4-20 mA configurable vibration
transmitter module
iT300
The iT300 transmitter provides an easy means to connect a standard IEPE vibration
sensor to a PLC, DCS or SCADA system. The transmitter’s input provides power
to and measures the signal from either an accelerometer, piezovelocity sensor or
dual output sensor. The input circuitry has a wide frequency response, capable of
measuring signals between 0.2 Hz and 20,000 Hz.
Band 1
(adjustable)
Band 2
(adjustable)
The transmitter has two
independent processing bands
with flexible mapping options
to two separate 4-20 mA
analog outputs. The processing
channels contain selectable
integration, allowing input from
accelerometers to be output
as acceleration or velocity.
Selectable band filters and
detector types make it easy to
tailor the processing to specific
machines or applications.
System architecture – input/output
Key features
• Accepts input from
accelerometers (single or
dual output) or piezovelocity
sensors
• Input signal is split into
two independent processing
bands
• Measures real-time sensor
bands, BOV, true peak and
temperature (if applicable)
• Built-in web server for
custom configuration of
bandwidth/detection type
• 2 x 4-20 mA outputs, userdefined
Power input
4-20 mA outputs
• Text field for user entry of
machine information
Input/output µprocessor
• Configurations can be stored
• Selectable speed range
• Manufactured in an
approved ISO 9001 facility
Certifications
Note: Due to continuous process improvement, specifications are subject to change without notice.
This document is cleared for public release.
Wilcoxon Sensing Technologies
An Amphenol Company
99256 Rev.D.1 10/18
8435 Progress Drive
Frederick, MD 21701
USA
Tel: +1 (301) 330-8811
Fax: +1 (301) 330-8873
info@wilcoxon.com
buy.wilcoxon.com
www.wilcoxon.com
1
4-20 mA configurable vibration
transmitter module
iT300
SPECIFICATIONS
INPUT
MAPPABLE OUTPUTS
IEPE sensor type
Temperature sensor input
Single-ended, DC coupled
10 mV/°C
4-20 mA output
2 user-configurable, based on (5)
mappable options
IEPE power source
+24 VDC, 4.5 mA
Max loop resistance
500 Ω
Sensitivity range:
acceleration
velocity
9 - 11,000 mV/g
9 - 11,000 mV/ips
Full scale input range
± 10 VDC
Output scaling1:
acceleration
velocity
displacement
g (m/sec2) - rms, peak, peak-peak
ips (mm/sec) - rms, peak, peak-peak
mils (mm) - rms, peak, peak-peak
Frequency response
Fmax options
0.2 - 20 kHz (-3 dB, -0.1 dB)
200, 500 Hz; 1, 2, 5, 10, 20 kHz
Accuracy
± 0.2% of full scale, 100 Hz
Output ranges1:
acceleration
velocity
displacement
1 - 50 g (10 - 500 m/sec2)
0.1-5 ips (2-100 mm/sec)
10 - 200 mils (0.2 - 5.0 mm)
ADC sampling rate
48 kbps, 24 bits delta-sigma
ENVIRONMENTAL
FFT resolution, windowing
1,600 lines, Hanning window
Dynamic range
>90 dB
CONFIGURABLE OPTIONS
Frequency bands 1 and 2
Sensor unit1 or single integration2
Fstart3
Fstop3
Detection type: rms, peak, pk-pk
Fixed measurement bands
True peak, BOV, temperature4
Temperature range
–40° to +70°C
(storage: –40°C to +85°C)
Power
11 - 32 VDC, 3.8 watts max
(158 mA at 24 VDC)
Isolation
500 VAC
Connection type
screw terminal, 14 - 24 AWG
Mounting
35 mm DIN rail
Dimensions
W x H x D: 22.5 x 99.2 x 114.5 mm
Notes: Based on IEPE sensor type (accelerometer or piezovelocity).
2 Acceleration signal to velocity, velocity signal to displacement.
3 The available selections are affected by the Fmax setting.
4 786T style sensors only.
1
System architecture
PLUS +24 VOLT POWER
TOP TERMINAL BLOCK
CONNECTORS
POWER SUPPLY GROUND
REAR
POWER CONNECTION,
#17 & #18
MIDDLE
2 X 4-20 mA OUTPUT LOOPS
FRONT
BLANK
Terminal numbers and
signal assignments
IO Port
Vibration sensor
1 – No connection
2 – Temperature sensor (in T+)
3 – Signal in / Sensor Power (IN+)
4 – Circuit Common (COM)
Temperature
dynamic output
5 – Circuit Common (COM)
6 – Temperature out (T)
Sensor dynamic
output
7 – Circuit Common (COM)
8 – Sensor out (SENS)
4-20 mA Loop B
13 – B14 – B+
4-20 mA Loop A
15 – A16 – A+
Power input
17 – P18 – P+
Not used
19 –
20 –
REAR PANEL
MOUNTED T-BUS
CONNECTOR
(OPTIONAL)
RJ-45 CONNECTOR
FOR INTERFACING WITH PC
EQUIPPED WITH SUPPORTED WEB
BROWSER TO CONFIGURE MODULE
BOTTOM
TERMINAL BLOCK
CONNECTORS
FRONT
REAR
P+
PNO CONNECTION
D(A)
D(B)
DYNAMIC OUTPUT
SENSOR CONNECTION
Note: Due to continuous process improvement, specifications are subject to change without notice.
This document is cleared for public release.
Wilcoxon Sensing Technologies
An Amphenol Company
99256 Rev.D.1 10/18
8435 Progress Drive
Frederick, MD 21701
USA
Tel: +1 (301) 330-8811
Fax: +1 (301) 330-8873
info@wilcoxon.com
buy.wilcoxon.com
www.wilcoxon.com
2
Built-in web server
iT300
Save & Enable
Changes
Settings changes do not take effect until the "Save & Enable Changes" button is pressed
Abandon
Changes
Login
Login required before any changes can be made
Machine Information
Location
Machine ID
Machine Location
Machine Name
Machine Name
Measurement Point
IEPE Power
Machine ID
MACHINE INFORMATION
Measurement Point
User entry of machine identity
Sensor Input
Sensor Type
Acceleration
Sensitivity (mV/g)
100
Averaging Time
1 sec
5 kHz
Enabled
Serial Number
SENSOR INPUT
Sensor Serial Number
User entry of sensor parameters
Frequency Range
F max
F min
FREQUENCY RANGE
5 Hz
User selection of frequency
analysis range
Sensor Band Configuration
Output Type
F start (Hz)
Band 1
Velocity
5
Band 2
Acceleration
5
F stop (Hz)
5000
5000
Detector Type
RMS
RMS
SENSOR BAND CONFIGURATION
Analysis band type and
frequency limits
Measurement Results
Present
Level
Result Unit
Band 1
in/sec
1.000 in/sec
Band 2
g
1.000 g
True Peak
g
1.417 g
Temperature
Fahrenheit
Results from each band in
selectable units
32.0 °F
Volts
BOV
MEASUREMENT RESULTS
12.1 Volts
Current Loops
Loop Source
Full Scale
Loop A
Band 1
5
Loop B
Disabled
5
Level
in/sec
Destination
Force Loop
Force Value (mA)
7.20 mA
Loop A Dest
10
0.00 mA
Loop B Dest
10
CURRENT LOOPS
4-20 mA mapping
Network Configuration
IP Address
192.168.0.100
Default Gateway
192.168.0.1
NETWORK CONFIGURATION
Subnet Mask
255.255.255.0
MAC Address
00:50:C2:19:BF:FB
Module Information
Model
iT300
Hardware Revision
D8
Serial Number
ENG2
Firmware Revision
1.01
Change
Password
Load Configuration
from File
Save Configuration
to File
Restore Factory
Defaults
Update
Firmware
Note: Due to continuous process improvement, specifications are subject to change without notice.
This document is cleared for public release.
Wilcoxon Sensing Technologies
An Amphenol Company
99256 Rev.D.1 10/18
8435 Progress Drive
Frederick, MD 21701
USA
Default configuration. Consult full
manual on configuring your PC
network adaptor.
Default user: user
Default password: admin
Remember to save your changes
to have new values take effect.
Tel: +1 (301) 330-8811
Fax: +1 (301) 330-8873
info@wilcoxon.com
buy.wilcoxon.com
www.wilcoxon.com
3
很抱歉,暂时无法提供与“IT300”相匹配的价格&库存,您可以联系我们找货
免费人工找货