. CE certified
ALEV200
C
T
High Voltage DC Contactor
ALEV200 Series
500A+/900VDC
Product Data Sheet
OPERATE/RELEASE TIME
MAIN CONTACT
Contact Arrangement
1 Form X (SPST-NO)
Operating Voltage
12-900VDC
Rated current
500A
Max. Short Circuit Current
2,000A@320VDC 1 cycle
Withstand
Voltage *1
Insulation
Resistance*1
Between
Open
Contacts
4,000 VDC, ≤ 1mA
Between
Contacts
to Coil
2,500VAC, ≤ 1mA
Terminal
to
Terminal
Terminals
to Coil
Voltage Drop (@200A)
New product: Minimum 100
MΩ @500VDC
≤80mV
Close (not including bounce)
30ms, Max. @20°C
Release Time
12ms, Max. @20°C
ENVIRONMENTAL DATA
Shock
11ms % Sine
Operating
20G Peak
Vibration
Sine, Peak
20G
80—2,000Hz
Operating Temperature
-40~+85°C
Humidity
5%~85%RH
Weight
1.32 lb. (0.60 kg)
Note:
*1: Does not meet Dielectric & IR after test.
AUXILARY CONTACT
EXPECTED LIFE
200A @ 450VDC
5000 Cycles
Mechanical Life
200,000 Cycles
Aux. Contact Arrangement
1 Form A
Aux. Contact Current Max
2A@30VDC/3A@125VAC
Aux. Contact Current Min
100mA@8V
Aux. Contact Resistance
0.417 ohms @320VDC
0.150 ohms @125VAC
Current Carry Curve
COIL DATA
Note:
*When we using a higher conductor size, the current
will increase
P a ge 2
Voltage Rating
12 VDC
24 VDC
48 VDC
72 VDC
Voltage (Max.)
15 VDC
30 VDC
60 VDC
90 VDC
(Max.) Pick-up
Voltage ( 20 ˚C)
9.0 VDC
19.0 VDC
38.0 VDC
57.0 VDC
(Min.) Drop-out
Voltage (20 ˚C)
0.5 - 4.0
VDC
1.0 - 6.0
VDC
3.0 - 10.0
VDC
4.0 - 14.0
VDC
Coil Current
(20˚C, Nominal
Voltage)
1.1A
0.6A
0.3A
0.2A
Rated Coil
Resistance±5%
(20˚C)
11 Ω
40 Ω
145 Ω
357 Ω
High Voltage DC Contactor
ALEV200 Series
500A+/900VDC
Product Data Sheet
Outline Dimensions : inches (mm)
A. Bottom Mount:
2.69±0.02
[68.3±0.6]
+C Positive
Terminal
Two M8 x 1.25 Screw Terminal,
2 Washers,2 Lock Washers, 2 Nuts
Torque: 80-100 lb.in (8.8-11 N.m)
1.05±0.02
[26.7±0.6]
-C Negative Terminal
Two #10 Mounting Holes,
Torque:15-30 lb.in(1.7-3.3N.m)
Ø0.23±0.01
[Ø5.8±0.3]
Ø2.29±0.02
[Ø58.2±0.6]
Coil Wires: Black
Aux. Contact (Opt.): White wires
Wire Length 15.4±0.4 [390±10]
2.01±0.02
[51.2±0.6]
3.70±0.04
[94.1±1.0]
3.07±0.04
[78.1±1.0]
3.06±0.02
[77.7±0.6]
Ø2.01±0.02
[Ø51.0±0.6]
0.50±0.02
[12.7±0.6]
2.69±0.02
[68.3±0.6]
+C Positive
Terminal
1.05±0.02
[26.7±0.6]
Two M8 x 1.25 Screw Terminal,
2 Washers,2 Lock Washers, 2 Nuts
Torque: 80-100 lb.in (8.8-11 N.m)
-C Negative Terminal
Two #10 Mounting Holes,
Torque:15-30 lb.in(1.7-3.3N.m)
Ø0.23±0.01
[Ø5.8±0.3]
Ø2.29±0.02
[Ø58.2±0.6]
Coil Terminals
Two #10 - 32 Screw Terminal,
2 Washers,2 Lock Washers, 2 Nuts
Torque: 15-30 lb.in (1.7-3.4 N.m)
3.70±0.04
[94.1±1.0]
3.07±0.04
[78.1±1.0]
3.06±0.02
[77.7±0.6]
0.50±0.02
[12.7±0.6]
Pa ge 3
0.6±0.02
[15.3±0.6]
3.41±0.04
[86.7±1.0]
Ø2.01±0.02
[Ø51.0±0.6]
High Voltage DC Contactor
ALEV200 Series
500A+/900VDC
Product Data Sheet
B. Side Mount:
0.50±0.02
[12.7±0.6]
Two M8 x 1.25 Screw Terminal,
2 Washers,2 Lock Washers, 2 Nuts
Torque: 80-100 lb.in (8.8-11 N.m)
1.04±0.02
[26.4±0.6]
1.24±0.02
[31.5±0.6]
+C Positive
Terminal
2.38±0.02
[60.5±0.6]
-C Negative
Terminal
Ø2.29±0.02
[Ø58.2±0.6]
3.07±0.04
[78.1±1.0]
Ø0.23±0.01
[Ø5.8±0.3]
Coil Wires: Black
Aux. Contact (Opt.): White wires
Wire Length 15.4±0.4 [390±10]
3.70±0.04
[94.1±1.0]
2.69±0.02
[68.3±0.6]
Ø2.01±0.02
[Ø51.0±0.6]
Two #10 Mounting Holes,
Torque:15-30 lb.in(1.7-3.3N.m)
3.06±0.02
[77.7±0.6]
0.50±0.02
[12.8±0.6]
1.05±0.02
[26.7±0.6]
1.24±0.02
[31.5±0.6]
+C Positive
Terminal
2.39±0.02
[60.5±0.6]
Ø2.29±0.02
[Ø58.2±0.6]
Coil Terminals
Two #10 - 32 Screw Terminal,
2 Washers,2 Lock Washers, 2 Nuts
Torque: 15-30 lb.in (1.7-3.4 N.m)
3.07±0.04
[78.1±1.0]
Two M8 x 1.25 Screw Terminal,
2 Washers,2 Lock Washers, 2 Nuts
Torque: 80-100 lb.in (8.8-11 N.m)
-C Negative
Terminal
0.6±0.02
[15.3±0.6]
3.70±0.04
[94.1±1.0]
3.41±0.04
[86.7±1.0]
Ø0.23±0.01
[Ø5.8±0.3]
2.69±0.02
[68.3±0.6]
3.06±0.02
[77.7±0.6]
[Ø51.0±0.6]
Two #10 Mounting Holes,
Torque:15-30 lb.in(1.7-3.3N.m)
*Note: The wire gage is 22 AWG.
*When stud terminals are specified for coil connections, the
electrical connection is made at the base of the stud.
Pa ge 4
Ø2.01±0.02
High Voltage DC Contactor
ALEV200 Series
500A+/900VDC
Product Data Sheet
Application Notes
1.
Be sure to use split washer to prevent nuts from loosening, all the terminals or copper conductor must be in
direct contact with the contactor’s terminals. Nut tightening torque is specified below. Exceeding the maximum
torque can lead to product failure.
• Contact torque (M8): 80 - 100 lb.in (8.8 - 11 N.m)
• Mounting torque: 15 - 30 lb.in (1.7 - 3.3 N.m)
2.
Contact terminals are polarized so refer to drawing during connecting. We suggest using a varistor rather than
diode as a surge protector.
3.
Do not use if dropped.
4.
Avoid installing in a strong magnetic field (close to a transformer or magnet), or near a heat source.
5.
Electrical life:
Use per load capability and life cycle limits so as not to cause a function failure (treat the contactor as a
product with specified life and replace it when necessary). It is possible to make parts burn around the
contactor once operating failure occurs. It is necessary to take layout into account and to make sure power
shall be cut off within 1 second.
6.
Lifetime of internal gas diffusion The contactor is sealed and filled with gas, lifetime of gas diffusion is
determined by temperature in contact chamber (ambient temperature + temperature generated by contact
operation). Operate only in an ambient temperature from -40 to +85 ˚C.
7.
Drive power must be greater than coil power or it will reduce performance capability.
8.
Avoid debris or oil contamination on the main terminals to optimize contact and avoid excess heat generation.
9.
After continuous rated voltage / current has been applied to the coil and contacts, turning off the coil and
immediately re-energizing the coil will result in a higher pick-up voltage than the rated value. This is due to
increased coil resistance (coil temperature rise) of the device.